Group 3.9: Protections
6.1.10.1
Group 3.9.1: General
P3.8.6
Superv2 Mode
0
2
0
1436 See P3.8.2
P3.8.7
Superv2 Limit
-50.00
50.00
Varies
40.00
1437 See P3.8.3
P3.8.8
Superv2 Hyst
0.00
50.00
Varies
5.00
1438 See P3.8.4
Table 72. General protections settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.1.2
External fault
0
3
2
701
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
P3.9.1.3
InputPhase Fault
0
1
1
730
0= 3 Phases support
1= 1 Phase support
P3.9.1.4
Undervoltage Flt
0
1
0
727
0 = Fault stored in history
1 = Fault not stored in history
P3.9.1.5
OutputPhase Flt
0
3
2
702
See P3.9.1.2
P3.9.1.6
FieldbusComm Flt
0
4
3
733
0 = No action
1 = Alarm
2 = Alarm, PresetFreq
3 = Fault (Stop according to
stop mode)
4 = Fault (Stop by coasting)
P3.9.1.7
SlotComm Flt
0
3
2
734
See P3.9.1.2
P3.9.1.8
Thermistor Fault
0
3
0
732
P3.9.1.9
PID SoftFill Fault
0
3
2
748
P3.9.1.10
PID Supervision
0
3
2
749
P3.9.1.11
ExtPID Supervision
0
3
2
757
See P3.9.1.2
P3.9.1.13
PresetAlarmFreq
Hz
25.00
183
This frequency used when
fault response (in Group 3.9:
Protections) is Alarm+preset
frequency
P3.9.1.14
STO Fault
0
3
3
775
Defines drive operation when
STO function has been acti-
vated (eg. Emergency stop
button has been pressed).
Table 71. Supervision settings
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......