vacon • 75
Parameters
6
P3.3.1.7
Keypad Ref Sel
1
9
2
121
Selection of ref source when
control place is keypad:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.8
Keypad Reference
0.00
Hz
0.00
184
The frequency reference can
be adjusted on the keypad
with this parameter.
P3.3.1.9
Keypad Direction
0
1
0
123
Motor rotation when control
place is keypad
0 = Forward
1 = Reverse
P3.3.1.10
Fieldbus Ref Sel
1
9
3
122
Selection of ref source when
control place is Fieldbus:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
Table 51. Frequency reference parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description