6
vacon • 37
Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Example of an exception response
In an exception response, the Slave sets the
most-significant bit (MSB)
of the function code to
1. The Slave returns an exception code in the data field.
Command Master - Slave:
Message frame:
Exception response:
Answer Slave - Master:
Reply frame:
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
04 hex Function 4 hex (= 4)
DATA
Starting address HI 17 hex Starting address 1770 hex (= 6000)
Starting address LO 70 hex
No. of registers HI
00 hex Invalid number of registers 0005 hex (= 5)
No. of registers LO
05 hex
ERROR
CRC HI
34 hex
CHECK
CRC LO
66 hex CRC field 3466 hex (=13414)
01 04
17
70 00
05
34 66
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
84 hex Most significant bit set to 1
ERROR CODE
04 hex Error code 04 => Slave Device Failure
ERROR CRC HI
42 hex CRC field 42C3 hex (= 17091)
CHECK CRC LO
C3 hex
01 84
04
42 C3