ENGLISH

34

End of Stroke Inputs

City4

control unit allows connecting 2 mechanical ends of stroke

(normally closed contacts) which are activated by the door motion and
showing to the control unit that each door reached its position of
complete opening or closing. 

no

end of stroke inputs are disabled 

StoP

inputs enabled: the gate stops near the limit switches 

rALL

inputs enabled: the gate starts the slowdown phase (menu 
t.rAL) near the limit switches. 

Photocell Shadow Zone

In some installations it may occur that the gate door
passes before the photocells, so breaking their beam.
In this case, the gate cannot complete its closing cycle. 
Through this function, photocells can be temporarily 
disabled, so allowing the door passage. 
The door travel, during which photocells are not active,
is measured in seconds from the beginning of the door
closing and starting from the max. opening position.

The shadow zone limits are automatically set during the
self-learning phase (see paragraph page 27), provided
that this function has been enabled in advance by
setting any time in the menus i.ShA and F.ShA (also
0.0”). If it is necessary to set the limits manually,
follow these instructions:

• Completely open the gate with the disabled function,

then activate its closing and see after how many 
seconds the photocell operates.

• Set up a slightly lower time into 

i.ShA

menu and a 

slightly higher time into 

F.ShA

menu.

• During the time between 

i.ShA

and 

F.ShA

, photocells will not be active during the closing phase.

m

WARNING:

This function is active in case the ends of stroke have been fitted and enabled and if the START IN OPENING has

been disabled.

m

WARNING:

any improper use of this function may jeopardize the gate safe use. V2 recommends what follows: 

• Make use of this function only in case the door passage before the photocells is actually unavoidable.
• Set up the shadow zone limits as tight as possible, complying with the necessary margins to compensate any possible door speed 

difference.

Safety ribbon input

This menu allows the enabling of the safety ribbons and the
setting of their operation logic (see paragraph “Installation”).

no

Input disabled (ignored by the control unit).
No jumper with the common is required.

StAn

input enabled for standard safety ribbons with 
n.c. contact

rESi

input enabled for conductive rubber safety ribbons 
with nominal resistance 8,2 kohm.

After having selected the type of safety edge, it is necessary to
indicate the phase of the cycle in which it must be enabled:

AP.Ch

Input enabled in opening and closing phase

AP

Input enabled only in opening phase

Ch

Input enabled only in closing phase

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for city4

Page 1: ...LLE POUR LE CONTROLE D UN MOTEUR A 230V 120V UNIVERSELLE ZENTRALE EINHEIT ZUM STEUERN EINES 230V 120V MOTORS CUADRO DE MANIOBRAS DIGITAL UNIVERSAL PARA UN MOTOR 230V 120V I GB F D E City4 Pr 2 0 IL n...

Page 2: ...ISTRUZIONI 1 INSTRUCTIONS 23 NOTICES 45 ANLEITUNGEN 67 INSTRUCCIONES 89 I GB F D E...

Page 3: ...RTESY LIGHTS 23 ELECTRIC LOCK 23 PHOTOCELL 23 SAFETY RIBBONS 24 END OF STROKE 24 STOP 24 ACTIVATION INPUTS 24 PLUG IN RECEIVER 25 EXTERNAL AERIAL 25 ADI INTERFACE 25 CONTROL PANEL 25 USE OF DOWN MENU...

Page 4: ...We recommend to make use of an emergency button to be installed by the automation connected to the control unit STOP input so that the gate may be immediately stopped in case of danger Always remembe...

Page 5: ...120V 40W for model City4 120V blinker equipped with intermittence inside Connect blinker cables to terminals G6 and G7 of the control unit COURTESY LIGHTS Thanks to the output COURTESY LIGHT the cont...

Page 6: ...e again you will need a start command if the start function in pause is disabled it will be temporarily enabled to allow the gate release Connect the stop switch cables between terminal P3 and P4 of t...

Page 7: ...ANS433 or ANSGP433 in order to guarantee the maximal range Connect the antenna hot pole to terminal A2 of the control unit and the braiding to terminal A1 INTERFACE The ADI Additional Devices Interfac...

Page 8: ...by holding down the UP key items will scroll fast backwards until item dEF is viewed In this way you can quickly reach either the top or bottom of the list There are the following three kinds of menu...

Page 9: ...abled or if you realize that they do not signal the position to the control unit you must send a START command must be sent when the gate reaches its fully closed position mWARNING if the function PHO...

Page 10: ...ceives a Start Pedestrian command it will use this time to close the gate Max allowed time to be setup is t CH1 To avoid that the door does not close completely we recommend to setup a longer time tha...

Page 11: ...otion Motor power This menu allows adjusting the motor power The displayed value is the percentage of max motor power m WARNING In case an hydraulic motor is used set value 100 Start off When the gate...

Page 12: ...Select option no to set up the always open operation logic Slowing down time In case this function is enabled during the last seconds of motion the control unit will give motor a reduced power command...

Page 13: ...ways ignored during a total opening Closing after transit During the automatic operation the pause count down starts from the set up value each time a photocell operates during the pause If the photoc...

Page 14: ...opens after the set time biSt BISTABLE the relay changes each time a remote control arrives on channel 4 Mon MONOSTABLE the relay keeps closed until a signal given by the remote control on channel 4 a...

Page 15: ...for the closing phase only Warning if you select this option you must disable photocell test Test of safety devices In order to achieve a safer operation for the user the unit performs a safety devic...

Page 16: ...the disabled function then activate its closing and see after how many seconds the photocell operates Set up a slightly lower time into i ShA menu and a slightly higher time into F ShA menu During th...

Page 17: ...f stroke Obstacle Sensor Enabling This menu allows the sensitivity adjustment of the obstacle sensor over 10 levels from 1 to 10 By setting up 0 sensors will be disabled increasing the value the sensi...

Page 18: ...e setup be increased or decreased of 1000 units The previous displayed count will get lost Signal of service required As soon as the counter of cycles before the next request for service is zero the c...

Page 19: ...1 Remove the extractable part containing terminals P1 to P14 OVERLOAD led will switch off 2 Remove the overload cause 3 Reinsert the terminal board extractable part and check that this led is not on...

Page 20: ...E 0 0 3 0 Fast closing time after slowing down during closing 1 0 0 0 St AP Start in opening PAUS PAUS no Start command is not available ChiU Command close gate PAUS Stop the gate and goes in pause St...

Page 21: ...bled the control unit ignores it rESi Input enabled for conductive rubber ribbons StAn Input enabled for standard safety ribbons with normally closed contact AP Ch Input enabled in opening and closing...

Page 22: ...ng end of stroke N C contact P9 Common P10 P11 Power output 24 VAC for photocells and other accessories P11 P12 Photocell TX power supply for functional test P13 P14 Electric lock 12VAC G1 G2 Courtesy...

Reviews: