![V-TAC VT-524-S Instruction Manual Download Page 3](http://html1.mh-extra.com/html/v-tac/vt-524-s/vt-524-s_instruction-manual_3095803003.webp)
4) Drill out the two fixing holes located on the back of the luminaire, hold the luminaire in the required location and use these
holes as a template mark on the location of the fixing holes on the wall/ceiling (Please note when drilling fixing holes in the
wall/ceiling be careful not to damage concealed wires or pipes.)
5) Fix the luminaire to the wall/ceiling using suitable screws and fixings (not supplied).
6) Connect the mains supply wiring as follows.
7) For component protection in transit and user safety the luminaire battery fuse is supplied in the fitting.
8) When all connections have been made reassemble the fitting completely.
9) Restore the supply and check that the Green LED indicator illuminates to confirm the batteries are charging. There are
three possible reasons when the green LED indicator does not light up:
1) there is no power supply AC220-240V,
2) the batteries are not properly connected to the PCB,3) the batteries are not being charged.
10) Allow a short period for partly charging the batteries and then isolate the mains supply to the fitting in order to check the
correct operation of the fitting in emergency mode. After 36 hours on continuous charge (and only at a safe time) a mains
failure should be simulated to ensure that the fitting illuminates for its rated emergency duration.
The luminaire will have a 1-hour backup after 14 hours charging and will be fully charged after 24 hours (first charge 36
hours)
MAINTENANCE
Once the luminaire no longer meets the rated emergency operation the batteries must be replaced. AND batteries must be
replaced after a maximum of 4 years in service.
Repairs should only be carried out by a qualified person. Please recycle disposal of replaced components where facilities
exist. Special care should be taken if it’s required to open the fitting as the fitting may still be “live” even though the mains
supply has been isolated. In these circumstances immediately disconnect the battery supply.
Servicing and cleaning should only be carried out after the fitting has been made electrically safe. Cleaning of luminaires
should be carried out at regular intervals not only to ensure good optical performance but also ensure that dirt does not
accumulate to such an extent as to impair the electrical or thermal safety of the fitting.
(N) Blue
(L) Brown
In case of any query/issue with the product, please reach out to us at: [email protected]
For More products range, inquiry please contact our distributor or nearest dealers.
V-TAC EUROPE LTD. Bulgaria, Plovdiv 4000, bul.L.Karavelow 9B