Table 9. Monthly maintenance
Item
Refer Standard
Abnormal Handling Suggestion
Battery
appearance
The appearance is neat and clean without
stains.
The V-Power S14 terminals are intact.
The V-Power S14 shell is intact, and there are no
bumps, breaks, or cracks around it.
The appearance of V-Power S14 has no leakage.
There is no deformation or bulging of the shell.
If there is dirt on the surface, clean the V-
Power S14's appearance with a cotton
cloth.
If the appearance is damaged, leaking, or
deformed, take a photo and replace the
defected V-Power S14.
Please contact Vestwoods in time for
other abnormal situations.
Operation
environment
The operation environment is between 0
℃
-45
℃
.
Operation humidity range: ≤95% RH.
If temperature and humidity are abnormal,
check the indoor air conditioner status.
4.3
Quarterly Maintenance
Please refer to the following table for the quarterly maintenance of V-Power S14.
Table 10. Quarterly maintenance
Item
Refer Standard
Abnormal Handling Suggestion
Cable
There is no aging of the connecting wire and
no cracking of the insulation layer.
The bolts at the cable connection are not
loose.
Replace the faulty cable.
Fasten the screws.
4.4
Yearly Maintenance
It is recommended to perform trend analysis on recorded data (battery and environment).