VG-6777 Digital Isolate Interface 

Installation and Operation Manual V1.05

 

Mounting:

Warning:  Please  disconnect  the  loop  power  in  order  to  avoid  control  panel  broken  by  short  circuit  when 

mounting Base. 

1.Make sure the mounting direction mark 

” on Base is upwards .

2.Install the base stable by using two screws,and connect all cables in accordance with wiring details.

3.Install the Isolate interface body on to base directly.

4.Isolate interface Mounting showing in Fig.2

Fig.2 

Terminal Connection 

1.

1,3:

connecting with Detection loop L+;L-(Input),

A side isolate.

2.

8,10:

connecting with Detection loop L+;L- (Output),B

side isolate.

3.Loop wiring is shown in Fig.3

Warning 

Maxmium  32  devices  connect  with  one  side  of
Isolate

Interface.

Please  make  sure  1,10  connect  with  L+;3,8
connect

With  L-.It  recommends  using  different  colors  to
distinguish

the  line.Otherwise  it  will  cause  the  loop  wiring
error.

Fig.3 

Wiring Guide 

Wiring guide in Fig.4. 

If short circuit at 

“Zone 1”, “ Active B” LED of 

Isolate Interface A

 and 

“ Active A” LED of 

Isolate Interface B

will emitting ,

“Detection Zone 1” will be isolated.

If 

“Zone 3 ” had short circuit fault,the

 Isolate interface C

 will start to isolate, 

“Active B”of Isolate Interface C

Mounting direction 