VSL3.928.010SIASY
1
1.
Feature
Used as an warning device to generate fire alarm;
Installation and wiring same as detector base;
Driven by detection circuit, no need for extra
power line.
2.
Description
VG-6611S Conventional Alert Base is designed for the application inside a closed room. As an
warning device, the base will generate alarm sound when the detector detects a fire occurred.
Installed as a base, it is compatible with the range of conventional detectors. It is usually installed in
hotel room, residential bedroom or other locations that are far away from the audible and visual
alarm.
3.
Technical Data
Operating voltage:
15VDC
~
28VDC
Operating current:
Standby current: 0mA
Action current: ≤ 4mA (12V)
Sound level
>75dB at 1 meter
Tonal modification cycle
0.6~1.5S
Environment
Temperature:
-10
℃
~+55
℃
Relative humidity≤95%
,
non-condensing
Weight
67g
Dimension
diameter of 102mm, height of 25.5mm
Installation hole distance
73mm
4.
Outline and Installation Dimension
5.
Installation and Wiring
1)
The flame resistant twisted-pair ZR-RVS-2×1.0~1.5mm
2
is recommended to be used for the
wiring.
2)
Before the installation, please check whether the shell is intact without any damage, and whether
the label is complete.
3)
The terminals of the alert base shall be connected as the following diagram:
Control panel terminal Zone Input+: connected with the alert base’s position “1” or “2”;
Control panel terminal Zone Input
-
: connected with alert base’s position “4”;
VG
-
6611S Conventional Alert Base
Base
Installation and Operation Manual V1.00