USLR-XLT Field Inspection (1-14-19)
Copyright © 2019 Utility Solutions, Inc.
FIELD INSPECTION PROCEDURE
LOAD-RANGER® XLT Portable Load Break Tool
The following guide is recommended prior to use of the
LOAD-RANGER® XLT and
in between recommended periodic maintenance.
Visually inspect the tool. If any of the following are found, remove the tool from
the field and perform service:
• Damaged Hook Loop (all surfaces should
be clean to insure proper electrical
contact)
• Damaged or discolored Yellow Tube
• Loose Black Top Ring (tighten if possible,
remove from service if damaged)
• Damaged Clip Assembly, components
should operate smoothly with firm spring
pressure (all surfaces should be clean to
insure proper electrical contact)
• Damaged Control Arm, arm should pivot
smoothly in either direction (45˚) with firm
spring pressure
• Loose or Damaged External Conductor
Paths (tighten if possible, remove from
service if either are damaged)
• Verify tool has been properly Maintained
by qualified personnel (recommended
every 1,500 to 2,000 operations - refer to
your company guidelines)
1.
A) With the tool in the closed position, confirm continuity exists between the Hook
Loop and the Control Arm using a voltmeter as shown.
B) Confirm continuity exists while pulling the Hook Loop toward the open position.
Continuity should exist until the load break mechanism is engaged and the tool
locks in the open position.
C) Confirm NO continuity exists between the Hook Loop and the Control Arm when
the tool is in the fully opened positioned.
3.
!
!
WARNING
Carefully read and fully understand the manual prior to
operating, maintaining or testing this device. Improper
operation, handling or maintenance of this device can result
in death, grievous personal injury and or equipment damage.
VISUAL INSPECTION
CONTINUITY
RESET TOOL
0.25
A
The
LOAD-RANGER
®
XLT should be
reset and verified before EACH
use.
The current path will exist inside the tool until the load break mechanism
is triggered.
2.
PATENT NO. 6,965,008 - 5,861,595 - 5,650,602 Other Patents Pending
0.25
---
C
B
1) Extend the yellow tube to expose 2-3” by pulling on the Hook Loop.
2) Release the Hook Loop and confirm the spring force causes the tool to
“snap back” in the closed position. Remove from service immediately if not.
3) Fully extend the yellow tube until it locks in the open position. Remove
from service immediately if not. Press the black reset button to release the