USLR-XLT Field Inspection (1-14-19)

Copyright © 2019 Utility Solutions, Inc.

FIELD INSPECTION PROCEDURE 

LOAD-RANGER® XLT Portable Load Break Tool

The following guide is recommended prior to use of the 

LOAD-RANGER® XLT and 

in between recommended periodic maintenance.

Visually inspect the tool. If any of the following are found, remove the tool from 

the field and perform service:

• Damaged Hook Loop (all surfaces should 

be clean to insure proper electrical 

contact

• Damaged or discolored Yellow Tube

• Loose Black Top Ring (tighten if possible, 

remove  from service if damaged)

• Damaged Clip Assembly, components 

should operate smoothly with firm spring 

pressure (all surfaces should be clean to 

insure proper electrical contact)

• Damaged Control Arm, arm should pivot  

smoothly in either direction (45˚) with firm 

spring pressure

• Loose or Damaged External Conductor 

Paths (tighten if possible, remove  from 

service if either are damaged)

• Verify tool has been properly Maintained 

by  qualified  personnel  (recommended 

every 1,500 to 2,000 operations - refer to 

your company guidelines)

1.

A)  With the tool in the closed position, confirm continuity exists between the Hook 

Loop and the Control Arm using a voltmeter as shown.
B)  Confirm continuity exists while pulling the Hook Loop toward the open position. 

Continuity should exist until the load break mechanism is engaged and the tool 

locks in the open position.
C)  Confirm NO continuity exists between the Hook Loop and the Control Arm when 

the tool is in the fully opened positioned.

3.

!

!

WARNING

Carefully read and fully understand the manual prior to 

operating, maintaining or testing this device. Improper 

operation, handling or maintenance of this device can result 

in death, grievous personal injury and or equipment damage.

VISUAL INSPECTION

CONTINUITY

RESET TOOL

 

0.25

A

The 

LOAD-RANGER

® 

XLT should be 

reset and verified before EACH 

use.

The current path will exist inside the tool until the load break mechanism 

is triggered.

2.

PATENT NO. 6,965,008 - 5,861,595 - 5,650,602  Other Patents Pending

 

0.25

 

---

C

B

1)  Extend the yellow tube to expose 2-3” by pulling on the Hook Loop.
2)  Release the Hook Loop and confirm the spring force causes the tool to 

“snap back” in the closed position. Remove from service immediately if not.
3)  Fully extend the yellow tube until it locks in the open position.  Remove 

from service immediately if not. Press the black reset button to release the 

yellow tube and reset the tool. 