FIGURE 6-1 Safety Relief Valve
31
6.3 Safety Relief Valve and Air Vent
•
Install safety relief valve using pipe fitting
provided with boiler. See Figure 6-1.
• Install safety relief valve with spindle in vertical
position.
•
Do not install shutoff valve between boiler and
safety relief valve.
• Install discharge piping from safety relief valve.
Do not use plastic pipe.
• Use ¾" or larger pipe.
• Use pipe suitable for temperatures of 375°F
(191°C) or greater. Do not use plastic pipe on
safety relief valve.
• Individual boiler discharge piping shall be
independent of other discharge piping.
• Size and arrange discharge piping to avoid
reducing safety relief valve relieving capacity
below minimum relief valve capacity stated on
rating plate.
• Run pipe as short and straight as possible to
location protecting user from scalding and
properly drain piping.
• Install union, if used, close to safety relief valve
outlet.
• Install elbow(s), if used, close to safety relief
valve outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Use pipe suitable for temperatures of 375°F
(191°C) or greater. DO NOT use plastic pipe.
Install discharge piping per these instructions.
!
6 - HYDRONIC PIPING
6.4 Trim Piping
• Temperature - Pressure Gauge. Install temperature
pressure gauge using tee and bushing provided in
near boiler piping on supply side. See Figure 6-2.
• Some boiler models may have integral drain valve
located inside jacket directly underneath pump.
Install external drain valve as required.
6.5 System Piping
• Ensure plugs are removed from boiler water
connections.
• See Figure 6-5 for basic system piping
configurations.
•
Systems with automatic fill valves require back flow
prevention device.
• Single boiler system. See Figures 6-2, 6-5, for
general guidance. Additional considerations:
• Boiler control only supports integrated pump.
Installer responsible for integration of multiple
central heating pumps using field supplied
external control.
• Boiler control allows domestic hot water
prioritization.
•
Thoroughly flush all hydronic piping.
•
Secure all valves/fittings to boiler.
• Manufacturer recommends installing an isolation
and purge valve to use during commissioning to
ensure the boiler does not shut down due to over-
temperature. See figure 6-2 for details.
• Do not install isolation valve between boiler and any
field installed LWCO.
• If soldering piping to boiler, avoid over heating and
damaging seals and gaskets.
• Connect system valve pipe work to the boiler.
• Route pressure relief valve discharge piping to the
floor. Follow local code with respect to necessary
distance to the floor.
See Figure 6-1.
• Verify all drain valves are closed.
When installing safety relief valve it must
be installed in a vertical position with
spindle at top.
Note
240013371 REV B, [10/01/2021]
Summary of Contents for MACF-115
Page 2: ...MACF 150 ...
Page 4: ...MAHF 125 ...
Page 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Page 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Page 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Page 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Page 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Page 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Page 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...