P/N 501-1776ZE-1-09 • REV 09 • ISS 16APR14  

Figure 7: Detector/sounders per loop 

 

A. 

Cable length panel to first sounder 

B. 

Cable length first to last sounder 

C. 

Cable length last sounder to panel 

1. 

Detectors and Sounders 

Table 4: Maximum detectors and sounders per loop 

Quantity allowed [1] 

10 m 

980 m 

10 m 

50 detectors and 50 sounders 

63 detectors and 42 sounders 

100 m  

800 m 

100 m 

45 detectors and 45 sounders 

63 detectors and 40 sounders 

200 m 

600 m 

200 m 

40 detectors and 40 sounders 

63 detectors and 37 sounders 

300 m  

400 m  

300 m 

37 detectors and 37 sounders 

63 detectors and 35 sounders 

[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm² 

Specifications 

 

Operating voltage 
 

External supply 

 

Loop supply, ZP protocol 

 
18 to 30 VDC 
19.5 to 20.5 V pulsed, max. 4 V line 
loss 

Current (line powered) 
 

Quiescent (RMS) 

 

Alarm (RMS) 

 

Alarm (excluding device 

 

address) 

 

Alarm (at device address) 

 
820 

µ

6.4 mA 
9.4 mA max. 
 
25 mA max. 

Current (externally powered) 
 

Quiescent (RMS) 

 

Alarm (RMS) 

 

Maximum number 

 
470 

µ

500 

µ

50 per 1 km loop (subject to cable 
size and sounder spacing) 

Sound output 
 

Tone 1 

 

Tone 2 

 

Tone 3 

90 dBA (all around) 
Continuous 980 Hz 
Intermittent 980 Hz (0.5 sec on/off) 
Two-tone warble 980 Hz/670 Hz 

Sound distribution 

Wide 

CNPP anechoic sound levels 

See Figure 8 

Monitoring 
 

ZP loop 

 

Sound output level 

 
Open and short circuit fault 
Self test facility 

Compatibility 

Ziton analogue addressable 
systems 

Addressing method 

7-segment DIP switch 

Mounting 

Surface, with plug-in base 

Wiring 

Two-core loop 

Construction 
 

Material 

 

Weight 

 

Dimensions (Ø × D) 

 
Moulded thermoplastic 
275 g 
127 × 113 mm 

Operating environment
 

Temperature 

 

Relative humidity 

 
−10 to +60°C 
10 to 95%, noncondensing 

Storage temperature 

−20 to +70°C 

Figure 8: CNPP anechoic sound levels 

 

Regulatory information 

This section includes both regulatory information and a 
summary on the declared performance according to the 
Construction Products Regulation 305/2011. For detailed 
information refer to the product Declaration of Performance. 

 

Certification 

 

Certification body 

0370 

Declaration of 
Performance number 

360-5201-0399 

Year of first CE marking  14 

Product Identification 

ZP755HA-2

 

Intended use 

See DoP point 3 

Essential characteristics  See DoP point 9 

Manufacturer 

Gulf Security Technology Co.,Ltd 
80, Changjiang East Road, 
QETDZ, Qinhuangdao, 
Hebei Province, China 066004 

Authorized EU manufacturing 
representative:  
UTC Fire & Security B.V.  
Kelvinstraat 7, 6003 DH Weert, Netherlands 

European Union 
directives 

1999/5/EC (R&TTE directive): Hereby, UTC 
Fire & Security declares that this device is in 
compliance with the essential requirements 
and other relevant provisions of Directive 
1999/5/EC. 

 

2002/96/EC (WEEE directive): Products 
marked with this symbol cannot be disposed 
of as unsorted municipal waste in the 
European Union. For proper recycling, 
return this product to your local supplier 
upon the purchase of equivalent new 
equipment, or dispose of it at designated 
collection points. For more information see: 
www.recyclethis.info. 

Contact information 

For contact information, see www.utcfssecurityproducts.eu. 

A

C

B

1

1

6

5

O

105

O

75

O

45

O

1

5

O

13

5

O

dBA

70

75

80

85

70

75

80

85

90

90

Summary of Contents for Ziton ZP755HA-2

Page 1: ...e Red Plug in base Polar White Installation To install the device follow these general steps 1 Wire the base 2 Set the operating power 3 Set the address 4 Set the mode of operation 5 Set the tone 6 Set the volume 7 Mount the sounder onto the base The details of each step are given below Wiring the base Connect the loop wiring for the plug in base as shown in Figure 1 There is no wiring between the...

Page 2: ...gure operation as a stand alone sounder 1 Set SW2 7 to ON 2 Navigate to the following menu to tag the sounders as SAB ZP3 Panel Menu Setup Sounders SAB Add SAB The Planner can also be used 3 To map an alert to evac function make the first input type a fast flash input The sounder will sound the alert tone in response to a fast flash input or an evac tone when the input configured as steady is trig...

Page 3: ...volume control must be set to the full clockwise position If the volume is adjusted for any reason it must be returned to the full clockwise position Figure 5 Volume control 1 Tone select 2 SW2 6 on 3 SW2 6 off 4 Volume control Mounting the sounder onto the base Refer to Figure 6 Align the addressable sounder to the plug in base Push up A and turn the sounder until it clicks into place B Push the ...

Page 4: ... plug in base Wiring Two core loop Construction Material Weight Dimensions Ø D Moulded thermoplastic 275 g 127 113 mm Operating environment Temperature Relative humidity 10 to 60 C 10 to 95 noncondensing Storage temperature 20 to 70 C Figure 8 CNPP anechoic sound levels Regulatory information This section includes both regulatory information and a summary on the declared performance according to t...

Reviews: