is within detection range of the detector. If the LED does 

not stay on for 4 seconds, move the detector and retest. 

LED indications 

The red LED located on the front of the detector indicates the 

status of the detector as shown in Table 2 below. 

Table 2: LED indications 

Status LED 

indication 

Power on 

Flashes once when power is applied. 

Clap test/alarm 
memory 

 

In response to the clap test: Flashes twice to 
indicate the detector has power and is functioning 
properly; or On for 4 seconds to indicate the 
detector has alarmed. 

Alarm 

On for 4 seconds with relay when breaking glass is 
detected. 

Test mode 

 

On for 4 seconds with relay, then flashes for 60 
seconds. Each test trigger resets the test mode 
clock and the LED starts over flashing for 60 
seconds. 

4  

ShatterPro 3 Glassbreak Detector Installation Instructions 

Hand-clap test and alarm memory 

To check alarm memory and detector operation with the hand-

clap test, do the following: 

1.  Standing under the detector, clap your hands together. 

2.  Observe the LED on the detector. 

If the detector has power and is functioning properly, the LED 

quickly flashes twice. 

If the detector has alarmed, the LED will light for 4 seconds. 

Cycle power to clear the alarm memory. 

Caution: 

The hand-clap test is intended as a functional test 

and is not an accurate indication of detector range. 

Maintenance 

When installed and used properly, the detector provides years 

of service with minimal maintenance. You should test the 

detector annually to ensure proper operation. 

Clean the cover with a damp (water) cloth as needed to keep it 

free of dust and dirt. Always test the detector after cleaning it. 

Specifications 

Input voltage 

9.5 to 16 VDC 

Current 
   Typical 
   Maximum 

 
15 mA 
25 mA 

Electrical configuration  Form A, Form C 

Relay rating 

16 V, 50 mA max. 

Tamper switch rating 

12 V, 50 mA max. 

Detection range 

3 to 25 ft. (0.9 to 7.6 m) x 360° 

Alarm response 

4 seconds 

Minimum glass size 

12 x 24 in. (30.5 x 61 cm) 

Recommended glass 
thickness 
   Plate 
   Tempered 
   Wired 
   Laminated 

 

3/32 to 1/4 in. (2.4 to 6.4 mm) 
1/8 to 1/4 in. (3.2 to 6.4 mm) 
1/4 in. (6.4 mm) 
1/4 in. (6.4 mm) 

Operating temperature 

32 to 122°F (0 to 50°C) 

Relative humidity 

10 to 90% noncondensing 

Dimensions 
   Rectangle housing 
(DxWxH) 
   Round housing 

 
0.81 x 2.75 x 4.52 in. (2.1 x 2.75 x 4.52 cm)
0.81 (2.1 cm) depth, 4.0 in. (10.2 cm) 
diameter 

Color white 

Field wiring size 

18 to 24 AWG 

Regulatory information 

UL listings 

CUL, ULC-S306, UL 639 

FCC compliance 

This device complies with part 15 of the FCC 
rules.  Operation is subject to the following 
conditions: 
This device may not cause harmful interference.
This device must accept any interference 
received, including interference that may cause 
undesired operation. 
Changes or modifications not expressly approved 
by the party responsible for compliance could 
void the user’s authority to operate the 
equipment.

 

Certification 

 

Product ordering 

Product  

Description 

5812NT 

ShatterPro 3, rectangular housing, Form A 

R5812NT  ShatterPro 3, round housing, Form A 

5815NT 

ShatterPro 3, rectangular housing, Form C, tamper switch

R5815NT  ShatterPro 3, round housing, Form C, tamper switch 

Accessories 

5709C 

Glassbreak hand-held tester 

Contact information 

www.utcfireandsecurity.com

 or 

www.interlogix.com

 

For customer support: 

www.interlogix.com/customer-support

  

Copyright © 2011 UTC Fire & Security. All rights reserved. 

Summary of Contents for interlogix ShatterPro 3

Page 1: ...base to prevent tampering Hand clap test In addition to a test mode you can test the detector by clapping your hands Optional tamper switch Sends a signal to the control panel when the cover is removed from the base You will need the following tools and parts to install the detector ShatterPro 3 detector including cover screw Screws and wall anchors Flat blade screwdriver Phillips screwdriver UTC ...

Page 2: ... test it before permanently mounting the detector To install the detector do the following 1 Run the security system wiring to the detector location 2 Remove the front cover of the detector as follows Round housing Press the release tab on the lip of the base twist the cover counter clockwise and lift the cover off Figure 4 below Figure 4 Round housing parts Microphone LED Release tab Rectangle ho...

Page 3: ...are unsure about the glass type 2 To put the detector in test mode hold the tester so that the speaker is within 1 in 25 mm of the detector microphone Figure 8 below and activate the tester When the detector is in test mode the LED on the detector lights steady for 4 seconds and then flashes for 60 seconds The relay opens for 4 seconds then returns to standby Time resets after each valid test Figu...

Page 4: ... to keep it free of dust and dirt Always test the detector after cleaning it Specifications Input voltage 9 5 to 16 VDC Current Typical Maximum 15 mA 25 mA Electrical configuration Form A Form C Relay rating 16 V 50 mA max Tamper switch rating 12 V 50 mA max Detection range 3 to 25 ft 0 9 to 7 6 m x 360 Alarm response 4 seconds Minimum glass size 12 x 24 in 30 5 x 61 cm Recommended glass thickness...

Page 5: ...D PRODUCTS For more information on warranty disclaimers and product safety information please check https firesecurityproducts com policy product warning or scan the QR code Certification European Union directives UTC Fire Security hereby declares that this device is in compliance with the applicable requirements and provisions of the Directive 2014 30 EU and or 2014 35 EU For more information see...

Reviews: