UTC Fire and Security interlogix DI601AM Installation Sheet Download Page 7

EN: Installation Sheet 

Package

The package contains:

•1 x DI601AM

•1 x drilling template for fixing holes

•3 x 31.75 mm / 1.25 in. wall plugs

•3 x 31.75 mm / 1.25 in. screws

•1 x lens mask

•2 x additional curtain shutters

•1 x tamper cup

•2 x tamper caps (different lengths)

•1 x plastic locking tool

•1 x installation sheet

•1 x front cover screw cap

Introduction

The DI601AM Outdoor PIR/AM Detector is an external motion 

detector and alarm trigger that uses two independent passive 

infrared detectors.

Both sensors must trigger to cause the detector to signal an 

alarm. The DI601AM uses quad PIR technology to deliver 

precise, reliable presence detection. 

Programmable options include a variable pulse count and a 

choice of three detection ranges: 10 m, 20 m and 30 m.

Mounting the unit

When positioning the detector please consider that he PIR 

sensor is more sensitive to a movement across the beams, and 

less sensitive to a movement directly towards or away from the 

beams. 

During installation, protect the electronics against water, as 

trapped moisture can affect or damage the unit.

We recommend that the cable entry and screw mounting holes 

be sealed from within the detector using acrylic (non-silicone 

based) sealants.

Note: 

When locating the detector, please ensure the detector’s 

field of view is unobstructed.

To mount the detector:

1.Drill the wall to accept the fixing screws, the cable entry, and 

the tamper cup (if used). See Figures 1 and 3. 

A hole-drilling template is provided. 

Notes

•Leave a minimum 10 cm (4 inches) clearance above the top of 

the detector housing to allow the cover and the detector to be 

positioned correctly.

•We recommend using the tamper cup on uneven wall surfaces.

•The recommended optimum mounting height for the detector is 

3 m. Whilst it is possible to mount the unit higher, this will give 

a reduced detection range and will require the detection subject 

to move further through the already reduced detection area 

before activation is signaled.

2.Remove the cover assembly by loosening the locking screw. 

Squeeze the sides of the front cover to release the internal 

catches.

The cover hinges from the top and lifts out of the location slot. 

See Figure 2.

3.Use a razor knife to open a rubber seal to allow the cabling 

into the unit (see Figure 4). Feed standard eight-core or 12-core 

alarm cable though the wall and directly into the cable entry. 

Bare the wires and connect to the top PCB terminal block 

(Figure 15)

Caution: 

Do not allow the cable to be trapped between the 

rear gasket and the mounting surface as this may cause water 

ingress. For surface mount cables use the conduit knock-out at 

the bottom of the detector. Refer Fig 1 for good and bad cable 

routings.

4.Screw the unit to the wall ensuring that the tamper pin is 

correctly located and that the tamper micro-switch is closed. 

Always ensure the detector base is screwed tightly to the wall 

so that the tamper foot is pushed into the rear rubber gasket. 

On uneven surfaces use the tamper cup and locate the tamper 

foot into the cup. Drilling template is provided.

To aid installation, two spare tamper feet are provided. One 

is 1 mm shorter and the other is 1 mm longer than the tamper 

foot originally fitted. The tamper foot is a push fit and can be 

removed by carefully pulling it from the pin. See Figure 1. 

5.When the detector is aligned, connected, and programmed to 

suit the installation:

a.Fit the cover to the detector base.

b.Lightly screw the locking screw.

c.Put the top of the locking tool into the small notch on each 

side of the cover, and then apply slight pressure until the cover 

locks into the base, as shown in Figure 5.

d.Tighten the locking screw.

Connecting the unit

The DI601AM includes jumpers that let you configure internal 

Triple End-of-Line (TEOL) resistor values, when TEOL resistors 

are required. Values are: 1, 2.2, 3.3, 4.7, 5.6, and 6.8 kΩ for 

Alarm and Tamper (DEOL resistors). The values are 2.2, 3.3, 

4.7, 5.6 and 10kΩ for Fault/Anti-Mask. Figure 15 shows:

1.TEOL resistor jumpers

2.Wiring points

3.TEOL enable used in conjunction with a jumper at the 

required resistance

Alternatively, you can remove the jumpers and connect a 

discrete resistor directly to the alarm, tamper or Fault/Anti-Mask 

outputs as specified by third-party equipment.

The wiring schematic in Figure 15 shows how to connect and 

the table in figure 16 shows how to calculate DEOL and TEOL 

values with examples.

Table 1: Connections

         

 Terminal 

 Label 

           Description

1

LED

Remote LED 

enable

2

TEST

Remote TEST 

input

3, 4

FAULT/MASK

Fault/Anti-Mask 

relay normally 

closed

Summary of Contents for interlogix DI601AM

Page 1: ...EN DE ES FR IT NL PL PT SV Figure 1 DI601AM Outdoor PIR AM Detector Installation Sheet Figure 2 Figure 3 ...

Page 2: ...Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 TOP ...

Page 3: ...50131 2 2 Grade 3 compliance requires 3m mounting height and 0º adjustment or 1 5m mounting height and 2º adjustment TOP Long range 30m section Short medium range 6m to 20m section 0 24 26 28 30m 0m 2m 4m 6m 8m 10m 0 2 4 6 8 10 12 14 16 18 20 22 3m TOP 9 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30m 0m 2m 4m 6m 8m 10m 6m Note This setup has not been tested to EN50131 2 2 ...

Page 4: ...4m 2m 4m 70 Figure 14 45 MASK THIS SECTION OFF FOR CURTAIN COVERAGE APPLICATIONS 0 2 4 6 8 10 12 14 16m 0 2m 4m 6m 8m 10m 0 2 4 6 8 0 2m 4m 6m 8m 10m 6m 70 0 2m 4m 6m 8m 10m 12m 2m 4m 6m 8m 10m 12m 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30m ...

Page 5: ... item 2 Jt Jumper to set EOL resistor value for standby Figure 15a item 3 Jf Jumper to set EOL resistor value for fault Figure 15a item 4 Ja Jt J TEOL Jf alarm n c tamper fault alarm n o Ja 1 2 Figure 15a 3 4 0V 12V ALARM N O ALARM N O TAMPER TAMPER ALARM N C ALARM N C FAULT A M FAULT A M REMOTE TEST REMOTE LED DEOL TEOL ...

Page 6: ...Inf OPEN CIRCUIT EXAMPLE USING 4K7 TAMPER 4K7 ALARM AND 10K FAULT A M RESISTORS ALSO TEOL JUMPER SELECTED REMOVE ALL JUMPERS FOR ISOLATED OUTPUTS Single zone TEOL Calculation Event Default Ohm CALCULATION TAMPER SHORT 0 CLOSED CIRCUIT STANDBY 4K7 Rt ALARM 9K4 Rt Ra TAMPER OPEN Inf OPEN CIRCUIT EXAMPLE USING 4K7 TAMPER AND 4K7 ALARM RESISTORS REMOVE ALL JUMPERS FOR ISOLATED OUTPUTS Single zone DEOL...

Page 7: ...igure 2 3 Use a razor knife to open a rubber seal to allow the cabling into the unit see Figure 4 Feed standard eight core or 12 core alarm cable though the wall and directly into the cable entry Bare the wires and connect to the top PCB terminal block Figure 15 Caution Do not allow the cable to be trapped between the rear gasket and the mounting surface as this may cause water ingress For surface...

Page 8: ...edges of the pan and tilt module and press on the lens to click it into place Always replace the lens the correct way up to ensure exact beam pattern coverage The top of the lens is marked TOP as shown in Figure 7 There is a locating notch on the top of the pan and tilt module that locates into the cut out on the top of the lens Table 2 below summarizes typical masking configurations for use when ...

Page 9: ... CAUTION The range of the detector increases without the protective front cover Therefore the front cover must be fitted to establish the correct beam pattern Use Table 3 to adjust the range as necessary Pan and tilt the lens module over the field of view to obtain the correct coverage area See Figure 18 Fault Anti Mask Circuit Fault Anti Mask technology prevents deliberate disabling of the detect...

Page 10: ... memory Walk test Output test mode with LED indication Option to disable LEDs Operating temperature 30 to 65 C Housing High impact ABS plastic with HDPE cover UV stabilized Dimensions W x H x D 125 x 175 x 130 mm Weight 348g Net 534 g Gross Mounting height Variable up to 6 m Optimum height 3 m for full range Regulatory information Manufacturer UTC Fire Security Americas Corporation Inc 1275 Red Fo...

Reviews: