Remote Booster Power Supply Technical Reference Manual
Notes
•
CC1(S) modules must be wired and programmed on the Signature controller for proper
operation.
•
Any BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel
when DIP switch SW2-6 is on. AC power failure is delayed for three hours.
•
CC1(S) wiring must be within three feet of the BPS enclosure and in conduit or mounted
within the BPS’s enclosure. If CC1(S) wiring is more than three feet from a BPS enclosure,
then a separate listed EOL relay (PAM1, 6254A-003, or 73402A) or equivalent must be used
to supervise the 200 mA AUX circuit wiring.
•
When configured for AC power loss reporting using the trouble relay (DIP switch SW2-6 ON),
the CT1 module supervises and reports the AC power loss to the control panel. When DIP
switch SW2-6 is OFF, the CT1 module is not required.
Figure 19: Multiple CC1(S) modules using the BPS’s sense inputs
+
+
+
+
+