UTC Fire and Security EDWARDS 250-CO SafeAir Installation Sheet Download Page 6

6 / 8 

 

P/N 1061018 • REV E • ISS 14JUL11 

8.  Strip 3/8 in. of insulation from each wire. 

9.  Determine the correct wiring, and then insert the wires 

under the appropriate screw terminals. See "Wiring" and 
Figure 4 to Figure 6. 

10.  Tighten both screws to secure the base to the wall plate. 

11.  Replace the detector cover. 

12.  Apply power. The LED should flash green for 

approximately four seconds, and then pulse green. 

13.  If required by the AHJ or local codes, affix the supplied CO 

Warning Label (P/N 10634757) in proximity to the 
detector. 

14.  Test in accordance with “Testing” below. 

Wiring 

There are three typical wiring configurations: 

• 

Single device and single zone (Figure 4) 

• 

Multiple devices in a single zone (Figure 5) 

• 

Multiple devices with separate alarm and trouble zones 
(Figure 6) 

Notification 

Notification of carbon monoxide detectors should be consistent 
with NFPA 720 and the local AHJ. Notification zones should be 
consistent with the emergency plan for the protected premises. 

Maintenance 

Note: 

The 250-CO is shipped from the factory as an 

assembled unit; it contains no user-serviceable parts and 
should not be disassembled. 

Clean the outside of the detector each month with a clean cloth 
(either dry or dampened with water) to keep openings free from 
dust and dirt. 

Do not paint the detector or expose it to cleaning solutions. 

CO detector replacement 

The 250-CO SafeAir Carbon Monoxide Detector has a long-life 
carbon monoxide electrochemical sensor. Replace the detector 
with a new 250-CO detector after six years from the date of 
manufacture (found on the product label on the back of the 
detector) or when the control panel goes into trouble and an 
audible/visible annunciation occurs signaling “end of life”. 

Testing 

WARNING: 

To reduce the risk of carbon monoxide poisoning, 

test alarm operation when not in use for 10 days or more. 

Test the detector by pushing the test button after installation 
and once a week to verify that it is functioning properly. If the 
detector fails the test, verify all connections, wait briefly then try 
again. If the detector fails again, replace it. 

Notify all persons and facilities that receive alarm and trouble 
signals before beginning the test (to prevent unnecessary 
response). 

To test the trouble relay: 

1. Momentarily 

disconnect 

the power supply from the 

detector and verify that the common trouble relay opens. 

2.  Verify that the panel reacts correctly to the relay activation. 

Test/hush button:

 (Refer to Figure 7.) Use the test/hush 

button to test the detector and silence an activated detector. 
When in alarm, momentarily pushing the test/hush button 
silences the integral sounder for five minutes. The red alarm 
light stays on, and if CO is still present after five minutes, the 
detector once again sounds in the temporal-four pattern. The 
detector automatically resets when CO is no longer detected. 

Three different tests can be performed by pressing the 
test/hush button. How long the button is pressed determines 
which tests are performed. See Table 2. 

Table 2: Press duration and resulting test 

Duration Test 

Description 

Short press 

Buzzer test only 

Generates the temporal-four 
pattern twice. 

Two seconds  Buzzer test 

 
Fast CO test 

Generates the temporal-four 
pattern twice.  
While in the fast CO test mode, a 
functional carbon monoxide gas 
test can be performed using a can 
of CO testing agent [1]. 

Five seconds  Buzzer test 

 
Fast CO test 
 
 
 
Alarm relay test 

Generates the temporal-four 
pattern twice.  
While in the fast CO test mode, a 
functional carbon monoxide gas 
test can be performed using a can 
of CO testing agent [1]. 
Activates the alarm relay. 

[1] Use the UL-certified “Solo C6” canned CO product from SDi 

To test the buzzer: 

1. Momentarily 

press 

the test/hush button. 

The sounder generates four quick beeps, followed by five 
seconds of silence, and then four quick beeps. 

firealarmresources.com

Summary of Contents for EDWARDS 250-CO SafeAir

Page 1: ... 2011 UTC Fire Security All rights reserved 1 8 P N 1061018 REV E ISS 14JUL11 250 CO SafeAir Carbon Monoxide Detector Installation Sheet 1 2 3 4 3 1 2 4 3 2 1 5 1 2 3 firealarmresources com ...

Page 2: ...ectly for more information about CO safety for the equipment Make sure that motor vehicles are not and have not been operating in an attached garage or adjacent to the premises Information about carbon monoxide WARNINGS Read these installation instructions in their entirety before proceeding Leave these instructions with the owner user of this CO detection equipment This product is intended for us...

Page 3: ...tions in vent pipes or unconventional vent pipe designs which can amplify the above situations Poorly designed or maintained chimneys and or vents Extended operation of unvented fossil fuel burning devices range oven fireplace etc Idling cars in an open or closed attached garage or near the premises General limitations of CO detectors This detector is designed to protect individuals from the acute...

Page 4: ...flashing amber LED and intermittent sounder chirps to indicated that the detector needs replacing The detector also signals a trouble condition when the CO sensor reaches end of life As soon as possible replace a detector that reaches end of life because it may no longer detect carbon monoxide accurately Common trouble relay When connected to a listed control panel the trouble relay can report a t...

Page 5: ...on AHJ The 250 CO detector can connect to either UL 985 Household Fire Warning or UL 864 Commercial Fire control panels It is not intended for use in industrial applications such as gasoline refineries or parking garages which require different listings The 250 COPLT adapter plate The 250 CO detector has an optional adapter mounting plate Use the 250 COPLT adapter plate when replacing a 240 COe wi...

Page 6: ...or 10 days or more Test the detector by pushing the test button after installation and once a week to verify that it is functioning properly If the detector fails the test verify all connections wait briefly then try again If the detector fails again replace it Notify all persons and facilities that receive alarm and trouble signals before beginning the test to prevent unnecessary response To test...

Page 7: ...uminates approximately 2 seconds Waiting five minutes until the unit automatically exits out of the fast CO test mode Specifications Input voltage 12 or 24 VDC supplied by control panel or resettable auxiliary power supply Current consumption Normal Alarm 20 mA 40 mA 75 mA in test Alarm relay Type UL rating 150 mA at 33 VDC Form C Zone Common trouble relay Type UL rating 150 mA at 33 VDC Normally ...

Page 8: ...8 8 P N 1061018 REV E ISS 14JUL11 firealarmresources com ...

Reviews: