background image

95-8555

4.3

28

aPPENDIX E

vdS Schadenverhütung GmbH

Approval

vdS

Performance per EN54-10, 

Certificate of Approval G-203084.

EC-Certificate of Conformity

08 0786 – CPD – 20779

EN54-10 Flame detectors - Point detectors. 

SUbJECT MATTER OF THE AppROvAL

IR Flame Detector Type X9800 for use in Automatic Fire Detection and Fire Alarm Systems.

bASIS OF AppROvAL

DIN EN 54, Part 10 (05/02) - Flame Detectors.

INSTRUCTIONS FOR THE AppLICATION OF THE AppROvAL COMpONENT/SYSTEM

The Installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view 

angle in this direction is <90°.

The IR-flame detector corresponds to class 1.

Summary of Contents for Det-Tronics X9800

Page 1: ...Instructions 95 8555 IR Flame Detector with Pulse Output X9800 4 3 Rev 6 10 95 8555 ...

Page 2: ...sitioning 6 Detector Orientation 6 Protection Against Moisture Damage 7 Wiring Procedure 7 EOL Resistors 15 Startup Procedure 15 Manual oi Test 15 Count Test Mode 15 Fire Alarm Test 16 Troubleshooting 16 Maintenance 17 Cleaning Procedure 17 oi Plate Removal 17 Periodic Checkout Procedure 17 Clock Battery 17 Features 18 Specifications 18 Replacement Parts 20 Device Repair And Return 20 Ordering Inf...

Page 3: ...cal design The detector is equipped with both automatic and manual oi test capability The X9800 with pulse relay output is designed for use in controller based systems In addition to use in new systems it can serve as a direct field replacement for Det Tronics controller based flame detectors that generate a pulse output not compatible with R7484 and R7409B C When used as a field replacement all o...

Page 4: ...by the fault relay and is evident by the yellow color of the LED on the face of the detector See the Troubleshooting section for further information Magnetic oi Manual oi CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test The detector incorporates both magnetic oi and manual oi test capabilities These tests provide pulses 80 to 100 ...

Page 5: ...re and input voltage Event data is stored in non volatile memory when the event becomes active and again when the status changes Data is accessible using the RS 485 port integral wiring compartment All external wiring to the device is connected within the integral junction box The screw terminals accept wiring from 14 to 24 AWG The detector is furnished with four conduit entries with either 3 4 in...

Page 6: ...arbonaceous fuels It should not be used to detect fires from fuels that do not contain carbon such as hydrogen sulfur and burning metals FALSE ALARM SOURCES The detector has been designed to ignore steady state infrared sources that do not have a flicker frequency characteristic of a fire however it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts...

Page 7: ...and dirt buildup Paint overspray Water and ice IMportant Safety Notes Warning Do not open the detector assembly in a hazardous area when power is applied The detector contains limited serviceable components and should never be opened Doing so could disturb critical optical alignment and calibration parameters possibly causing serious damage This type of damage could be undetected and could result ...

Page 8: ...st performance the detector should be mounted on a rigid surface in a low vibration area Dense fog rain as well as certain gases and vapors can absorb IR radiation and reduce the sensitivity of the detector Verify that all detectors in the system are properly aimed at the area to be protected The Det Tronics Q1201C Laser Aimer is recommended for this purpose If possible fire tests should be conduc...

Page 9: ...9800 The use of shielded cable is required to protect against interference caused by EMI and RFI When using cables with shields terminate the shields as shown in Figures 6 through 10 Consult the factory if not using shielded cable The B pulse output and D oi driver leads from each detector should be shielded from the B and D leads of all other detectors in order to prevent false alarms resulting f...

Page 10: ...inuity 3 Make the final sighting adjustments and ensure that the mounting bracket hardware is tight 13 1 33 4 10 6 27 0 4 0 10 2 4 0 10 2 3 0 7 6 3 0 7 6 4X ø0 42 1 1 E2069 NOTE THIS ILLUSTRATION SHOWS THE DETECTOR MOUNTED AT THE 10 MINIMUM THESE DIMENSIONS WILL CHANGE BASED ON THE DETECTOR S MOUNTING ANGLE Figure 3 Q9033 Mounting Bracket Dimensions in Inches cm See Figure 1 for Correct Detector O...

Page 11: ...ATA BUS 1 DATA BUS 2 DATA BUS 3 DATA BUS 4 DATA BUS 5 DATA BUS 6 DATA BUS 7 CHASSIS EARTH GND J1 7 J1 15 J1 5 J1 13 J1 6 J1 14 J1 8 J1 16 J1 9 J1 17 J1 10 J1 18 J1 11 J1 19 J2 R7404 CONTROLLER J1 2 1 19 22 X9800 DETECTOR 1 2 1 19 22 2 1 19 22 X9800 DETECTOR 2 2 1 19 22 2 1 19 22 X9800 DETECTOR 3 2 1 19 22 2 1 19 22 X9800 DETECTOR 4 2 1 19 22 2 1 19 22 X9800 DETECTOR 5 2 1 19 22 2 1 19 22 X9800 DET...

Page 12: ... 63 64 ZONE OUTPUT 1 ZONE OUTPUT 2 ZONE OUTPUT 3 ZONE OUTPUT 4 ZONE OUTPUT 5 ZONE OUTPUT 6 ZONE OUTPUT 7 ZONE OUTPUT 8 FIRE LOGIC A FIRE LOGIC B ALARM OUTPUT EXTERNAL RESET INHIBIT OUTPUTS INHIBITED FAULT OUTPUT EXTERNAL ACCEPT STATUS DET OUTPUT S1 STATUS DET OUTPUT S2 STATUS DET OUTPUT S3 STATUS DET OUTPUT S4 STATUS DET OUTPUT S5 STATUS DET OUTPUT S6 STATUS DET OUTPUT S7 STATUS DET OUTPUT S8 DATA...

Page 13: ...48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUTPUT 1 ZONE OUTPUT 2 ZONE OUTPUT 3 ZONE OUTPUT 4 ZONE OUTPUT 5 ZONE OUTPUT 6 ZONE OUTPUT 7 ZONE OUTPUT 8 FIRE LOGIC A FIRE LOGIC B ALARM OUTPUT EXTERNAL RESET INHIBIT OUTPUTS INHIBITED FAULT OUTPUT EXTERNAL ACCEPT STATUS DET OUTPUT S1 STATUS DET OUTPUT S2 STATUS DET OUTPUT S3 STATUS DET OUTPUT S4 STATUS DET OUTPUT S5 STATUS DET OUTPUT S6 ST...

Page 14: ...CTOR 7 2 1 19 22 2 1 19 22 X9800 DETECTOR 8 2 1 19 22 R7495 CONTROLLER NOT FM APPROVED J1 J2 A2185 NOTE IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS EARTH GROUND CONNECT A 0 47 μF 400 VDC NON POLARIZED CAPACITOR BETWEEN J1 2 AND J1 5 NOTE 2 5 AMPERES 24 VDC REQUIRED PER EIGHT DETECTORS NOTE DETECTOR CONTROLLER CIRCUITS MEET CLASS B STYLE 0 5 REQUIREMENTS SIGNALING LINES A AND C 3 4 5 T...

Page 15: ...OR 8 2 1 19 22 R7405 CONTROLLER NOT FM APPROVED J1 J2 A2186 NOTE IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS EARTH GROUND CONNECT A 0 47 μF 400 VDC NON POLARIZED CAPACITOR BETWEEN J1 2 AND J1 5 NOTE 2 5 AMPERES 24 VDC REQUIRED PER EIGHT DETECTORS NOTE DETECTOR CONTROLLER CIRCUITS MEET CLASS B STYLE 0 5 REQUIREMENTS SIGNALING LINES A AND C 290 VDC 3 4 5 TO J1 2 0 47 μF 400 VDC NON POLA...

Page 16: ...RE2 N C FIRE2 COM FAULT1 N O FAULT1 24 VDC 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 SPARE SPARE RS 485 A RS 485 B MAN Oi Figure 11 Ex d Wiring Option A2188 FIRE ALARM PANEL X9800 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WITH NO ALARM CONDITION PRESENT ...

Page 17: ...complete system test including detector relays Generates fire alarm output Manual oiTest Output to Controller 1 Place the keylock switch in the TEST position 2 Press the SELECT button to display the desired zone on the ZONE indicator on the front panel of the controller 3 Press and hold the TEST button The ZONE OUTPUT LED for the tested zone flashes and the SYSTEM STATUS display indicates a 6 fire...

Page 18: ...Laser Aimer is recommended for this purpose 5 Enable extinguishing equipment when the test is complete TROUBLESHOOTING Warning The sensor module front half of the detector contains no user serviceable components and should never be opened The terminal compartment is the only part of the enclosure that should be opened by the user in the field 1 Disable any extinguishing equipment that is connected...

Page 19: ...lowing the procedure described below oi plate Removal 1 Disable any extinguishing equipment that is connected to the unit 2 Loosen the two captive screws then grasp the oi plate by the visor and remove it from the detector See Figure 14 3 Thoroughly clean the oi plate reflective surfaces holding it by its edges to avoid leaving fingerprints on the inside reflective surface 4 Re install the oi plat...

Page 20: ...s at 24 Vdc in alarm 2 2 watts at 30 Vdc nominal 4 0 watts at 30 Vdc in alarm Heater only 8 watts maximum Total power 16 5 watts at 30 Vdc with EOL resistor installed and heater on maximum EOL resistor must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts POWER UP TIME Fault indication clears after 0 5 second device is ready to indicate an alarm...

Page 21: ...ppendix B M OVED For complete ATEX CE certification details refer to Appendix C NOTE Operational performance verified from 40 C to 75 C NOTE An optional third party addressable module can only be used within the Ex d flameproof model unless the addressable module is component certified as Ex e for use within the Ex d e increased safety model NOTE Refer to EOL Resistors section for installation det...

Page 22: ... 005003 001 1 oz grease for detectors non silicon 006097 001 Q1201 Laser 007240 001 Q1116A1001 Air Shield AL 007255 001 Q1201C1001 X Series Laser Holder AL Plastic 007290 001 Q9033B Stainless Steel Swivel Mount Assembly is for aluminum and stainless steel detectors 007290 002 Q9033A Aluminum Swivel Mount Assembly is for aluminum detectors only 007307 001 oi plate for X3301 requires inspector conne...

Page 23: ...Detector TYPE MATERIAL A Aluminum S Stainless Steel 316 TYPE THREAD TYPE 4M 4 PORT METRIC M25 4N 4 PORT 3 4 NPT TYPE OUTPUTS 15 Relay and Pulse TYPE APPROVAL AGENCY W FM CSA ATEX CE IECEx TYPE CLASSIFICATION 1 Division Zone Ex d e 2 Division Zone Ex d Detectors are always Class I Div 1 ...

Page 24: ...s 40 F to 167 F 40 C to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 2000 The following performance criteria were verified OPTICAL INTEGRITY TEST The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50 of its detection range verifying that the detector performs a calibrate...

Page 25: ...ypical Response Time seconds Sunlight direct modulated unmodulated 2 inch dia Heptane 10 3 30 Sunlight reflected modulated unmodulated 2 inch dia Heptane 10 3 30 70 w sodium vapor lamp unmodulated 5 1 5 2 inch dia Heptane 5 1 5 3 70 w sodium vapor lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 3 250 w mercury vapor lamp unmodulated 5 1 5 2 inch dia Heptane 5 1 5 2 250 w mercury vapor lamp modulated...

Page 26: ...quartz halogen lamp 3 0 9 No alarm No alarm 1500 w electric quartz heater 10 3 No alarm No alarm Two 34 w fluorescent lamps 3 0 9 No alarm No alarm Fuel Size Distance feet m Horizontal degrees Typical Horiz Response Time seconds Vertical Degrees Typical Horiz Response Time seconds n Heptane 1 x 1 foot 42 5 13 45 45 12 14 45 30 10 16 Methane 32 inch plume 30 9 1 45 45 7 4 45 30 6 4 Fuel Size Distan...

Page 27: ...ns Class I Division 1 Groups B C and D T5 Class II Division 1 Groups E F and G T5 Class I Division 2 Groups A B C and D T3 Class II Division 2 Groups F and G T3 Class III Enclosure Type 4X Infrared Flame Detector Controller X9800 series rated 18 30 Vdc 2 1 Watts to 16 5 Watts Relay contacts rated 5 Amps 30 Vdc ...

Page 28: ...for use with the terminal compartment in type of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The met...

Page 29: ...n type of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Infrared IR flame de...

Page 30: ... OF THE APPROVAL IR Flame Detector Type X9800 for use in Automatic Fire Detection and Fire Alarm Systems BASIS OF APPROVAL DIN EN 54 Part 10 05 02 Flame Detectors Instructions for the application of the approval component system The Installation shall take into account that the orientation arrow on the flame detector is directed upwards as the view angle in this direction is 90 The IR flame detect...

Page 31: ...Integrity oi are registered trademarks or trademarks of Detector Electronics Corporation in the United States other countries or both Other company product or service names may be trademarks or service marks of others Copyright Detector Electronics Corporation 2010 All rights reserved X3301 Multispectrum IR Flame Detector PointWatch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety ...

Reviews: