Installation, Operation and 

Maintenance Manual 

 

 

 

 
 
 
 

 

© Chubb Fire & Security Pty Ltd - 2011

 

 

Summary of Contents for Chubb FSM-ES

Page 1: ... FS S SM M M S S S F F Fi i ir r re e e S S Sy y ys s st t te e em m m M M Mo o on n ni i it t to o or r ri i in n ng g g P P Pa a an n ne e el l ls s s Installation Operation and Maintenance Manual Chubb Fire Security Pty Ltd 2011 ...

Page 2: ...re and Security Pty Ltd 2010 All rights reserved This work is copyright Permission is given to Chubb Fire Security personnel to make copies of this work or part thereof This work or part thereof may not be reproduced for the purpose of resale or hire to third parties For permissions outside the conditions described in the Australian Copyright Act 1968 apply in writing to Chubb Fire Security Pty Lt...

Page 3: ...es to formatting 1 2 Removed Company Confidential Fixed Figure 13 This manual is an uncontrolled document Chubb Fire Security Pty Ltd Chubb reserves the right to alter this manual at any time in accordance with our policy of continuous development Chubb welcomes feedback regarding this manual and associated equipment For further information or feedback contact Chubb Fire Security on 1300 369 309 ...

Page 4: ... Field Wiring 8 Inputs 8 Outputs FSM ES 8 2 Installation 9 Interfacing 11 Pressure switches 12 Discharge pressure switch 13 Switches for multiple PEFS Cylinder Installations 13 3 Manual Controls 15 DIM button 15 Test button 15 Reset function 15 Acknowledge function 16 4 Operation 17 Alarm Discharge 17 Engine Shutdown FSM ES 17 Low pressure 17 3 Commissioning 18 4 Troubleshooting 19 Power supply 19...

Page 5: ...ial and workmanship under normal use for a period of twelve 12 months from the date of commissioning of PEFS Chubb agrees to repair or replace as its option any inherently defective panel This warranty does not cover damage resulting from the Customer s negligence fault misuse neglect or incorrect use of the product abuse or fair wear and tear In addition the warranty does not cover work required ...

Page 6: ... equipment that may produce high RF radio frequency energy e g cabling for RF transceiver antennas inverters motors etc Figure 1 FSM ES Typical installation All wiring and electrical connections must be installed in accordance with the customer s requirements and or the equipment manufactures specifications Power supply and equipment shutdown connections should either be completed by the Customer ...

Page 7: ...S Power Supply Both panels operates on a 8 to 35 volts operating range nominal 12 or 24 volts and the preferred power supply arrangement for is through a battery isolator or ignition circuit Fig 4 Figure 4 Power supply arrangement If continuous monitoring is required the panels can be wired direct to the vehicle battery provided that the minimum specified circuit protection of a 2 amp fast blow fu...

Page 8: ...layed in Figure 5 6 Inputs Power input Low pressure switch input Discharge pressure switch input Note The default configuration for both pressure switches is N C contacts closed normal operation contacts open fault discharge Figure 5 FSM S pin out configuration Outputs FSM ES Shutdown output Selectable contacts N O or N C default N O latching 3 pole relay clean contact capable of switching 2A 30V ...

Page 9: ...ccess for maintenance purposes provide a high degree protection from potential damage and be compliant with manufacturer specifications and customers requirements The panel can be secured using four mounting holes Fig 7 8 Use bolts that have thread diameter no greater then 4 5mm and a head diameter no greater than 9 5mm Figure 7 Panel mounting holes Figure 8 Panel dimensions mm The recommended wir...

Page 10: ...ed for the operator on the display panel Fig 9 The default setting for the shutdown delay the time it takes for the shutdown relay to operate after a fire alarm is 30 secs Four 4 different shutdown delay times Table 2 can be configured using the dipswitches located inside the panel on the PCB Fig 10 Shutdown Delay Switch 1 Switch 2 0 Second OFF OFF 15 Seconds ON OFF 30 Seconds default OFF ON 60 Se...

Page 11: ...d engine shutdown if applicable can be made via the Deutsch connector Fig 11 For field wiring purposes each panel is kitted with the mated plug DETAIL A in Fig 11 and a pin diagram See Figure 12 13 which is located inside the panel Ensure that blanking plugs are fitted to openings that are not in use Figure 11 Deutsch Connector Figure 12 Detail A FSM ES Field Wiring DETAIL A ...

Page 12: ...tion with Chubb PEFS systems the switches that are specified for use are 1 Pressure Low 1 200kPa setting part number 87042 2 Discharge 200kPa setting part number 87041 Both switches have a 1 8 NPT thread connection and are kitted with an IP65 rated Deutsch DTM series connector The pressure switch inputs on the panels are configured for Normally Closed N C i e contacts closed normal operation conta...

Page 13: ...he countdown timer See page 17 Engine Shutdown FSM ES for more information For PEFS systems pressure switches should be installed in the cylinder valves as depicted in Figure 15 Figure 15 PEFS pressure switch arrangements Switches for multiple PEFS Cylinder Installations Pressure Low switch For multiple LOP cylinder installations which have a common LOP actuation system a single cylinder low press...

Page 14: ...Fire System Monitoring Panels Chubb Fire Security Pty Ltd Technical Manual Page 14 of 22 Figure 16 Field Wiring for Multiple PEFS cylinders ...

Page 15: ...button This button will test all indicators on both panels by illuminating all LEDS and sounding the audible alarm The test mode will operate when the TEST button is pressed and held down Fig 17 Figure 17 DIM TEST buttons on FSM ES Model Reset function The reset function allows the panel to be reset after an alarm discharge and shutdown if applicable event To reset the panel press and hold the DIM...

Page 16: ...for a period of one 1 hour Only a LOW PRESSURE fault can be acknowledged silenced The acknowledge function is activated by 1 FSM ES panel Press the DELAY and TEST buttons simultaneously Fig 19 2 FSM S panel Press the ACK button Fig 20 The panel will sound two short beeps to confirm that the low pressure alarm has been silenced Figure 19 FSM ES Acknowledge feature Figure 20 FSM S Acknowledge featur...

Page 17: ...gin to flash and o the audible alarm will begin to sound continuously o the DELAY button is enabled and can be either o pressed repetitively each press of the button will restart the countdown timer for the set period o held Indefinitely to pause the countdown When the DELAY button is released the countdown will restart for the set period At the end of engine shutdown countdown period Shutdown out...

Page 18: ...cordance with AS5062 2006 Fire protection for Mobile and Transportable Equipment must be completed in order to ensure that the panel is installed correctly and is fully functional The outcomes of the test should be recorded as part of the fire suppression system commissioning report and completion documentation provided to the customer ...

Page 19: ... the entire manual A service technician must have a sure understanding of the functionality of system before attempting corrective maintenance These tables contain instructions to aid a technician in the causes of common system faults Power supply Symptom Probable Cause Corrective Action No LED s on 1 No power to panel 1 Check fuses power supply and connections 2 Check equipment isolation switches...

Page 20: ...Fire System Monitoring Panels Chubb Fire Security Pty Ltd Technical Manual Page 20 of 22 5 Wiring Diagrams FSM ES ...

Page 21: ...Fire System Monitoring Panels Chubb Fire Security Pty Ltd Technical Manual Page 21 of 22 FSM S ...

Page 22: ...9581 6364 Email Craig Hafey chubb com au 1 PART NUMBER 2 TITLE Fire System Monitoring Panels FSM ES FSM S 3 VERSION V1 0 4 USER EVALUATION MANUAL IS EXCELLENT GOOD FAIR POOR COMPLETE INCOMPLETE 5 PROBLEM QUESTION SUGGESTION COMMENT 6 RECOMMENDED CHANGE TO PUBLICATION PAGE NO PARAGRAPH NO LINE NO COLUMN NO RECOMMEND CHANGES AND REASON 7 ORIGINATOR 8 STATE TERRITORY BRANCH AREA 9 ADDRESS 10 OFFICE U...