Installation
VENT TErMiNATiON CLEArANCES:
A
Minimum 4-foot clearance below or beside any door or window that opens.
B
Minimum 1-foot clearance above any door or window that opens.
C
Minimum 3-foot clearance from any adjacent building.
D
Minimum 7-foot clearance from any grade when adjacent to public walkways.
E
Minimum 2-foot clearance above any grass, plants, or other combustible materials.
F
Minimum 3-foot clearance from a forced air intake of any appliance.
G
Minimum 2-foot clearance below eaves or overhang.
H
Minimum 1-foot clearance horizontally from combustible wall.
I
Must be a minimum of 36-inches above the roof and 24-inches above the highest point of the roof within 10-feet.
VENT TERMINATION CLEARANCES