CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during
installation of the stove. Refer to the tables below :
Floor to ceiling height must be at least 7’ (84”) in all cases.
The clearance between the flue pipe and a wall are valid only for verticle walls and for verticle flue
pipe.
The flue pipe must not go through roof trussing, an attic, a closet, a floor, a combustible partition,
or similar spaces.
A flue pipe crossing a combustible wall must have a minimum clearance of 18”.
To reduce flue clearances from combustible materials, contact your local safety department.
•
•
•
•
•
Single pipe / Double pipe
A
B
C
D
E
F
7/6
23/24
16/17
13.7/12.7
34.9/35.9
37.9/28.9