Temperature sensors should be mounted on the side of the battery case in the
middle of the bank. Mount the sensor so that it remains below the liquid level en-
suring an accurate reading of cell temperature. Half way down the case is general-
ly sufficient.
4.7 DELTA-Q CHARGING ALGORITHMS
The following link will take you to a US Battery Technical Service Bulletin regarding the
appropriate Delta-Q charging algorithms for each battery:
4
CHARGING AND
EQUALIZING
5
STORAGE
The following tips will help ensure that your batteries remain in good condition during
storage:
●
Fully charge batteries before placing in storage.
●
Store in a cool, dry location, protected from the elements.
●
Disconnect from equipment to eliminate potential parasitic loads that may dis-
charge the battery.
●
Batteries gradually self-discharge during storage. Monitor the specific gravity or
voltage every 4-6 weeks. Stored batteries should be given a boost charge when
they are at 80% state of charge (SOC) or less. Refer to Diagrams 9 and 10 for
specific gravity and voltage measurements for flooded/wet and AGM batteries re
-
spectively.
●
When batteries are taken out of storage, recharge before use.
●
If put on float voltage there is no need for periodic boost
DIAGRAM 9
100%
80%
60%
40%
20%
0
0%
30
60
90
120
150
180
1.75
1.83
1.91
1.99
2.07
2.15
Open Circuit Stand Time (days)
Self-Discharge Rate
at 20ºF to 120ºF
20ºF (-6.7ºC)
60ºF (16ºC)
40ºF (4.4ºC)
80ºF (27ºC)
100ºF (38ºC)
120ºF (49ºC)
U.S. BATTERY FLOODED-LEAD ACID BATTERY
SELF-DISCHARGE RATE
Mounting Temperature Sensor
Sensor
DIAGRAM 8