CALL MODULES
PROGRAMMING
7
1. LUx LINE CONTACT CONFIGURATION
Please do not change these parameters until necessary, for
example: cannot call specific doorphone. Before this please
eliminate all other causes.
1.01 STOP TIME [ms]
P 1. 0 1
In this step you can change stop time. Press shortly
#
button to
leave this parameter unchanged or enter new value within 5 – 300
range.
This parameter is expressed in [ms].
Press and hold
#
button to save value.
Default setting
-
100 ms
1.02 INTERRUPT TIME AFTER STOP [ms]
P 1. 0 2
In this step you can change break time after stop. Press shortly
#
button to leave this parameter unchanged or enter new value within
5 – 300 range.
This parameter is expressed in [ms].
Press and hold
#
button to save value.
Default setting
-
100 ms
1.03 LENGTH OF ADDRESS IMPULSE [us]
P 1. 0 3
In this step you can change length of address impulse. Press
shortly
#
button to leave this parameter unchanged or enter new
value within 10 – 50 range.
This parameter is expressed in [us].
Press and hold
#
button to save value.
Default setting
-
25 us
1.04 ADDRESS IMPULSES PERIOD [us]
P 1. 0 4
In this step you can change period of address impulse. Press
shortly
#
button to leave this parameter unchanged or enter new
value within 100 – 500 range.
This parameter is expressed in [us].
Press and hold
#
button to save value.
Default setting
-
200 us
1.05 AUDIO TURN ON TIME [ms]
P 1. 0 5
In this step you can change audio turn on time after pick up. Press
shortly
#
button to leave this parameter unchanged or enter new
value within 5 – 300 range.
This parameter is expressed in [ms].
Press and hold
#
button to save value.
Default setting
-
100 ms
1.06 MINIMAL LENGTH OF OPENING IMPULSE [ms]
P 1. 0 6
In this step you can change minimal length of opening impulse
(opening impulse is an impulse which causes opening the door -
electrical lock release). Press shortly
#
button to leave this
parameter unchanged or enter new value within 1 – 20 range.
This
parameter is expressed in [ms].
Press and hold
#
button to save value.
Default setting
-
3 ms
1.07 MAXIMAL LENGTH OF OPENING IMPULSE [ms]
P 1. 0 7
In this step you can change maximal length of opening impulse
(opening impulse is an impulse which causes opening the door -
electrical lock release). Press shortly
#
button to leave this
parameter unchanged or enter new value within 1 – 20 range.
This
parameter is expressed in [ms].
Press and hold
#
button to save value.
Default setting
-
15 ms
1.08 LEVEL OF CURRENT FOR ACTIVATION [mA]
P 1. 0 8
In this step you can change level of current for doorphone activation
(value of the current in the LU Line at which the system detect
audio turn on in the doorphone - the handset is picked up). Press
shortly
#
button to leave this parameter unchanged or enter new
value within 10 – 300 range.
This parameter is expressed in [ms].
Press and hold
#
button to save value.
Default setting
-
45 mA
1.09 LEVEL OF CURRENT FOR PRESENCE [mA]
P 1. 0 9
In this step you can change value of current for doorphone
presence (value of the current in the LU Line at which the system
detect doorhones turn on during ringing). Press shortly
#
button to
leave this parameter unchanged or enter new value within 10 – 300
range.
This parameter is expressed in [mA].
Press and hold
#
button to save value.
Default setting
-
60 mA