Uponor Heat-only Thermostat Installation And Operation Manual Download Page 3

Uponor Heat-only Thermostat with Touchscreen l 3

Note:

 Avoid mounting the thermostat on a return-air chase or 

where the temperature inside the wall differs from the room 
temperature. If that is unavoidable, it may be necessary to plug 
or seal the wire hole opening to prevent the environment inside 
the wall from affecting the thermostat’s readings.

Wiring

 Caution:

 Disconnect electrical power to the system to 

prevent electrical shock and damage.

1.   Remove 

3

16

" of 

insulation from the 
wire ends. Ensure 
the wire ends are 
clean, dry and free 
from corrosion.

2.  Connect the power 

wires to the Rh 
and W terminals. 
This corresponds 
to terminals 2 and 
3 on the Uponor 
Zone Control 
Module (A3031003 
or A3031004). The 
RH and W terminals 
are not polarity sensitive.

3.  Connect the optional floor sensor to the 

SEN1 and COM terminals.

Note:

 The floor sensor is detected when power is first applied to 

the thermostat. Connecting the floor sensor with power applied 
will prevent the floor functions from operating and may damage 

the thermostat.

Important!

 Do not connect power to the floor sensor terminals 

as damage to the device may occur.

Attaching the thermostat to the back plate

1.  Locate the tabs and holes on the controller and back plate.
2.  Align the back plate tab with the controller holes by leaning 

the top of the controller on the back plate until it hooks.

3.  Gently hinge the bottom of the thermostat onto the wiring 

terminals until the thermostat engages with the terminal 
connectors.

4.  Use gentle pressure on the bottom of the thermostat until the 

controller clicks into its locked position.

Important!

 Only gentle pressure is needed to engage the 

controller onto the back plate. If resistance is felt, realign 
the controller to the left or to the right to ensure the controller 
pins are correctly aligned with the terminals. Do not apply 
extreme pressure to the display area as damage to the 
equipment may result.

Installing the floor sensor (optional)

The floor sensor (A9010599) comes with a 10-ft. wire. Install 

the sensor and wire in a manner so it can be replaced should 
it fail. If additional wire is needed to connect the sensor to the 
thermostat, use 24/2 AWG. Uponor recommends installers 
solder the connections (versus wire nuts) and place the 
connections in an accessible junction box.

• 

Concrete/lightweight applications —

 If installing a floor 

sensor in a lightweight application, make sure the sensor is 
installed within a conduit (without splices) for easy removal 

and replacement should the sensor fail. The floor sensor and 

conduit should be placed equidistant between two parallel runs 
of pipe for optimal sensing and control.

• 

Joist Trak™ installation —

 When installing a floor sensor 

beneath the subfloor and the surface above is finished, cut 

a piece of 1" rigid insulation a minimum of 6" x 6". Cut a 

¼

groove from the outside edge to the center of the insulation. 

Insert the floor sensor into the insulation and run the sensor 
wire through the channel. Attach the insulation to the subfloor 

with adhesive or other suitable material. Make sure the sensor 
is placed in the center of the joist, between the two plates.

• 

Quik Trak

®

 installations —

 Prior to the finished flooring

 

being installed over the Quik Trak panels, cut or router a 

¼

groove into the subfloor to accommodate the sensor and wire. 

Route the wire to a location where the sensor can be wired 
into the thermostat.

Testing the sensor —

 The floor sensor should be tested 

prior to pouring concrete, closing up a ceiling or installing the 

finished flooring. The installation will require a multimeter and 
digital thermometer to properly test the resistance (ς) through 

the sensor wires. Using the thermometer, read or measure 

the temperature around the floor sensor location. Using the 

multimeter, measure the resistance between the two wire leads 
of the sensor. (

Note:

 The wires should NOT be connected to 

the thermostat.) 
Compare the resistance value read on the meter to the value 
on the table based on the temperature on the thermometer. The 
values do not have to match but they should be close. If the 
value on the meter is reading high, check for broken wires or a 
bad sensor. If the value is reading low, there may be moisture 
inside the sensor or the wiring is shorted. 

Sequence of operation

This thermostat is designed to control hydronic radiant 
applications. The dynamics of these types of systems differ 
from a typical forced-air furnace or baseboard heating 
application. A radiant system heats the mass and the objects 
in the room. This thermostat uses fully automatic differential 
and pulse width modulation (PWM) control functions to ensure 

zone is comfortable and energy efficient.

A3100101 Uponor Thermostat with Floor Sensor

A9010599

Floor Sensor

(Optional)

Sen1 Com

W  

 

  R

A3031003-4 Zone

Control Module

R
C
ES
ES

2    3     4

R1  R2  Y1  Y2

Summary of Contents for Heat-only Thermostat

Page 1: ...Uponor Heat only Thermostat with Touchscreen Installation and operation manual...

Page 2: ...800 321 4739 U S or 888 994 7726 Canada Tools required Small flathead screwdriver Phillips screwdriver mounting hardware Wire stripper and cutter Volt meter floor sensor installations Digital thermom...

Page 3: ...rete lightweight applications If installing a floor sensor in a lightweight application make sure the sensor is installed within a conduit without splices for easy removal and replacement should the s...

Page 4: ...y combining the effects of air temperature air speed and thermal radiation This provides superior control of a radiant heating system while maximizing comfort and efficiency The design of the thermost...

Page 5: ...essed and changed by a qualified installer Improper adjustment of these settings can result in incorrect operation of the heating system Changing the temperature units The thermostat is set to display...

Page 6: ...sensor operation and the floor sensor fails ERROR will appear on the display The thermostat will ignore any slab setpoint temperature and set the air temperature for 65 F 18 C When the thermostat is s...

Page 7: ...ES 2 3 4 R1 R2 Y1 Y2 A3100101 Uponor Thermostat with Floor Sensor A3100101 Uponor Thermostat with Floor Sensor A3100101 Uponor Thermostat with Floor Sensor A9010599 Floor Sensor Optional A9010599 Floo...

Page 8: ...TVG technician for help Setpoint limits settings Minimum range 38 F 3 C to maximum limit setting 50 F 10 C default Maximum range Minimum limit setting to 99 F 37 C 86 F 30 C default Floor sensor 10K...

Reviews: