Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
RAC14J364S21(E)
INDOOR COIL MODEL NO.
FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1000
1200
1400
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
33.2
35.1
35.4
38.6
42.2
35.0
35.9
36.1
39.5
43.1
36.8
36.7
36.8
40.4
44.0
S.C.
32.9
30.3
25.8
25.5
20.0
34.8
33.3
28.1
27.8
21.3
36.7
36.4
30.5
30.1
22.7
KW
1.88
1.88
1.88
1.90
1.92
1.89
1.89
1.89
1.90
1.93
1.90
1.90
1.90
1.91
1.93
75
T.C.
32.0
33.4
33.6
36.9
40.5
33.7
34.4
34.4
37.7
41.3
35.5
35.3
35.2
38.5
42.0
S.C.
31.6
29.4
25.0
24.7
19.3
33.4
32.3
27.4
27.1
20.8
35.3
35.3
29.7
29.4
22.2
KW
2.18
2.19
2.18
2.19
2.21
2.19
2.19
2.19
2.20
2.21
2.19
2.19
2.19
2.20
2.22
85
T.C.
30.8
31.7
31.8
35.2
38.8
32.5
32.8
32.6
36.0
39.4
34.2
33.9
33.5
36.7
40.1
S.C.
30.3
28.5
24.2
24.0
18.7
32.1
31.3
26.6
26.4
20.2
33.9
33.9
28.9
28.8
21.8
KW
2.48
2.49
2.48
2.49
2.49
2.48
2.49
2.49
2.49
2.50
2.48
2.48
2.49
2.49
2.50
95
T.C.
29.6
30.1
30.0
33.5
37.1
31.2
31.3
30.9
34.2
37.6
32.9
32.6
31.8
34.9
38.1
S.C.
29.0
27.7
23.4
23.2
18.1
30.8
30.3
25.8
25.7
19.7
32.5
32.6
28.2
28.1
21.3
KW
2.79
2.80
2.79
2.78
2.78
2.78
2.79
2.78
2.78
2.78
2.78
2.78
2.78
2.78
2.79
105
T.C.
27.5
27.8
27.5
30.9
34.5
29.2
29.1
28.3
31.5
34.9
30.9
30.4
29.1
32.2
35.4
S.C.
27.1
26.2
22.1
22.2
17.2
28.8
28.5
24.4
24.5
18.8
30.4
30.4
26.6
26.8
20.3
KW
3.38
3.39
3.40
3.36
3.31
3.36
3.35
3.39
3.34
3.30
3.33
3.32
3.38
3.33
3.30
115
T.C.
25.5
25.6
25.1
28.3
32.0
27.2
26.9
25.7
28.9
32.4
28.9
28.2
26.4
29.5
32.8
S.C.
25.2
24.8
20.8
21.2
16.4
26.8
26.7
23.0
23.3
17.9
28.4
28.2
25.1
25.5
19.4
KW
3.96
3.96
4.00
3.91
3.83
3.92
3.91
3.98
3.89
3.81
3.87
3.85
3.95
3.87
3.79
125
T.C.
23.6
23.4
22.6
25.8
29.5
25.3
24.7
23.2
26.3
29.8
27.0
26.0
23.7
26.8
30.1
S.C.
23.3
23.4
19.6
20.2
15.6
24.8
24.7
21.6
22.2
17.1
26.3
26.0
23.7
24.2
18.5
KW
4.54
4.53
4.60
4.47
4.34
4.47
4.46
4.56
4.44
4.32
4.40
4.38
4.53
4.40
4.29
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC37
1.01
1.01
1.01
–
FC/MC/PC43
1.00
1.00
1.00
–
FC/MC/PC48
1.01
1.02
1.02
–
FC/MC/PC60
0.99
1.02
1.02
–
FC/MC62
1.01
1.03
1.01
–
FC64
1.04
1.07
1.02
–
HD48
1.01
1.00
1.02
–
UC60
0.97
0.95
1.02
RFCX36CE
–
1.02
1.04
0.93
RFCX42DE
–
1.03
1.06
0.92
RFCX48DE
–
1.02
1.05
0.92
RFCX60DE
–
1.04
1.06
0.91
RFCX36BP
–
1.00
1.01
1.03
RFCX42CP
–
1.02
1.05
1.00
MX12B
FC/MC43B
1.02
1.05
0.97
MX12D
FC/MC48D
1.04
1.07
0.94
MX12D
FC/MC60D
1.03
1.07
0.94
MX12D
FC/MC62D
1.05
1.10
0.92
MX12D
FC64D
1.08
1.14
0.91
MX16C
FC/MC43C
1.02
1.03
0.91
MX16C
FC/MC48C
1.03
1.06
0.90
MX20D
FC/MC60D
1.04
1.10
0.91
MX20D
FC/MC62D
1.04
1.10
0.91
MX20D
FC64D
1.08
1.14
0.91
Furnaces
Coils
T.C.
S.C.
KW
R*L*AE12
FC/MC/PC37A
1.04
1.06
1.00
R*L*BE12
FC/MC/PC43B
1.03
1.06
0.97
R*L*CE16
FC/MC/PC43C
1.03
1.03
0.97
R*L*CE16
FC/MC/PC48C
1.05
1.06
0.97
R*L*CE16
HD48
1.01
1.02
0.96
R*L*CE16
UC60C
0.99
0.98
0.96
R*L*CE20
FC/MC/PC43C
1.04
1.06
0.98
R*L*CE20
FC/MC/PC48C
1.04
1.05
0.97
R*L*CE20
HD48
1.03
1.05
0.97
R*L*CE20
UC60D
1.01
1.03
0.98
R*9*BE12
FC/MC/PC43B
1.03
1.06
0.99
R*9*CE16
FC/MC/PC43C
1.03
1.06
0.97
R*9*CE16
FC/MC/PC48C
1.04
1.07
0.98
R*9*CE16
FC/PC60C
1.00
1.02
0.96
R*9*CE16
HD48
0.98
1.06
0.95
R*9*CE20
FC/MC/PC43C
1.02
1.03
0.97
R*9*CE20
FC/MC/PC48C
1.04
1.05
0.98
R*9*CE20
FC/PC60C
0.99
0.98
0.95
R*9*CE20
HD48
1.03
1.05
0.99
R*9*DE20
FC/MC/PC48D
1.04
1.05
0.98
R*9*DE20
FC64D
1.05
1.08
1.00
R*9*DE20
HD48
1.03
1.05
0.99
R*9*DE20
UC60D
1.01
1.02
0.97