Subject to change without notice. Published in U.S.A.
810764-UTG-A-0313
Copyright
©
2013 by Johnson Controls, Inc. All rights reserved.
Supersedes Nothing
York International Corp.
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
RAC13J604S31(E)
INDOOR COIL MODEL NO.
FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1600
1800
2000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
51.4
54.0
54.3
58.2
61.8
52.3
54.7
54.9
59.1
62.4
53.3
55.5
55.4
60.0
63.1
S.C.
51.4
44.9
38.8
37.5
30.3
52.3
46.7
40.6
38.6
31.1
53.3
48.6
42.3
39.8
31.8
KW
3.31
3.33
3.34
3.34
3.41
3.32
3.33
3.35
3.37
3.41
3.33
3.33
3.35
3.40
3.41
75
T.C.
50.5
52.7
52.8
56.9
60.2
51.6
53.5
53.5
57.7
60.8
52.6
54.3
54.1
58.6
61.4
S.C.
50.5
45.3
38.8
37.5
29.7
51.6
47.2
40.6
38.8
30.6
52.6
49.2
42.4
40.1
31.4
KW
3.85
3.86
3.87
3.89
3.95
3.86
3.86
3.87
3.91
3.95
3.87
3.87
3.88
3.94
3.96
85
T.C.
49.6
51.5
51.3
55.5
58.5
50.8
52.3
52.1
56.4
59.2
52.0
53.1
52.8
57.2
59.8
S.C.
49.6
45.7
38.8
37.6
29.1
50.8
47.7
40.7
38.9
30.1
52.0
49.8
42.5
40.3
31.0
KW
4.38
4.39
4.39
4.44
4.49
4.39
4.40
4.40
4.46
4.50
4.41
4.41
4.41
4.47
4.51
95
T.C.
48.8
50.2
49.8
54.2
56.9
50.0
51.1
50.6
55.0
57.5
51.3
51.9
51.4
55.8
58.2
S.C.
48.7
46.1
38.8
37.6
28.5
50.0
48.2
40.7
39.1
29.6
51.3
50.4
42.6
40.6
30.6
KW
4.91
4.92
4.92
4.99
5.03
4.92
4.93
4.93
5.00
5.05
4.94
4.94
4.94
5.01
5.06
105
T.C.
45.2
47.2
45.7
49.9
53.2
46.4
47.7
46.5
50.6
53.7
47.6
48.3
47.3
51.2
54.2
S.C.
45.1
43.7
37.1
35.8
27.3
46.4
45.4
38.9
37.3
28.4
47.6
47.1
40.7
38.8
29.4
KW
5.63
5.64
5.63
5.71
5.80
5.66
5.66
5.64
5.73
5.81
5.69
5.69
5.66
5.75
5.82
115
T.C.
41.8
44.2
41.7
45.7
49.7
42.9
44.5
42.5
46.2
50.0
44.0
44.8
43.2
46.8
50.3
S.C.
41.7
41.4
35.4
34.1
26.2
42.8
42.7
37.1
35.6
27.2
43.9
43.9
38.9
37.1
28.2
KW
6.34
6.34
6.31
6.40
6.54
6.38
6.38
6.33
6.44
6.55
6.41
6.41
6.35
6.47
6.57
125
T.C.
38.4
41.2
37.8
41.5
46.2
39.3
41.2
38.5
41.9
46.3
40.3
41.2
39.1
42.3
46.5
S.C.
38.2
39.2
33.6
32.3
25.0
39.2
40.0
35.3
33.8
26.0
40.2
40.8
37.0
35.3
27.0
KW
7.04
7.04
7.00
7.10
7.27
7.09
7.09
7.02
7.14
7.29
7.14
7.14
7.04
7.18
7.31
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC60
1.00
1.00
1.00
–
FC/MC62
1.01
1.03
1.01
–
FC64
1.05
1.08
1.02
–
UC60
0.97
0.95
1.00
RFCX60DE
–
1.03
1.05
0.98
RFCX60DP
–
1.00
1.00
1.00
MX20D
FC/MC60D
0.99
0.97
0.95
MX20D
FC/MC62D
1.03
1.04
0.96
MX20D
FC64D
1.05
1.05
0.94