• Locate at least one smoke alarm on every floor level.
• Locate a smoke alarm in any area where a smoker sleeps or where electrical appliances are

operated in sleeping areas.

• Smoke, heat and other combustion products rise to the ceiling and spread horizontally. Mounting

the smoke alarm on the ceiling in the center of the room places it closest to all points in the room.
Ceiling mounting is preferred in ordinary residential construction. However, in mobile homes, wall
mounting on an inside partition is preferred to avoid the thermal barrier that may form at the ceiling.

• When mounting smoke alarm on the ceiling, locate it a minimum of 4" (10cm) from a side wall or

corner (see Diagram A).

• When mounting smoke alarm on a wall, if local codes allow, use an inside wall with the top edge

of the smoke alarm a minimum of 4" (10cm) and a maximum of 12" (30.5cm) below the ceiling/
wall intersections (See Diagram A).

Page 3

Sloped Ceilings (Peaked Ceilings):
Smoke alarms or smoke detectors mounted on a peaked ceiling shall be located within 36 in. (914 mm)
horizontally of the peak, but not closer than 4 in. (102 mm) vertically to the peak.

Sloped Ceilings (Shed Ceilings):
Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft. in 8 ft. (1 m
in 8 m) horizontally shall be located within 36 in. (914 mm) of the high side of the ceiling, but not closer
than 4 in. (102 mm) from the adjoining wall surface.

Tray-Shaped Ceilings:
Smoke Alarms or smoke detectors shall be installed on the highest portion of the ceiling or on the sloped
portion of the ceiling within 12 in. (305 mm) vertically down from the highest point.

Mobile Home Installation:
For minimum protection, smoke alarms  should be installed in compliance with H.U.D. Manufactured Home
Construction Safety Standards, Title 24 CFR, Section 3280.208 and Section 3282. For additional protection,
see Single Story Residence smoke alarm requirements/recommendations for Existing Homes and New
Construction Homes.

Note: For mobile homes built before 1978, install smoke alarms on inside walls between 4” and 12” from
the ceiling (older mobile homes have little or no insulation in the ceiling). This is especially important if the
ceiling is unusually hot or cold.

Install a smoke alarm inside each bedroom and in the hallway outside each separate sleeping area.

Existing Homes:
The NFPA requires a smoke alarm on every level and outside each sleeping area in existing construction.
An existing household with one level and one sleeping area is required to have one smoke alarm.

New Construction Homes and Manufactured Homes:
The NFPA requires AC-powered, interconnected smoke alarms to be installed inside each bedroom, outside
each bedroom area, and on every level of the home. They also require a minimum of two AC-powered,
interconnected smoke alarms in any new construction home.

AVOID THESE LOCATIONS

• the garage – products of combustion are produced when you start your vehicle.
• near appliances or areas where normal combustion regularly occurs (kitchens, near furnaces,

gas hot water heaters). Use smoke alarms with photoelectric sensors or smoke alarms with
Silence Feature  for these areas.

• in areas with high humidity, like bathrooms or areas near dishwashers or washing machines.

Install at least 3 feet (0.9 meters) away from these areas.

• in areas of turbulent air such as air returns or heating and cooling supply vents, smoke alarms

shall not be located where airflow prevents smoke from reaching the alarms.

Summary of Contents for MDS101CN

Page 1: ...t 7 Cautions Warnings 7 Silence Feature 7 Backup Battery Replacement 8 Develop and Practice a Plan of Escape 8 Operational Summary 9 Warranty Back Cover SECURITY INSTRUMENTS INC READ ALL INSTRUCTIONS...

Page 2: ...rms A SMOKE ALARM MAY NOT ALWAYS WARN YOU ABOUT FIRES CAUSED BY CARELESSNESS AND SAFETY HAZARDS LIKE SMOKING IN BED VIOLENT EXPLOSIONS ESCAPING GAS IMPROPER STORAGE OF FLAMMABLE MATERIALS OVERLOADED E...

Page 3: ...Home Installation For minimum protection smoke alarms should be installed in compliance with H U D Manufactured Home Construction Safety Standards Title 24 CFR Section 3280 208 and Section 3282 For a...

Page 4: ...ting one or both of these features deters someone from removing the smoke alarm from the mounting bracket or removing the battery from the alarm The breakaway locking pins are clearly marked and molde...

Page 5: ...smoke and carbon monoxide natural gas alarms 6 other initiating alarms which may be a combination of USI ELECTRIC or UNIVERSAL CO Alarms and Heat Alarms and six other non initiating devices such as U...

Page 6: ...0 Ohms 2 Attach the mounting bracket to the electrical junction box 3 To activate 9 volt battery and alarm hold the QUICK DRAW R battery drawer closed pull and remove the PULL TAB Confirm that the ent...

Page 7: ...a non interconnected installation it is necessary to test each alarm by pressing and releasing the Test Silence button to determine the originating alarm RESET To reset the QUICK FIND Alarm Originatio...

Page 8: ...he smoke alarm Return the smoke alarm for servicing See warranty for instructions or in warranty returns There will be a service charge for repairing out of warranty smoke alarms DEVELOP AND PRACTICE...

Page 9: ...Stays On Condition One alarm has sensed smoke Recommendation QUICKFIND AlarmOrigination Inaninterconnected system it is difficult to determine which alarm initiated the alarms to sound The QUICK FIND...

Page 10: ...T WARRANT AND SPECIFICALLY DISCLAIMS ANY WARRANTY WHETHER EXPRESS OR IMPLIED OF FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THE WARRANTY CONTAINED HEREIN NO IMPLIED WARRANTY ON THIS PRODUCT CREATED BY...

Reviews: