This model comprises a total of 22 inputs and 8 relay, 4 npn outputs. Input functionality can be 
adapted as follows: 

1. 22 inputs may be used as digital inputs. They may be wired, in a group, and set to either  

npn or pnp via a single jumper. 

  In addition, according to jumper settings and appropriate wiring:  

- Inputs 14 and 15 can function as either digital or analog inputs. 
- Inputs 0, 2, and 4 can function as high-speed counters, as part of a shaft-encoder,  

or as normal digital inputs.  

- Inputs 1, 3, and 5 can function as either counter reset, as part of a shaft-encoder,  

or as normal digital inputs. 

- If inputs 0, 2 and 4 are set as high-speed counters (without reset), inputs 1, 3 and 5  

can function as normal digital inputs. 

Input Jumper Settings

The tables below show how to set a specific jumper to change input functionality. To access the I/O 
jumpers, you must open the controller according to the instructions beginning on page 9.

 

Incompatible jumper settings and wiring connections may seriously damage the controller. 

Digital Inputs 0-21: Set Type 

 

Set to 

JP3 (all Inputs)   

npn (sink) 

 

pnp (source)* 

 

Inputs 14/15: Set as Digital or Analog  

Set to 

JP1 (Input 14) 

JP2 (Input 15) 

Digital* B 

Analog A 

Analog Inputs AN0/AN1: Set Type 

Set to 

JP5 (AN0) 

JP4 (AN1) 

Voltage A 

Current* B 

*Default settings 

I/O Wiring

I/O Configuration 

Summary of Contents for Vision V350-35-TR34

Page 1: ...ed analog weight and temperature measurement I Os via On board I O configuration Model dependent I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Calibrate the touchscreen Stop initialize and reset the PLC To enter Information Mode pre...

Page 2: ...g this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry...

Page 3: ...oller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure...

Page 4: ...5 kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Ins...

Page 5: ...part of a shaft encoder or as normal digital inputs If inputs 0 2 and 4 are set as high speed counters without reset inputs 1 3 and 5 can function as normal digital inputs Input Jumper Settings The tables below show how to set a specific jumper to change input functionality To access the I O jumpers you must open the controller according to the instructions beginning on page 9 Incompatible jumper ...

Page 6: ...Guide 6 Unitronics npn sink Input Wiring Input wiring HSC input wiring pnp source Input Wiring Input wiring HSC input wiring Shaft encoder Analog Input Wiring Analog input wiring current 2 wire Analog input wiring current 3 wire ...

Page 7: ...ect A clamping diode in parallel with each inductive DC load An RC snubber circuit in parallel with each inductive AC load Power Supply A non isolated power supply can be used if a 0V signal is connected to the chassis Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or...

Page 8: ... 1 is type RJ 11 and may be set to either RS232 or RS485 via jumper as shown below By factory default the port is set to RS232 termination ON Use RS232 to download programs from a PC and to communicate with serial devices and applications such as SCADA Use RS485 to create a multi drop network containing up to 32 devices Pinouts The pinouts below show the PLC port signals To connect a PC to a port ...

Page 9: ...tion jumpers must be moved To access the jumpers you must open the controller according to the instructions beginning on page 9 Opening the Controller Before performing these actions touch a grounded object to discharge any electrostatic charge Avoid touching the PCB board directly Hold the PCB board by its connectors 1 Turn off the power supply disconnect and dismount the controller 2 The back co...

Page 10: ... applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any impli...

Reviews: