V350-35-TR20 Installation Guide  

 

 

Unitronics 

 

 

DIN-rail Mounting 

 

1. Snap the controller onto the DIN 

rail as shown in the figure to the 
right. 

 

2. When properly mounted, the 

controller is squarely situated on 
the DIN-rail as shown in the figure 
to the right. 

 

 

Wiring 

 

 

  Do not touch live wires. 

 

  Install an external circuit breaker. Guard against short-circuiting in external wiring. 

  Use appropriate circuit protection devices. 

  Unused pins should not be connected. Ignoring this directive may damage the device. 

  Double-check all wiring before turning on the power supply. 

Caution

 

  To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 

  Do not use tin, solder, or any substance on stripped wire that might cause the wire strand 

to break. 

  Install at maximum distance from high-voltage cables and power equipment. 

Wiring Procedure 

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 

2

–3.31 mm

2

): 

1.  Strip the wire to a length of 7±0.5mm (0.250

–0.300 inches).  

2.  Unscrew the terminal to its widest position before inserting a wire.  

3.  Insert the wire completely into the terminal to ensure a proper connection. 

4.  Tighten enough to keep the wire from pulling free. 

  Input or output cables should not be run through the same multi-core cable or share the same wire. 

  Allow for voltage drop and noise interference with input lines used over an extended distance.  

Use wire that is properly sized for the load. 

  The controller and I/O signals must be connected to the same 0V signal. 

  Connect cable shields to the system earth ground using the shortest and thickest possible wire. 

 

Summary of Contents for Vision OPLC V350-35-TR20

Page 1: ...ital high speed analog weight and temperature measurement I Os via On board I O configuration Model dependent I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information Mode press the i butt...

Page 2: ...t the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs ...

Page 3: ...ller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure ...

Page 4: ...on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ens...

Page 5: ...eset as part of a shaft encoder or as normal digital inputs If inputs 0 2 4 are set as high speed counters without reset inputs 1 3 5 can function as normal digital inputs Input Jumper Settings The tables below show how to set a specific jumper to change input functionality To access the I O jumpers you must open the controller according to the instructions beginning on page 9 Incompatible jumper ...

Page 6: ...0 35 TR20 Installation Guide 6 Unitronics I O Wiring I O Configuration npn Input Wiring Input wiring npn sink HSC input wiring npn sink pnp Input Wiring Input wiring pnp source HSC input wiring pnp source ...

Page 7: ...signal s source The 0V signal of the analog input must be connected to the controller s 0V Relay Outputs Increasing Contact Life Span To increase the life span of the relay output contacts and protect the device from potential damage by reverse EMF connect A clamping diode in parallel with each inductive DC load An RC snubber circuit in parallel with each inductive AC load ...

Page 8: ...o maximize system performance avoid electromagnetic interference by Mounting the controller on a metal panel Connect each common and ground connection directly to the earth ground of your system For ground wiring use the shortest and thickest possible wire Communication Port Turn off power before making communications connections Caution Signals are related to the controller s 0V the same 0V is us...

Page 9: ... 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B RS232 to RS485 Jumper Settings The figure to the right shows the jumper factory default settings RS232 RS485 termination ON Note that in order To change the communication setting to RS485 both communication standard jumpers must be moved To change the RS485 termination both termination jumpers must be moved To access the jumpers...

Page 10: ...the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but ...

Reviews: