Unitronics  

1

Vision™ OPLC™ 

Installation Guide 
V1040-T20B 

This guide provides basic information for Unitronics’ controllers V1040-T20B.   

General Description 

V1040 OPLCs are programmable logic controllers that comprise a built-in operating panel containing 
a 10.4” Color Touchscreen. The V1040 offers function keys along with a virtual alpha-numeric 
keyboard which is automatically displayed when the application requires the operator to enter data. 

Communications 

2 isolated RS232/RS485 ports 
USB programming port (Mini-B) 
Isolated CANbus port 
The user can order and install an additional port. This may be 
either Ethernet 

or

 serial. 

Communication Function Blocks include: SMS, GPRS, MODBUS 
serial/IP; Protocol FB enables PLC to communicate with almost 
any external device, via serial or Ethernet communications 

I/O Options 

V1040 supports digital, high-speed, 
analog, weight and temperature 
measurement I/Os via: 

Snap-in I/O Modules
Plug into the back of the 
controller to provide an on-
board I/O configuration 
I/O Expansion Modules
Local or remote I/Os may be 
added via expansion port or 
CANbus. 

 

Installation instructions and other data may be found in the module’s technical 
specification sheet. 

Information Mode 

This mode enables you to: 

Calibrate the touchscreen 
View & Edit operand values, COM port settings, RTC and screen 
contrast/brightness settings 
Stop, initialize, and reset the PLC 

To enter Information Mode, press the touchscreen and maintain contact for 
several seconds. 

Programming 
Software,  
& Utilities 

The Unitronics Setup CD contains VisiLogic software and other utilities 

VisiLogic
Easily configure hardware and write both HMI and Ladder control 
applications; the Function Block library simplifies complex tasks 
such as PID. Write your application, and then download it to the 
controller via the programming cable included in the kit. 
Utilities
These include UniOPC server, Remote Access for remote 
programming and diagnostics, and DataXport for run-time data 
logging. 

To learn how to use and program the controller, as well as use utilities such as 
Remote Access, refer to the VisiLogic Help system. 

 

Summary of Contents for Vision OPLC V1040-T20B

Page 1: ... controller to provide an on board I O configuration I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Installation instructions and other data may be found in the module s technical specification sheet Information Mode This mode enables you to Calibrate the touchscreen View Edit operand values COM port settings RTC and screen contrast brightness settings Stop in...

Page 2: ...nsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissibl...

Page 3: ...ver on the rear of the controller 1 Remove the battery cover shown on page 4 The polarity is marked on the battery holder and on the battery 2 Insert the battery ensuring that the polarity symbol on the battery is facing up aligned with the symbol on the holder 3 Replace the battery cover Mounting Dimensions Note that the LCD screen may have a single pixel that is permanently either black or white...

Page 4: ...he right 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the 8 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut ...

Page 5: ...Power Supply The controller V1040 T20B requires either an external 12 or 24VDC power supply Permissible input voltage range 10 2 28 8VDC with less than 10 ripple The power supply must include double insulation Outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin Install an external circuit breaker Guard again...

Page 6: ...ontaining up to 32 devices Pinouts The pinouts below show PLC port signals To connect a PC to a port that is set to RS485 remove the RS485 connector and connect the PC to the PLC via the programming cable Note that this is possible only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description Pin 1 1 DTR signal 1 A signal 2 0V refe...

Page 7: ...ith the slots on the controller as shown below 3 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned Removing a Snap in I O Module 1 Locate the four buttons on the sides of the controller two on either side 2 Press the buttons and hold them down to open the locking mechanism 3 Gently rock the module...

Page 8: ...at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of ...