6 / 0 5
V 2 0 0 - 1 8 - E 4 X B
S n a p - i n I / O M o d u l e
Unitronics
13
Analog/ PT100/ TC Inputs
Number of inputs
4
Type of input
Set via appropriate wiring and jumper settings.
Analog Inputs Power Supply
Galvanic isolation
Analog/PT/TC inputs to bus
Yes
Analog/PT/TC inputs to
analog outputs
Yes
Analog /PT/TC inputs to
Analog /PT/TC inputs
No
Analog inputs
Input range
0-10V, 0-20mA , 4-20mA
Power supply
See Analog I/O’s Power Supply above
Conversion method
Succesive approximation
Resolution at 0-10V,
0-20mA
14-bit (16384 units). See Note 7.
Resolution at 4-20mA
3277 to 16383 (13107 units). See Note 7.
Conversion time
Synchronized to cycle time
Input impedance
>1M
Ω
—voltage
121.5
Ω
—current
Absolute maximum rating
±20V—voltage
±40mA—current
Full-scale error
±0.4%
Linearity error
±0.04%
Status indication
Notes:
7.
12 or 14-bit resolution may be selected via software.
8.
The analog value can indicate faults as shown below:
Value Possible
Cause
16384 Input value deviates
slightly above
the input range
32767 -Input value deviates
greatly above
or
below
the input range
-Power supply disconnected