background image

Cara Bereck Levy 

 

  

Unitronics  

 

V200-18-E4XB   

 Snap-in I/O  Module     

 

The V200-18-E4XB  
plugs directly into the 
back of compatible 
Unitronics OPLCs, 
creating a self-
contained PLC unit 
with a local I/O 
configuration. 

Features 

„

 

18 isolated digital inputs, includes 2 H.S.C inputs, type pnp/npn 
(source/sink) 

„

 

15 isolated pnp (source) outputs  

„

 

2 isolated pnp/npn (source/sink) transistor outputs, includes 2 H.S. outputs 

„

 

4 isolated analog/PT100/TC inputs 

„

 

4 isolated analog outputs  

„

 

Before using this product, it is the responsibility of the user to read and understand this document 
and any accompanying documentation. 

„

 

All examples and diagrams shown herein are intended to aid understanding, and do not guarantee 
operation.  Unitronics accepts no responsibility for actual use of this product based on these 
examples. 

„

 

Please dispose of this product in accordance with local and national standards and regulations. 

„

 

Only qualified service personnel should open this device or carry out repairs. 

 

User safety and equipment protection guidelines 

This document is intended to aid trained and competent personnel in the installation of this equipment as 
defined by the European directives for machinery, low voltage, and EMC.  Only a technician or engineer trained 
in the local and national electrical standards should perform tasks associated with the device’s electrical wiring. 

Symbol Meaning 

Description 

 

Danger 

The identified danger causes physical 
and property damage. 

 

Warning 

The identified danger can cause 
physical and property damage. 

Symbols are used to highlight 
information relating to the user’s 
personal safety and equipment 
protection throughout this document.  
When these symbols appear, the 
associated information must be read 
carefully and understood fully. 

Caution

  

Caution Use 

caution. 

 

„

 

Failure to comply with appropriate safety guidelines can result in severe personal injury 
or property damage.  Always exercise proper caution when working with electrical 
equipment. 

 

„

 

Check the user program before running it. 

„

 

Do not attempt to use this device with parameters that exceed permissible levels. 

„

 

Install an external circuit breaker and take appropriate safety measures against short-
circuiting in external wiring. 

„

  To avoid damaging the system, do not connect / disconnect the device when the power 

is on. 

Caution 

„

 

Ascertain that terminal blocks are properly secured in place. 

Environmental Considerations 

 

 

„

 

Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, 
moisture or rain, excessive heat, regular impact shocks or excessive vibration. 

 

 

„

 

Provide proper ventilation by leaving at least 10mm of space between the top and 
bottom edges of the device and the enclosure walls. 

„

 

Do not place in water or let water leak onto the unit. 

„

 

Do not allow debris to fall inside the unit during installation. 

 

i4 Automation Ltd - 01480 395256

Summary of Contents for V200-18-E4XB

Page 1: ... with the device s electrical wiring Symbol Meaning Description Danger The identified danger causes physical and property damage Warning The identified danger can cause physical and property damage Symbols are used to highlight information relating to the user s personal safety and equipment protection throughout this document When these symbols appear the associated information must be read caref...

Page 2: ...e wire do not exceed a maximum torque of 0 5 N m 5 kgf cm Do not use tin solder or any other substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment I O Wiring General Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference wi...

Page 3: ...al input wiring pnp source digital input wiring npn sink high speed counter pnp source high speed counter Inputs I0 I1 and I2 I3 can be used as shaft encoders as shown below npn sink shaft encoder wiring pnp source shaft encoder wiring i4 Automation Ltd 01480 395256 ...

Page 4: ...s 9 10 11 12 13 14 15 and 16 In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Transistor Outputs Outputs 0 and 1 can function as either npn or pnp in accordance with jumper settings and wiring Open the device and set the jumpers according to the instructions beginning on page 8 Outputs 2 to 16 function as p...

Page 5: ...e to the 0V terminal In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Since the analog I O power supply is isolated the controller s 24VDC power supply may also be used to power the analog I Os The 24VDC power supply must be turned on and off simultaneously with the controller s power supply i4 Automation L...

Page 6: ...e In order to function correctly the analog power supplies must be wired as shown on page 5 To ensure proper performance a warm up period of a half an hour is recommended Analog Inputs Inputs may be wired to work with either current or voltage When set to current voltage all inputs share a common ACM signal current current voltage RTD Inputs 1 Wire one lead of each RTD input to the common signal C...

Page 7: ...iguration note that in order to set mV inputs thermocouple jumper settings are used Thermocouple Analog Outputs Shields should be earthed connected to the earth of the cabinet An output can be wired to either current or voltage Use the appropriate wiring as shown below Open the device and set the jumpers according to the instructions beginning on page 8 To ensure proper performance a warm up perio...

Page 8: ...ectly by holding the PCB board by its connectors Accessing the Jumpers First remove the snap in module 1 Locate the 4 buttons on the sides of the module two on either side Press the 2 buttons on either side of the module as shown and hold them down to open the locking mechanism 2 Gently rock the module from side to side easing the module from the controller 3 Using a Philips screwdriver remove the...

Page 9: ... Voltage Current T C or mV PT100 14 A B B A 13 A B B A Analog input 3 12 A A B B 11 A B B A 10 A B B A Analog input 2 9 A A B B 8 A B B A 7 A B B A Analog input 1 6 A A B B 5 A B B A 4 A B B A Bottom PCB board Analog input 0 3 A A B B Digital Output Jumpers Jumper PNP NPN Digital Output 0 1 A B Note that Jumpers 15 16 are not used Digital Output 1 2 A B i4 Automation Ltd 01480 395256 ...

Page 10: ...ing Reassembling the controller 1 Return the PCB board to the module and secure the center screw 2 Next reinstall the module Line the circular guidelines on the controller up with the guidelines on the Snap in I O Module as shown below 3 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned i4 Automat...

Page 11: ...speed counter or as part of a shaft encoder In each case high speed input specifications apply When used as a normal digital input normal input specifications apply 2 Inputs 1 and 3 can each function as either counter reset or as a normal digital input in either case its specifications are those of a normal digital input These inputs may also be used as part of a shaft encoder In this case high sp...

Page 12: ... See Note 6 pnp 2kHz npn 50kHz ON voltage drop pnp 0 5VDC maximum npn 0 4VDC maximum Short circuit protection Yes pnp only pnp source power supply See Digital Output s Power Supply above npn sink power supply operating voltage 3 5V to 28 8VDC unrelated to the voltage of either the I O module or the controller Notes 5 Outputs 0 1 2 3 4 5 6 7 and 8 share a common power signal Outputs 8 9 10 11 12 13...

Page 13: ...imation Resolution at 0 10V 0 20mA 14 bit 16384 units See Note 7 Resolution at 4 20mA 3277 to 16383 13107 units See Note 7 Conversion time Synchronized to cycle time Input impedance 1MΩ voltage 121 5Ω current Absolute maximum rating 20V voltage 40mA current Full scale error 0 4 Linearity error 0 04 Status indication Yes See Note 8 Notes 7 12 or 14 bit resolution may be selected via software 8 The ...

Page 14: ...uts Input range As shown in the table on page 15 See Note 11 Conversion method Voltage to frequency Resolution 0 1 C 0 1 F maximum Conversion time 100mS minimum per channel depending on software filter type Input impedance 10MΩ Cold junction compensation Local automatic Cold junction compensation error 1 5 C 2 7 F maximum Absolute maximum rating 0 6VDC Full scale error 0 4 Linearity error 0 04 War...

Page 15: ...e Analog Outputs Number of outputs 4 single ended Output range 0 10V 4 20mA See Note 13 Resolution 12 bit 4096 units Conversion time Synchronized to scan time Load impedance 1kΩ minimum voltage 500Ω maximum current Galvanic isolation Analog outputs to bus Yes Analog outputs to Analog PT TC inputs Yes Analog outputs to analog outputs No Linearity error 0 1 Operational error limits 0 2 Notes 13 Note...

Page 16: ...merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this document Unitronics assumes no responsibility for the use of any parts compon...

Reviews: