Unitronics V200-18-E3XB Manual Download Page 12

V 2 0 0 - 1 8 - E 3 X B      

S n a p - i n   I / O     M o d u l e

6 / 0 5

 

12 

Unitronics 

Relay Outputs 

Number of outputs 

15 relays (in two groups). See Note 4. 

Output type 

SPST-NO (Form A) 

Isolation

By relay

Type of relay 

Tyco PCN-124D3MHZ or compatible 

Outputs’ power supply  

See Digital Output’s Power Supply above 

Galvanic isolation 

Relay outputs to bus 

Yes 

Group to group, relay 
outputs 

Yes 

Relay to transistor outputs 

Yes 

Output current 

3A maximum per output (resistive load) 
8A maximum total for common (resistive load) 

Rate voltage 

250VAC / 30VDC 

Minimun load 

1mA@5VDC 

Life expectancy 

100k operations at maximum load 

Response time 

10mS (typical) 

Contact protection 

External precautions required (see Increasing Contact Life Span, p.4) 

Notes: 

4.

Outputs #2,3,4,5,6 and 7 share a common signal. Outputs #8,9,10,11,12,13,14,15 and 16
share a common signal

Transistor Outputs  

Number of outputs 

2, high-speed. Each can be individually set as pnp (source) or npn (sink) via 
wiring and jumper settings. See Note 5. 

Output type 

pnp: P-MOSFET (open drain)  
npn: N-MOSFET (open drain)  

Galvanic isolation 

Transistor outputs to bus 

Yes 

Transistor outputs to 
transistor outputs 

No 

Transistor outputs to relay 
outputs 

Yes 

Output current 

pnp: 0.5A maximum per output 
npn: 50mA maximum per output 

Maximum frequency 

Resistive load  
pnp: 2kHz 
npn: 50kHz 
Inductive load  
0.5Hz 

ON voltage drop 

pnp: 0.5VDC maximum 
npn: 0.4VDC maximum 

Short circuit protection  

Yes (pnp only) 

pnp (source) power supply 

See Digital Output’s Power Supply above 

npn (sink) power supply 

operating voltage  

3.5V to 28.8VDC,  
unrelated to the voltage of either the I/O module or the controller 

Notes: 

5.

Both transistor outputs may be used as high-speed outputs.

Summary of Contents for V200-18-E3XB

Page 1: ...ated with the device s electrical wiring Symbol Meaning Description Danger The identified danger causes physical and property damage Warning The identified danger can cause physical and property damage Symbols are used to highlight information relating to the user s personal safety and equipment protection throughout this document When these symbols appear the associated information must be read c...

Page 2: ...oid damaging the wire do not exceed a maximum torque of 0 5 N m 5 kgf cm Do not use tin solder or any other substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment I O Wiring General Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise ...

Page 3: ... npn sink digital input wiring pnp source digital input wiring npn sink high speed counter pnp source high speed counter Inputs I0 I1 and I2 I3 can be used as shaft encoders as shown below npn sink shaft encoder wiring pnp source shaft encoder wiring ...

Page 4: ...power supply specifications connect the device to a regulated power supply Relay Outputs Each output can be wired separately to either AC or DC as show below The 0V signal of the relay outputs is isolated from the controller s 0V signal Increasing Contact Life Span To increase the life span of the relay output contacts and protect the device from potential damage by reverse EMF connect a clamping ...

Page 5: ... source Analog I O Power Supplies Use a 24VDC power supply for all analog input and output modes 1 Connect the positive cable to the V2 terminal and the negative to the 0V terminal In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Since the analog I O power supply is isolated the controller s 24VDC power sup...

Page 6: ...he signal source In order to function correctly the analog power supplies must be wired as shown on page 5 To ensure proper performance a warm up period of a half an hour is recommended Analog Inputs Inputs may be wired to work with either current or voltage When set to current voltage all inputs share a common ACM signal current current voltage RTD Inputs 1 Wire one lead of each RTD input to the ...

Page 7: ...gs Hardware Configuration note that in order to set mV inputs thermocouple jumper settings are used Thermocouple Analog Outputs Shields should be earthed connected to the earth of the cabinet An output can be wired to either current or voltage Use the appropriate wiring as shown below Open the device and set the jumpers according to the instructions beginning on page 8 To ensure proper performance...

Page 8: ...e PCB board directly by holding the PCB board by its connectors Accessing the Jumpers First remove the snap in module 1 Locate the 4 buttons on the sides of the module two on either side Press the 2 buttons on either side of the module as shown and hold them down to open the locking mechanism 2 Gently rock the module from side to side easing the module from the controller 3 Using a Philips screwdr...

Page 9: ... Jumpers Jumper Voltage Current T C or mV PT100 14 A B B A 13 A B B A Analog input 3 12 A A B B 11 A B B A 10 A B B A Analog input 2 9 A A B B 8 A B B A 7 A B B A Analog input 1 6 A A B B 5 A B B A 4 A B B A Bottom PCB board Analog input 0 3 A A B B Digital Output Jumpers Jumper PNP NPN Digital Output 0 1 A B Note that Jumpers 15 16 are not used Digital Output 1 2 A B ...

Page 10: ...lt factory setting Reassembling the controller 1 Return the PCB board to the module and secure the center screw 2 Next reinstall the module Line the circular guidelines on the controller up with the guidelines on the Snap in I O Module as shown below 3 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly ali...

Page 11: ...s Notes 1 Inputs 0 and 2 can each function as either high speed counter or as part of a shaft encoder In each case high speed input specifications apply When used as a normal digital input normal input specifications apply 2 Inputs 1 and 3 can each function as either counter reset or as a normal digital input in either case its specifications are those of a normal digital input These inputs may al...

Page 12: ...d 7 share a common signal Outputs 8 9 10 11 12 13 14 15 and 16 share a common signal Transistor Outputs Number of outputs 2 high speed Each can be individually set as pnp source or npn sink via wiring and jumper settings See Note 5 Output type pnp P MOSFET open drain npn N MOSFET open drain Galvanic isolation Transistor outputs to bus Yes Transistor outputs to transistor outputs No Transistor outp...

Page 13: ...nputs to Analog PT TC inputs No Analog inputs Input range 0 10V 0 20mA 4 20mA Power supply See Analog I O s Power Supply above Conversion method Succesive approximation Resolution at 0 10V 0 20mA 14 bit 16384 units See Note 6 Resolution at 4 20mA 3277 to 16384 13107 units See Note 6 Conversion time Synchronized to cycle time Input impedance 1MΩ voltage 121 5Ω current Absolute maximum rating 20V vo...

Page 14: ...hermocouple inputs Input range As shown in the table on page 15 See Note 10 Conversion method Voltage to frequency Resolution 0 1 C 0 1 F maximum Conversion time 100mS minimum per channel depending on software filter type Input impedance 10MΩ Cold junction compensation Local automatic Cold junction compensation error 1 5 C 2 7 F maximum Absolute maximum rating 0 6VDC Full scale error 0 4 Linearity...

Page 15: ...ue Red White Blue Analog Outputs Number of outputs 4 single ended Output range 0 10V 4 20mA See Note 12 Resolution 12 bit 4096 units Conversion time Synchronized to scan time Load impedance 1kΩ minimum voltage 500Ω maximum current Galvanic isolation Analog outputs to bus Yes Analog outputs to Analog PT TC inputs Yes Analog outputs to analog outputs No Linearity error 0 1 Operational error limits 0...

Page 16: ...s representatives as well as a U S subsidiary For more information regarding Unitronics products contact your distributor or Unitronics headquarters via email export unitronics com Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 343 287 19 19 yekaterinburg klinkmann spb ru St Petersburg tel 7 812 327 3752 klinkmann klinkmann spb ru Moscow tel 7 495 641 1616 moscow klinkmann ...

Reviews: