![Unitronics V200-18-E3B Manual Download Page 12](http://html.mh-extra.com/html/unitronics/v200-18-e3b/v200-18-e3b_manual_845602012.webp)
V200-18-E3B
S n a p - i n I / O M o d u l e
11/04
12
Unitronics Industrial Automation
Relay Outputs
Number of outputs
15 (in two groups). See Note 4.
Output type
SPST-NO relay; 230VAC / 24VDC
Type of relay
Takamisawa (Fujitsu) NY-24W-K or NAIS (Matsushita) PA1a-24V
Outputs’ power supply
See Digital Output’s Power Supply above
Galvanic isolation
Relay outputs to bus
Yes
Group to group, relay
outputs
Yes
Relay to transistor outputs
Yes
Output current
Resistive Load
3A maximum per output
8A maximum total for common. See Note 4.
Inductive Load
1A maximum per output
4A maximum total for common. See Note 4.
Maximum frequency
0.5Hz (at maximum rated load)
Contact protection
External precautions required (see Increasing Contact Life Span, p.4)
Notes:
4.
Outputs #2,3,4,5,6 and 7 share a common signal. Outputs #8,9,10,11,12,13,14,15 and 16
share a common signal
Transistor Outputs
Number of outputs
2, high-speed. Each can be individually set as pnp (source) or npn (sink) via
wiring and jumper settings. See Note 5.
Output type
pnp: P-MOSFET (open drain)
npn: N-MOSFET (open drain)
Galvanic isolation
Transistor outputs to bus
Yes
Transistor outputs to
transistor outputs
No
Transistor outputs to relay
outputs
Yes
Output current
pnp: 0.5A maximum per output
npn: 50mA maximum per output
Maximum frequency
Resistive load
pnp: 2kHz
npn: 50kHz
Inductive load
0.5Hz
ON voltage drop
pnp: 0.5VDC maximum
npn: 0.4VDC maximum
Short circuit protection
Yes (pnp only)
pnp (source) power supply
See Digital Output’s Power Supply above
npn (sink) power supply
operating voltage
3.5V to 28.8VDC,
unrelated to the voltage of either the I/O module or the controller
Notes:
5.