background image

10/06 

V200-18-E2B   

S n a p - i n   I / O   M o d u l e

 

Unitronics 

 

 

Analog Outputs 

Wiring the Analog Outputs’ Power Supply 

1. 

Connect the "positive" cable to the "+V" terminal, and the “negative” to the "0V" terminal.   

„

 

The analog 0V signal must be the same 0V used by the controller’s power supply.  

„

 

A non-isolated power supply can be used provided that a 0V signal is connected to the chassis.  

„

 

Do not connect the ‘Neutral’ or ‘Line’ signal of the 110/220VAC to the device’s 0V pin. 

„

  In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the 

device to a regulated power supply. 

 

The 24VDC power supply must be turned on and off simultaneously with the controller’s  
power supply. 

Output Wiring 

„

 

Shields should be earthed, connected to the earth of the cabinet. 

„

 

An output can be wired to either current or voltage. 

„

 

Do not use current and voltage from the same source channel. 

current/voltage 

 

 

Summary of Contents for V200-18-E2B

Page 1: ...d with the device s electrical wiring Symbol Meaning Description Danger The identified danger causes physical and property damage Warning The identified danger can cause physical and property damage Symbols are used to highlight information relating to the user s personal safety and equipment protection throughout this document When these symbols appear the associated information must be read care...

Page 2: ...the controller You must remove this cap before installing a module 1 Pry the cap off using the blade of a screwdriver 2 Line the circular guidelines on the controller up with the guidelines on the module as shown below 3 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned Removing a Snap in I O Modu...

Page 3: ...maximum torque of 0 5 N m 5 kgf m Do not use tin solder or any other substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment I O Wiring General Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with input lines used over...

Page 4: ... npn sink digital input wiring pnp source digital input wiring npn sink high speed counter pnp source high speed counter Inputs I0 I1 and I2 I3 can be used as shaft encoders as shown below npn sink shaft encoder wiring pnp source shaft encoder wiring ...

Page 5: ...mity to voltage power supply specifications connect the device to a regulated power supply Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin Relay Outputs The 0V signal of the relay outputs is isolated from the controller s 0V signal Increasing Contact Life Span To increase the life span of the relay output contacts and protect the device from potential damage by r...

Page 6: ...gnal of the transistor outputs is isolated from the controller s 0V signal npn sink pnp source Analog Inputs Shields should be connected at the signal source Inputs may be wired to work with either current or voltage Note that the analog input s 0V signal must be the same 0V used by the controller s power supply current current voltage ...

Page 7: ...d to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply The 24VDC power supply must be turned on and off simultaneously with the controller s power supply Output Wiring Shields should be earthed connected to the ear...

Page 8: ...ital input normal input specifications apply 2 Inputs 1 and 3 can each function as either counter reset or as a normal digital input in either case its specifications are those of a normal digital input These inputs may also be used as part of a shaft encoder In this case high speed input specifications apply Relay Outputs Number of outputs 10 See Note 3 Output type SPST NO relay Form A Isolation ...

Page 9: ...m See Note 4 Short circuit protection Yes pnp only Power supply operating voltage 20 4 to 28 8VDC nominal operating voltage 24VDC npn sink power supply operating voltage 3 5V to 28 8VDC unrelated to the voltage of either the I O module or the controller Notes 4 Outputs 12 and Output 13 may be used as high speed outputs Analog Inputs Number of inputs 2 single ended Input range 0 10V 0 20mA 4 20mA S...

Page 10: ...entatives as well as a U S subsidiary For more information regarding Unitronics products contact your distributor or Unitronics headquarters via email export unitronics com The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features...