Warnings

:

- Unused pins should not be connected. Ignoring this directive may

damage the controller.

- Improper use of this product may severely damage the controller.
- Refer to the controller's User Guide regarding wiring considerations.
-  Before using this product, it is the responsibility of the user to read the

product's User Guide and all accompanying documentation.

npn (sink) high-speed counter

Shaft encoder

pnp (source) high-speed counter

Power supply, pnp (source) inputs

I16
I17
I18
I19
I20
I21

+V

0V 24VDC

See Note 6
Circuit

protection

device

I1

I0

I3

I2

I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15

I16
I17
I18
I19
I20
I21

+V

0V

24VDC

Circuit

protection

device

I1

I0

I3

I2

I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15

Graphic

 

O

perator Panel &

 

P

rogrammable

 

L

ogic

 

C

ontroller

®

24 VDC, 22 pnp/npn digital inputs, including 2 analog inputs

1

 and 3 high-speed counter/shaft

encoder inputs, 12 relay outputs, I/O expansion port, 2 RS232/RS485 ports

Power supply

24VDC

Permissible range

20.4VDC to 28.8VDC with less 

than 10% ripple

Maximum current consumption

290mA@24VDC

Digital inputs

22 pnp (source) or npn (sink) 

inputs. See Notes 1 and 2

Nominal input voltage

24VDC. See Note 3.

Input voltages for pnp (source):

0-5VDC for Logic ‘0’

17-28.8VDC for Logic ‘1’

Input voltages for npn (sink):

17-28.8VDC/<1mA for Logic ‘0’

0-5VDC/>3mA for Logic ‘1’

Input current

3.7mA@24VDC

Input impedance

6.5K

W

Response time

10mS typical

(except high-speed inputs)

Galvanic isolation

None

Input cable length

Up to 100 meters, unshielded

High-speed counter

Specifications below apply

 

when 

inputs are wired for use as a high-

speed counter input/shaft 

encoder. See Notes 4 and 5.

Resolution

32-bit

Input freq.

10kHz max.

Minimum pulse

40µs

1

Notes:

1. The total number of inputs is 22. All of these may be used as normal digital

inputs. Via jumper settings and wiring, certain of these inputs may be
adapted to analog inputs.

2. All 22 inputs can be set to pnp (source) or npn (sink) via a single jumper

and appropriate wiring.

3. npn (sink) inputs use voltage supplied from the controller’s power supply.
4. Inputs #0, #2 and #4 can each function as either high-speed counter or as

part of a shaft encoder. In each case, high-speed input specifications apply.
When used as a normal digital input, normal input specifications apply.

5. Inputs #1, #3 and #5 can each function as either counter reset, or as a normal

digital input; in either case, specifications are those of a normal digital input.
These inputs may also be used as part of a shaft encoder.
In this case, high-speed input specifications apply.

6. To avoid electromagnetic interference, mount the controller in a metal

panel/cabinet and earth the power supply. Earth the power supply signal to
the metal using a wire whose length does not exceed 10cm.
If your conditions do not permit this, do not earth the power supply.

V

120-22-R34

V120-22-R34

06/09

Vision

120

TM

ESC

Vision

120

TM

ESC

npn (sink) inputs

+V

High-speed

Counter

0V

24VDC

Circuit

protection

device

I1

I0

I3

I2

I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15

High-speed

Counter

I1

I0

I3

I2

I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15

+V
0V

24VDC

Circuit

protection

device

A  B

I1

I0

I3

I2

I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15

+V
0V

24VDC

Circuit

protection

device

Distributed by:
M.A. Selmon Company, Inc
4 Oxford Rd. 
Milford, CT 06460
203-377-3525

Summary of Contents for V120-22-R34

Page 1: ...ts are wired for use as a high speed counter input shaft encoder See Notes 4 and 5 Resolution 32 bit Input freq 10kHz max Minimum pulse 40µs 1 Notes 1 The total number of inputs is 22 All of these may be used as normal digital inputs Via jumper settings and wiring certain of these inputs may be adapted to analog inputs 2 All 22 inputs can be set to pnp source or npn sink via a single jumper and ap...

Page 2: ...an time Absolute max rating 15V 30mA Full scale error 2 LSB Linearity error 2 LSB Status indication Yes See Note Note The analog value can also indicate when the input is functioning out of range If an analog input deviates above the permissible range its value will be 1024 2 Relay outputs 12 relay in 3 groups See Note Output type SPST NO Form A Type of relay Tyco PCN 124D3MHZ or compatible Isolat...

Page 3: ...umber of I Os may vary according to expansion model V120 22 R34 06 09 Keypad Sealed membrane Number of keys 16 Program Application memory 448K Memory Bits coils 4096 Memory Integers registers 2048 Long Integers 32 bit 256 Double Word 32 bit unsigned 64 Floats 24 Timers 192 Counters 24 Data Tables 120K RAM 64K FLASH HMI displays Up to 255 Execution time 0 8µs for bit operations Graphic Display STN ...

Page 4: ...uts JP3 A B Analog 1 I14 JP4 A B B JP2 A A B Analog 0 I15 JP5 A B B V120 22 R34 I O Jumper Setting 5410 1231 9 V120 22 R34 06 09 Default factory setting Opening the controller enclosure 1 Locate the 4 slots on the sides of the enclosure 2 Using the blade of a flat bladed screwdriver gently pry off the back of the controller as shown in the figure below exposing the controller s board Unitronics re...

Reviews: