Installation Guide 

USC-B5-RA28, USC-B10-RA28,  
USC-C5-RA28, USC-C10-RA28, 
USC-B5-TA30, USC-B10-TA30,  
USC-C5-TA30, USC-C10-TA30

 

 

This guide provides basic installation information for specific UniStream

®

 PLC models with 

built-in I/O. Technical specifications may be downloaded from the Unitronics website. 

General Features 

Unitronics’ 

UniStream

®

 PLCs are DIN-rail mounted Programmable Logic Controllers (PLCs) 

with a built-in I/O configuration.  
The series is available in three versions: Pro, Standard, and Basic.  
Note that a model number that includes: 

 

B10/C10

 refers to Pro version (e.g. USC-B

10

-T24) 

 

B5/C5

 refers to Standard version (e.g. USC-B

5

-RA28) 

 

B3/C3

 refers to Basic version (e.g. only for USC-B

3

-T20) 

Page 2 contains a comparison table detailing the features offered by the different models. 

Exact features are detailed in the product specification sheets. 

Power  

Features

 

 

Built-in Trends and Gauges, auto-tuned PID, data tables, data 

sampling, and Recipes 

 

UniApps™: Access & edit data, monitor,

 troubleshoot & debug and 

more  

 

Security: Multi-level password protection 

 

Alarms: Built-in system, ANSI/ISA standards 

COM  

Options

 

 

Built-in ports: 2 Ethernet, 1 USB host, 1 USB device port 

 

Add-on ports (UAC-CB), available by separate order: 

 

1 CANbus port may be added to all models  

 

RS232/485 ports: according to model technical specifications 

COM  

Protocols 

 

Fieldbus: CANopen, CAN Layer2, MODBUS, EtherNetIP and more. 

Implement any serial RS232/485, TCP/IP, or CANbus third-party 

protocols via Message Composer 

 

Advanced: SNMP Agent/Trap, e-mail, SMS, modems, GPRS/GSM, 

FTP Server/Client, Web Server, SQL, and MQTT.  

 

Remote Access via any device that supports VNC. 

Programming 
Software

 

All-in-One UniLogic software for hardware configuration, 
communications, PLC and HMI applications; free download. 

HMI 

All UniStream® PLCs can display HMI screens on the following devices:  

 

UniStream Display (USL)  

 

UniStream Modular HMI panel (USP) 

 

UniStream Built-in (on the panels integral to the device) 

 

Any device screen that supports VNC 

 

 

 

Summary of Contents for UniStream USC-B10-RA28

Page 1: ...in Trends and Gauges auto tuned PID data tables data sampling and Recipes UniApps Access edit data monitor troubleshoot debug and more Security Multi level password protection Alarms Built in system ANSI ISA standards COM Options Built in ports 2 Ethernet 1 USB host 1 USB device port Add on ports UAC CB available by separate order 1 CANbus port may be added to all models RS232 485 ports according ...

Page 2: ... Comparison table Feature B10 C10 Pro B5 C5 Standard B3 C3 Basic I O Expansion via Uni I O Yes No Remote I O Expansion via Ethernet I O Adapter URB Up to 8 1 VFD 32 2 MicroSD Yes No Add on COM modules 3 2 System Memory 6GB 3GB 3GB MODBUS Slaves Unlimited Up to 8 Ethernet IP Scanners 16 1 Ethernet IP Adapters 32 8 Web Server Yes No No SQL Client Yes No No MQTT Yes PID Loops 64 2 Data Sampler Trends...

Page 3: ...nal standards and regulations This product should be installed only by qualified personnel Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels Do not connect disconnect the device when power is on Environmental Considerations Ventilation 10mm space is required between the de...

Page 4: ...Ds 5 Top Door Closed Covers the Confirm button and the USB Host port 6 Bottom Door Closed Covers the internal door protecting the battery and microSD slot 7 Uni COM Jack Connection port for Uni COM CB modules Shipped covered leave cover in place when not in use Top View 8 Ethernet ports Two ports for Ethernet communications 9 Input Output connection points Model dependent Present in models with bu...

Page 5: ...roSD cards 17 Battery Holder The battery is supplied installed the user must remove the pull tab during installation These are available by separate order Installation Space Considerations Allocate space for The controller I O wiring Access to ports jacks and the microSD card slot Any modules that will be installed ensure you allow space to install uninstall modules Module dimensions and installat...

Page 6: ...he event of power off the battery must be connected First Use The battery is protected by the PLC s bottom and inner door The battery is supplied installed inside the unit with a plastic tab preventing contact Pull out this tab before using the device Battery Installation and Replacement Use proper precautions to prevent Electro Static Discharge ESD while servicing the battery Caution To preserve ...

Page 7: ...ould be performed while power is OFF Use over current protection such as a fuse or circuit breaker to avoid excessive currents into the power supply connection point Unused points should not be connected unless otherwise specified Ignoring this directive may damage the device Double check all wiring before turning on the power supply Caution To avoid damaging the wire use a maximum torque of 0 5 N...

Page 8: ...se the shortest and thickest wires possible less than 1m 3 3 in length minimum thickness 14 AWG 2 mm2 Connect the power supply 0V to the earth of the system Earthing the cables shield Connect the cable shield to the earth of the system preferably to the metal cabinet chassis Note that the shield must be connected only at one end of the cable it is recommended to earth the shield at the PLC side Ke...

Page 9: ...s The digital inputs are arranged in two isolated groups I0 I9 share common CM0 I10 I13 share common CM1 Each group may be wired together as sink or source Inputs I10 I11 I12 and I13 can be configured as either normal digital inputs or as high speed inputs that can receive high speed pulse signals from sensors or shaft encoders High Speed Input Modes Following are the different pin assignments for...

Page 10: ...ts Both inputs share the common point CM2 NOTE Each input offers two modes voltage or current You can set each input independently The mode is determined both by wiring and by the hardware configuration within the software application Voltage and current modes use distinct points Connect only the point associated with the selected mode leave the other point unconnected Voltage Differential Single ...

Page 11: ...ower supply port they are neither isolated from each other nor from the analog inputs Therefore temperature inputs isolation may be bypassed when using an exposed junction non isolated thermocouple in conjunction with analog inputs or another exposed junction thermocouple which can lead to flow of unwanted currents through the thermocouple wires that might interfere with thermocouple voltage readi...

Page 12: ...x RA28 To avoid risk of fire or property damage always use a limited current source or connect a current limiting device in series with the relay contacts The relay outputs are arranged in two isolated groups O0 O3 share the common return CM3 O4 O7 share the common return CM4 Increasing Contact Life Span To increase the life span of the relay contacts and protect the controller from potential dama...

Page 13: ...y analog signals wiring do not externally connect CM5 to the system 0V Do not use point CM5 for any purpose other than connecting the analog output load Using it for any other purpose may damage the controller Voltage Current Installing Uni I O Uni COM Modules Refer to the Installation Guides provided with these modules Turn off system power before connecting or disconnecting any modules or device...

Page 14: ...e market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no event shall Unitronics be liable for any speci...