![Unitronics UniStream UAG-XK Series Technical Specifications Download Page 5](http://html.mh-extra.com/html/unitronics/unistream-uag-xk-series/unistream-uag-xk-series_technical-specifications_845574005.webp)
UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-CX-XKPLxxxx, UAG-XKPLxxxx Technical Specifications
Daisy-chaining Configuration Summary
UniStream Modular and UniSream PLC
The tables below show the possible configurations between two cabinets.
Optional configurations in the cabinet
with the UniStream Controller
Optional configurations
in the other cabinet
Controller 1st 2nd
Max.
UniStream
Modular 7"
Max.
UniStream
Modular
10.4",15.6"
Max.
UniStream
PLC
-
-
3
5
8
XK
-
8
8
8
XKP
-
19
21
24
XKP XK
19
21
24
XK
XKP
24
24
24
XKP XKP
35
37
40
3rd
4th
5th
Max.
Modules
XKL
-
-
16
XK
-
16
XKP
-
32
XKP
XK
32
XK
XKP
32
XKP
XKP
48
XK-UAG-XKxxxx (Short Range Local Expansion Adapter without power supply)
XKP-UAG-XKPxxxx (Short Range Local Expansion Adapter with power supply)
XKL-UAG-XKLxxxx (Long Range Local Expansion Adapter)
N
OTE
Each combination in the right table can be used with each combination in the left table. They are
independent of each other and the total number of I/O modules that are supported is the sum of
the two tables.
UniStream™ built-in
You must use the UAG-CX-XKPxxx or UAG-CX-XKPLxxx, and it must be the adapter that is directly
connected to the controller.
Optional configurations in the cabinet
with the UniStream Controller
Optional configurations
in the other cabinet
Controller 1st 2nd Max. Modules
-
-
0
CX
-
16
XK
24
XKP
32
3rd
4th
5th
Max. Modules
XKL
-
-
16
XK
-
16
XKP
-
32
XKP
XK
32
XK
XKP
32
XKP
XKP
48
Environmental
Protection
IP20, NEMA
1
Operating Temperature
-20°C to 55°C (-4°F to 131°F)
Storage Temperature
-30°C to 70°C (-22°F to 140°F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Operating Altitude
2,000 m (6,562 ft)
Shock
IEC 60068-2-27, 15G, 11ms duration
Vibration
IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to
150Hz, 1G acceleration
Unitronics