Unitronics Jazz Micro-OPLC JZ10-11-T17 Installation Manual Download Page 2

JZ10-11-T17

2

Unitronics 

DIN-rail mounting 
Mounting

 

Snap PLC onto the DIN rail

 

Removal 

Push mounting clip down 

35

m

m

(1

.3

7

8"

)

53

m

m

(2

.0

87

")

.

.

Note:

 Removing the unit requires clearance space. Recommendation: approximately 40mm (1.58”). 

 

Wiring 

Note:

 All diagrams are based on the rear view of the OPLC. 

Do not touch live wires. 

Install an external circuit breaker. Guard against short-circuiting in external wiring. 
Use appropriate circuit protection devices. 
Unused pins should not be connected.  Ignoring this directive may damage the device. 
Double-check all wiring before turning on the power supply. 

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 
Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break. 
Install at maximum distance from high-voltage cables and power equipment. 

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 

2

–3.31 mm

2

).  

1. 

Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  

2. 

Unscrew the terminal to its widest position before inserting a wire.  

3. 

Insert the wire completely into the terminal to ensure a proper connection. 

4. 

Tighten enough to keep the wire from pulling free. 

Input or output cables should not be run through the same multi-core cable or share the same wire. 
Allow for voltage drop and noise interference with input lines used over an extended distance.  Use 

wire that is properly sized for the load. 

The controller, I/O signals, and outputs’ power supply must be connected to the same 0V signal. 

Inputs 

This model comprises a total of 10 inputs in 3 groups.  

1.  I0 to I5 are digital inputs. They may be wired, in a group, as either npn or pnp.  
2. 

I6 and I7 may be wired as either digital or analog inputs. These may be wired as either: 

npn digital inputs 
pnp digital inputs 
analog (voltage) inputs 

In addition, 1 input may be wired as a pnp input, while the other is wired as an analog input. 
Note that if 1 input is wired as an npn input, the other may not be wired as an analog input. 

3.  AN0 and AN1 are analog (current) inputs that may be wired using 2, 3, or 4 wires. 

Summary of Contents for Jazz Micro-OPLC JZ10-11-T17

Page 1: ...ce with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Ventilation 10mm space required between the controller s top bottom edges en...

Page 2: ...a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with input lines u...

Page 3: ...pn pnp pins must be connected Input wiring npn sink Input wiring pnp source 0V V 24VDC V 0V I7 I6 I5 I4 I3 I2 24VDC n p I0 5 n p I6 7 I1 HS I0 HS 0V V 24VDC V 0V I7 I6 I5 I4 I3 I2 24VDC n p I0 5 n p I6 7 I1 HS I0 HS Input wiring I0 I5 pnp source I6 I7 npn sink 0V V 24VDC V 0V I7 I6 I5 I4 I3 I2 24VDC n p I0 5 n p I6 7 I1 I0 Digital Outputs Outputs Power Supply Output wiring 0V VO 00 01 02 03 04 05 ...

Page 4: ...etion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a...