IO-DI8-RO8, IO-DI8-RO8-L Technical Specifications 

 

Max. current consumption 

70mA maximum from the adapter’s 5VDC 

Typical power consumption 

0.18W @ 5VDC 

Status indicator  

 

(RUN) 

Green LED: 
—Lit when a communication link is established between module and OPLC.
—Blinks when the communication link fails. 

Inputs 

 

Number of inputs 

8 (in one group) 

Input type 

pnp (source) or npn (sink) 

Galvanic isolation 

None 

Status indicators(IN) 

Green LEDs—Lit when the corresponding input is active. See Note 1. 

Nominal input voltage 

24VDC for IO-DI8-RO8,  12VDC for IO-DI8-RO8-L 

Input voltage 

IO-DI8-RO8 

IO-DI8-RO8-L 

pnp (source) 

0-5VDC for Logic ‘0’  
17-28.8VDC for Logic ‘1’  

0-3VDC for Logic ‘0’  
8-15.6V for Logic ‘1’  

npn (sink), voltage/current 

17-28.8VDC/<1.1 mA for Logic ‘0’ 
0-5VDC/>4.3mA for Logic ‘1’  

8-15.6VDC/<1.1 mA for Logic ‘0’  
0-3VDC/>4.3mA for Logic ‘1’  

Input current 

6mA@24VDC 

6mA@12VDC 

Response time 

10mSec typical 

Input #7 

The specifications below apply when this input is wired for use as a high-
speed counter input/frequency measurer. See Notes 2 and 3. 

Resolution 16-bit 
Frequency 5kHz 

maximum 

Minimum pulse width 

80µs 

Outputs 

 

Number of outputs 

8 relay 

Output type 

SPST-NO (Form A) 
All relays share a common signal 

Isolation By 

relay 

Type of relay 

 

IO-DI8-RO8 

Tyco PCN-124D3MHZ or compatible 

IO-DI8-RO8-L 

Tyco PCN-112D3MHZ or compatible 

Output current 

3A maximum per output (resistive load) 
8A maximum total for common (resistive load). 

Rated voltage 

250VAC / 30VDC 

Minimum load 

1mA@5VDC 

Life expectancy 

100k operations at maximum load 

Response time 

10mS (typical) 

Status Indicators (OUT) 

Red LEDs—Lit when the corresponding output is active. 

Contact protection 

External precautions required  
(see above: Increasing Contact Life Span) 

Outputs’ power supply: IO-DI8-RO8 

 

Nominal operating voltage 

24VDC 

Operating voltage 

20.4 to 28.8VDC 

Maximum current consumption 

70mA@24VDC 

 

Summary of Contents for IO-DI8-RO8-L

Page 1: ...itronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of t...

Page 2: ...derations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during instal...

Page 3: ...odules Unitronics 3 Screw Mounting The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 4: ...k all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Page 5: ...ource or npn sink inputs npn sink inputs pnp source inputs 0V V Circuit Protection Device 0V V npn sink high speed counter frequency measurer pnp source high speed counter frequency measurer 0V V Circuit Protection Device High speed Counter Reset High speed Counter 0V V High speed Counter Reset High speed Counter ...

Page 6: ...ormity to voltage power supply specifications connect the device to a regulated power supply Notes 1 The adapter and output s power supply must be connected to the same 0V signal Outputs Circuit Protection Device L1 L2 L3 115 230VAC V 12 24VDC Output s power supply 0V V N 0V Load See Note 1 Increasing Contact Life Span Both modules have 8 relay outputs To increase the life span of these contacts a...

Page 7: ...Logic 0 0 3VDC 4 3mA for Logic 1 Input current 6mA 24VDC 6mA 12VDC Response time 10mSec typical Input 7 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Outputs Number of outputs 8 relay Output type SPST NO Form A All relays share a common signal Isola...

Page 8: ... number indicates the I O s location in the system This number relates to both the position of the expansion module in the system and to the position of the I O on that module Expansion modules are numbered from 0 7 as shown in the figure below 0 1 2 3 4 5 6 7 Expansion module identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the O...

Reviews: