IO-DI16, IO-DI16-L
I / O E x p a n s i o n M o d u l e s
7/03
6
Unitronics Industrial Automation
IO-DI16, IO-DI16-L Technical Specifications
Max. current consumption
75mA maximum from the adapter’s 5VDC
Typical power consumption
0.2W @ 5VDC
Status indicator
(RUN) Green
LED:
—Lit when a communication link is established between module and OPLC.
—Blinks when the communication link fails.
Inputs
Number of inputs
16 (in two groups)
Input type
pnp (source) or npn (sink)
Galvanic isolation
None
Status indicators
(IN)
Green LEDs—Lit when the corresponding input is active. See Note 1
Nominal input voltage
24VDC for IO-DI16, 12VDC for IO-DI16-L
Input voltage
IO-DI16 IO-DI16-L
pnp (source)
0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
0-3VDC for Logic ‘0’
8-15.6VDC for Logic ‘1’
npn (sink), voltage/current
17-28.8VDC/<1.1 mA for Logic ‘0’
0-5VDC/>4.3mA for Logic ‘1’
8-15.6VDC/<1.1 mA for Logic ‘0’
0-3VDC/>4.3mA for Logic ‘1’
Input current
6mA@24VDC 6mA@12VDC
Response time
10mSec typical
Input #15
The specifications below apply when this input is wired for use as a high-speed
counter input/frequency measurer. See Notes 2 and 3.
Resolution 16-bit
Frequency 5kHz
maximum
Minimum pulse width
80µs
Environmental
IP20 / NEMA1
Operating temperature
0
°
to 50
°
C (32
°
to 122
°
F)
Storage temperature
-20
°
to 60
°
C (-4
°
to 140
°
F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Dimensions (WxHxD)
80mm x 93mm x 60mm (3.15” x 3.66” x 2.362”)
Weight
141g (4.9oz.)
Mounting
Either onto a 35mm DIN-rail or screw- mounted.
Notes:
1.
The inputs' LEDs light up only when communication link is established between module and OPLC.
2.
Input #15 can function either as a high-speed counter, a frequency measurer, or as a normal digital input.
When Input #15 is used as a normal digital input, normal input specifications apply.
3.
Input #14 can function either as the counter’s reset, or as a normal digital input; in either case, its
specifications are those of a normal digital input.