background image

 

Unitronics Industrial Automation Systems 

1   

 

EX90-DI8-RO8    

I/O Expansion Module      8 Inputs, 8 Outputs 

 
 
The EX90-DI8-RO8 is an I/O expansion 
module that can be used in conjunction 
with specific Unitronics OPLC controllers. 
The module offers 8 digital inputs, type 
pnp (source), and 8 relay outputs. 
The EX90-DI8-RO8 is snap-mounted on a 
DIN rail.

 

Component identification 

1 Power 

supply 

Input connection points 

OPLC-module communication port 

Input status indicators 

5 Status 

indicators 

Output status indicators 

Output connection points 

 

07

06

05

04

03

02

01

00

I7

I4

I5

I6

I3

I2

I1

I0

0V

24V

I5

I7

I6

I4

I3

I2

I1

I0

04

03

02

01

00

07

06

05

EX90-DI8-RO8

PWR

RUN

2

3

4

6

1

5

7

 

 

User safety and equipment protection guidelines 

This document is intended to aid trained and competent personnel in the installation of this equipment as defined by 
the European directives for machinery, low voltage and EMC. Only a technician or engineer trained in the local and 
national electrical standards should perform tasks associated with the electrical wiring of this device. 

 

Under no circumstances will Unitronics be liable or responsible for any consequential damage that may arise 
as a result of installation or use of this equipment, and is not responsible for problems resulting from improper 
or irresponsible use of this device. 

 

All examples and diagrams shown in the manual are intended to aid understanding.  They do not guarantee 
operation. 

 

Unitronics accepts no responsibility for actual use of this product based on these examples. 

 

Only qualified service personnel should open this device or carry out repairs. 

 

Please dispose of this product in accordance with local and national standards and regulations. 

 

 

Check the user program before running it. 

 

Do not attempt to use this device with voltage exceeding permissible levels. 

 

Install an external circuit breaker and take all appropriate safety measures against short-circuiting in 
external wiring. 

 

 

Summary of Contents for EX90-DI8-RO8

Page 1: ...r machinery low voltage and EMC Only a technician or engineer trained in the local and national electrical standards should perform tasks associated with the electrical wiring of this device Under no circumstances will Unitronics be liable or responsible for any consequential damage that may arise as a result of installation or use of this equipment and is not responsible for problems resulting fr...

Page 2: ...water or let water leak onto the unit Do not allow debris to fall inside the unit during installation DIN rail mounting 1 Snap the EX90 DI8 RO8 onto the DIN rail as shown below the device will be squarely situated on the DIN rail as shown below 55mm 110mm 122mm 07 06 05 04 03 02 01 00 I7 I4 I5 I6 I3 I2 I1 I0 0V 24V EX90 DI8 RO8 Connecting the OPLC to the EX90 DI8 RO8 An OPLC such as the M90 micro ...

Page 3: ... or any other substance on the stripped wire that might cause the wire strand to break We recommend that you use crimp terminals for wiring Install at maximum distance from high voltage cables and power equipment General Wiring Procedures 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely int...

Page 4: ...ded distance Use wire that is properly sized for the load Wiring Inputs Note that the power supply and input signals must be connected to the same 0V signal pnp source inputs pnp source high speed counter frequency measurer 24VDC Power Supply Circuit Protection Device 0V 24V I7 I4 I5 I6 I3 I2 I1 I0 0V 24V 24VDC Power Supply Circuit Protection Device 0V 24V High speed Counter I7 I4 I5 I6 I3 I2 I1 I...

Page 5: ... 28 8VDC for Logic 1 Input current 7 5mA 24VDC Response time 10mSec Input 7 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Outputs Number of outputs 8 relay Output type SPST NO relay 230VAC 24VDC Type of relay Takamisawa JY 24H K or NAIS Matsushita J...

Page 6: ...surer or as a normal digital input When Input 7 is used as a normal digital input normal input specifications apply 3 Input 6 can function either as the counter s reset or as a normal digital input in either case its specifications are those of a normal digital input Accessories EX1 CA050 0 5 meter communication cable EX1 CA100 1 meter communication cable EX1 CA200 2 meter communication cable EX1 ...

Page 7: ...n module identification number Adapter The formula below is used to assign addresses for I O modules used in conjuction with the M90 OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system wil...

Page 8: ...To order the expansion module that best fits your system contact your local distributor For a list of Unitronics distributors check our website http www unitronic com contact htm ...

Page 9: ...lease dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of this equipment as defined by the European directives for machinery low voltage and EMC Only ...

Page 10: ...ns Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation ...

Page 11: ...Unitronics 3 Screw Mounting The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 12: ...Do not touch live wires Unused pins should not be connected Ignoring this directive may damage the device Double check all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a...

Page 13: ...through the same multi core cable or share the same wire Allow for voltage drop and noise interference with input lines used over an extended distance Use wire that is properly sized for the load Digital Inputs Input wiring top group of inputs Input wiring bottom group of inputs L N 110 220 VAC 110 220 VAC L N ...

Page 14: ...dicators IN Green LEDs Lit when the corresponding input is active See Note 1 Input voltage range 80 to 250VAC 50 60 Hz Nominal Input voltage 110VAC 220VAC ON voltage min 80VAC 160VAC OFF voltage max 30VAC 50VAC Input current 8mA 12mA Response time typical Rise 30mSec Fall 40mSec Environmental IP20 NEMA1 Operating temperature 0 to 50 C 32 to 122 F Storage temperature 20 to 60 C 4 to 140 F Relative ...

Page 15: ...are numbered from 0 7 1 as shown in the figure below 0 1 2 3 4 5 6 7 Expansion module identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to ...

Page 16: ... but not limited to 0implied warranties of merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this document Unitronics assumes no res...

Page 17: ...ing and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and compete...

Page 18: ...corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto th...

Page 19: ...7 03 IO DI8 RO4 IO DI8 RO4 L I O Expansion Modules Unitronics Industrial Automation 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 20: ...k all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Page 21: ...h speed Counter Reset High speed Counter Wiring the Output s Power Supply Outputs Wiring DC supply 1 Connect the positive cable to the V0 terminal and the negative to the 0V terminal A non isolated power supply can be used provided that a 0V signal is connected to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or ...

Page 22: ...between module and OPLC Blinks when the communication link fails Inputs Number of inputs 8 in one group Input type pnp source or npn sink Galvanic isolation None Status indicators IN Green LEDs Lit when the corresponding input is active See Note 1 Nominal input voltage 24VDC for IO DI8 RO4 12VDC for IO DI8 RO4 L Input voltage IO DI8 RO4 IO DI8 RO4 L pnp source 0 5VDC for Logic 0 17 28 8VDC for Log...

Page 23: ... L Nominal operating voltage 24VDC 12VDC Operating voltage 20 4 to 28 8VDC 10 2 to 15 6VDC Maximum current consumption 40mA 24VDC 75mA 12VDC Environmental IP20 NEMA1 Operating temperature 0 to 50 C 32 to 122 F Storage temperature 20 to 60 C 4 to 140 F Relative Humidity RH 5 to 95 non condensing Dimensions WxHxD 80mm x 93mm x 60mm 3 15 x 3 66 x 2 362 Weight 164g 5 8oz Mounting Either onto a 35mm DI...

Page 24: ...earing in this document including but not limited to 0implied warranties of merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this d...

Page 25: ...itronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of t...

Page 26: ...derations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during instal...

Page 27: ...odules Unitronics 3 Screw Mounting The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 28: ...k all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Page 29: ...ource or npn sink inputs npn sink inputs pnp source inputs 0V V Circuit Protection Device 0V V npn sink high speed counter frequency measurer pnp source high speed counter frequency measurer 0V V Circuit Protection Device High speed Counter Reset High speed Counter 0V V High speed Counter Reset High speed Counter ...

Page 30: ...ormity to voltage power supply specifications connect the device to a regulated power supply Notes 1 The adapter and output s power supply must be connected to the same 0V signal Outputs Circuit Protection Device L1 L2 L3 115 230VAC V 12 24VDC Output s power supply 0V V N 0V Load See Note 1 Increasing Contact Life Span Both modules have 8 relay outputs To increase the life span of these contacts a...

Page 31: ...Logic 0 0 3VDC 4 3mA for Logic 1 Input current 6mA 24VDC 6mA 12VDC Response time 10mSec typical Input 7 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Outputs Number of outputs 8 relay Output type SPST NO Form A All relays share a common signal Isola...

Page 32: ... are those of a normal digital input Addressing I Os on Expansion Modules Inputs and outputs located on I O expansion modules that are connected to an OPLC are assigned addresses that comprise a letter and a number The letter indicates whether the I O is an input I or an output O The number indicates the I O s location in the system This number relates to both the position of the expansion module ...

Page 33: ...rantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in th...

Page 34: ...r flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto the DIN rail ...

Page 35: ...1 08 IO DI8 TO8 IO DI8 TO8 L I O Expansion Modules Unitronics 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 36: ...ck all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Page 37: ...ed Counter Reset High speed Counter 0V V High speed Counter Reset High speed Counter Wiring the Output s Power Supply Outputs Wiring DC supply 1 Connect the positive cable to the V0 terminal and the negative to the 0V terminal A non isolated power supply can be used provided that a 0V signal is connected to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V ...

Page 38: ... Input current 6mA 24VDC 6mA 12VDC Response time 10mSec typical Input 7 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Outputs Number of outputs 8 pnp source Output type P MOSFET open drain for both 24VDC and 12VDC outputs Galvanic isolation None Out...

Page 39: ...re connected to an OPLC are assigned addresses that comprise a letter and a number The letter indicates whether the I O is an input I or an output O The number indicates the I O s location in the system This number relates to both the position of the expansion module in the system and to the position of the I O on that module Expansion modules are numbered from 0 7 as shown in the figure below 0 1...

Page 40: ...at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of ...

Page 41: ...understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained a...

Page 42: ...rosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto the D...

Page 43: ...7 03 IO DI16 IO DI16 L I O Expansion Modules Unitronics Industrial Automation 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 44: ...Double check all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tigh...

Page 45: ...ounter frequency measurer npn sink I8 I9 I10 I11 I12 I13 I14 I15 P N 0V 0V V Circuit Protection Device High speed Counter Reset High speed Counter pnp source IO DI16 9 8 10 11 12 13 14 15 I7 I6 I5 I4 I3 I2 I1 I0 I8 I9 I10 I11 I12 I13 I14 I15 P N 0V P N 0V 0V V Circuit Protection Device 0V V I8 I9 I10 I11 I12 I13 I14 I15 P N 0V 0V V High speed Counter Reset High speed Counter pnp source input wirin...

Page 46: ... for Logic 0 0 3VDC 4 3mA for Logic 1 Input current 6mA 24VDC 6mA 12VDC Response time 10mSec typical Input 15 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Environmental IP20 NEMA1 Operating temperature 0 to 50 C 32 to 122 F Storage temperature 20 t...

Page 47: ...dule identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will be ad...

Page 48: ...ing in this document including but not limited to 0implied warranties of merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this docu...

Page 49: ...itronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of t...

Page 50: ...sive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto the DIN...

Page 51: ...7 03 IO RO8 IO RO8L I O Expansion Module Unitronics Industrial Automation 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 52: ...eck all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enoug...

Page 53: ...uations or non conformity to voltage power supply specifications connect the device to a regulated power supply Load 0V N 0V N N 0V N 0V V 12 24VDC L1 L2 L3 115 230VAC Circuit Protection Device Load L1 L2 L3 115 230VAC V 12 24VDC 0V N 0V N N 0V N 0V Outputs power supply 0V V POWER Increasing Contact Life Span Both modules have 4 relay outputs To increase the life span of these contacts and protect...

Page 54: ...ation By relay Status Indicators O0 to O7 Red LEDs Lit when the corresponding output is active Output current 5A maximum resistive load 1A maximum inductive load Maximum frequency 10Hz Contact protection External precautions required see above Increasing Contact Life Span Outputs power supply IO RO8 Nominal operating voltage 24VDC Operating voltage 20 4 to 28 8VDC Maximum current consumption 75mA ...

Page 55: ...le identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will be addr...

Page 56: ...g in this document including but not limited to 0implied warranties of merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this docume...

Page 57: ...ion Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installatio...

Page 58: ...rosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto the D...

Page 59: ...5 03 IO RO16 IO RO16 L I O Expansion Modules Unitronics Industrial Automation 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 60: ...nused pins should not be connected Ignoring this directive may damage the device Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin Double check all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscr...

Page 61: ...V terminal A non isolated power supply can be used provided that a 0V signal is connected to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Notes 1 The adapter and output s power supply must be connected to the ...

Page 62: ...tive Output current Resistive Load 3A maximum per output 8A maximum total for common See Note 1 Inductive Load 1A maximum per output 4A maximum total for common See Note 1 Maximum frequency 10Hz Contact protection External precautions required see above Increasing Contact Life Span Outputs power supply IO RO16 Nominal operating voltage 24VDC Operating voltage 20 4 to 28 8VDC Maximum current consum...

Page 63: ... identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the M90 OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will be ad...

Page 64: ...ing in this document including but not limited to 0implied warranties of merchantability and or fitness for a particular use or purpose Unitronics assumes no responsibility for the results direct and or indirect of any misuse of the information appearing in this document nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this docu...

Page 65: ...n the local and national electrical standards should perform tasks associated with the electrical wiring of this device Under no circumstances will Unitronics be liable or responsible for any consequential damage that may arise as a result of installation or use of this equipment and is not responsible for problems resulting from improper or irresponsible use of this device All examples and diagra...

Page 66: ... a minimum space of 10mm between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation DIN rail mounting Snap the device onto the DIN rail as shown below the module will be squarely situated on the DIN rail 60mm 3 5mm 14mm 80mm 93mm 44 5mm Screw Mounting The figure on the ...

Page 67: ...11 00 IO TO16 I O Expansion Module Unitronics Industrial Automation Systems 3 4mm 5 8mm 85mm 80mm 68 4mm 93mm 4mm x2 ...

Page 68: ...f outputs must be connected to the same 0V signal Do not use tin solder or any other substance on the stripped wire that might cause the wire strand to break We recommend that you use crimp terminals for wiring Install at maximum distance from high voltage cables and power equipment General Wiring Procedures 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its w...

Page 69: ...minal and the negative to the 0V terminal A non isolated power supply can be used provided that a 0V signal is connected to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply 0V V1 Circuit Protection Device 0V V0 24...

Page 70: ... is active S C Red LED Lit when an output s load short circuits Operating voltage per group 20 4 to 28 8VDC Nominal operating voltage 24VDC Environmental IP20 Operating temperature 0 to 50 C Storage temperature 20 to 60 C Relative Humidity RH 5 to 95 non condensing Dimensions WxHxD 80mm x 93mm x 60mm Weight 144g 5 08oz Mounting Either onto a 35mm DIN rail or screw mounted Notes 1 When an output is...

Page 71: ...dule identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the M90 OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will b...

Page 72: ...conjunction with the EX A1 adapter 12 bit sign 2 outputs 10V 0 20mA 4 20mA 12 bit 4 inputs 0 10V 0 20mA 4 20mA IO AI4 AO2 Analog I O To order the expansion module that best fits your system contact your local distributor For a list of Unitronics distributors check our website http www unitronic com contact htm 12 bit 4 PT100 50 to 460 C IO PT4 PT 100 8 8 8 8 8 8 8 8 C C C C C C C C o o o o o o o o...

Reviews: