I/O Expansion Modules and Adapters Installation Guide 

 

 

Unitronics 

 

 

Caution 

 This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-

hazardous locations only. 

 

 Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in 

accordance with the authority having jurisdiction. 

 

 WARNING

—Explosion Hazard—substitution of components may impair suitability for Class I, 

Division 2. 

 WARNING 

– EXPLOSION HAZARD – Do not connect or disconnect equipment unless power 

has been switched off or the area is known to be non-hazardous. 

 WARNING 

– Exposure to some chemicals may degrade the sealing properties of material 

used in Relays. 

 This equipment must be installed using wiring methods as required for Class I, Division 2 as 

per the NEC and/or CEC. 

Relay Output Resistance Ratings 

The products listed below contain relay outputs:  

Input/Output expansion modules, Models: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L 

  When these specific products are used in hazardous locations, they are rated at 3A res. 

 

 

 

Certification UL des automates programmables, pour une utilisation en 

environnement à risques, Class I, Division 2, Groups A, B, C et D. 

Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été 
certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D. 

 

Attention 

   Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et                           

D, ou dans Non-dangereux endroits seulement. 

 

 Le câblage des entrées/sorties doit être en accord avec les méthodes  

de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente. 

 

 

AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend 

caduque la certification du produit selon la Classe I, Division 2. 

 AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas 

l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue 
pour être non dangereuse. 

 AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés 

des matériaux utilisés pour l'étanchéité dans les relais.  

 Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I, 

Division 2  NEC et /ou CEC. 
 

Certification de la résistance des sorties relais 

Les produits énumérés ci-dessous contiennent des sorties relais: 

 

Modules d’Extensions d'E/S, modèles: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L. 

 

  Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent  

un courant de 3A charge résistive. 

 

 

 

 

 

Summary of Contents for EX-D16A3-RO8

Page 1: ...read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to compl...

Page 2: ...odules Snap the device onto the DIN rail as shown below the module will be squarely situated on the DIN rail 80mm 3 15 93mm 3 66 44 5mm 1 75 Screw Mounting The figure below is drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 3: ...puts must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin All wiring activities should be performed while power is OFF Use over current protection such as a fuse or circuit breaker to avoid excessive currents into the power supply connection point Unused points should not be connected unless otherwise specified Ignor...

Page 4: ...e that is properly sized for the load Earthing the product To maximize system performance avoid electromagnetic interference as follows Use a metal cabinet Connect the 0V and functional ground points if exist directly to the earth ground of the system Use the shortest less than 1m 3 3 ft and thickest 2 08mm 14AWG min wires possible UL Compliance The following section is relevant to Unitronics prod...

Page 5: ...rence à tous les produits Unitronics portant le symbole UL produits qui ont été certifiés pour une utilisation dans des endroits dangereux Classe I Division 2 Groupes A B C et D Attention Cet équipement est adapté pour une utilisation en Classe I Division 2 Groupes A B C et D ou dans Non dangereux endroits seulement Le câblage des entrées sorties doit être en accord avec les méthodes de câblage se...

Page 6: ...plied including but not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no event shall Unitronics be liable for any special incidental indirect or consequential damages of any kind or any damages whatsoever arising out of or in conn...

Reviews: