Wiring 

 

 

 

 

 

 

 

 

 

 

 

Figure 3: Wiring instructions

 

 

Specifications 

 

 

Operating voltage 

9 to 14 VDC 

Current consumption 

110 mA at 12 VDC 

Interface Proximity Reader 

Wiegand 

according to the card type  

Wiegand 32 bit :

 EM410x Cards 

Wiegand 40 bit : 

Casi-Rusco

 

Automatic Wiegand -

 HID Cards

 

EM410x

  

 
Wiegand 32 description 

32 data bits

 

Pulse width: 100 µs 

Pause: 1 ms 

Wiegand for EM410x Cards 

Casi-Rusco

 

 
Wiegand 40 description 

even  38 data bits + odd parity

 

Pulse width: 100 µs 

Pause: 1 ms 

P1 = even parity calculated over the bits 1 to 19 
P2 = odd parity calculated over the bits 0 to 39 

Wiegand for Casi-Rusco cards

 

 

HID 

 

 
Wiegand 26 

– 37 bit  

Automatic Wiegand according to the HID card type 

Interface Keypad 

Wiegand 26, 30, 34, 40, 42, 58 bit, 
8 bit per key, 6 bit per key, 4 bit per key

 

Wiegand 26 description 

even  24 data bits + odd parity 

Pulse width: 100 µs 

Pause: 1 ms 

P1 = even parity calculated over the bits 2 to 13 
P2 = odd parity calculated over the bits 14 to 25 

Wiegand 30 description 

even  28 data bits + odd parity 

Pulse width: 100 µs 

Pause: 1 ms 

P1 = even parity calculated over the bits 2 to 15 
P2 = odd parity calculated over the bits 16 to 29 

Wiegand 34 description 

even  32 data bits + odd parity 

Pulse width: 100 µs 

Pause: 1 ms 

P1 = even parity calculated over the bits 2 to 17 
P2 = odd parity calculated over the bits 18 to 33 

tamp 

Tamper 

tamp 

Tamper 

LG- 

LED Green minus 

LR- 

LED Red minus 

GND 

Ground 

+12 V 

9 to 14 VDC 

D0 

Data 0 

D1 

Data 1 

gray 

blue 

yellow 

orange 

black 

red 

green 

white 

 

LR- 

D1 

D0 

tamp 

GND 

+12 V 

LG- 

tamp 