background image

1.  Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall.  A fi reclay liner (ASTM C315 or  
equivalent) having a 5/8" minimum wall thickness must be used and it must be at least 12" away from any material  that could catch 
fi re.  Th

  e inside diameter of the fi reclay liner shall be sized for the proper snug fi t of a 6" diameter chimney connector pipe. Th

 e 

fi reclay liner shall run from the outer surface of the brick wall to, but not beyond, the  inner surface of the chimney fl ue and shall be 
fi rmly cemented in place. See Part A of Figure 8.
2.  Use a solid insulated listed factory-built chimney length having an inside diameter of 6" and having 1" or more of solid insulation.  
Th

  ere must be at least a 9" air space between the outer wall of the chimney length and any  combustible materials.  Th

  e inner end of 

the chimney length shall be fl ush with the inside of the masonry chimney fl ue  shall be sealed to the fl ue and to the brick masonry 
penetration with nonwater-soluble refractory cement.  Sheet steel supports which are at least 24 gauge(0.024") in thickness shall be 
securely fastened to wall  surfaces on all sides.  Fasteners between supports and the chimney length shall not penetrate the chimney 
liner. See Part B of Figure 8.
3.  Use a 10" diameter ventilated thimble made of at least 24 gauge(0.024") steel having two 1" air channels.  Th

  e ventilated thimble 

must be separated from combustible materials by a minimum of 6" glass fi ber insulation.  Th

  e opening in the combustible wall shall 

be covered and the thimble supported with sheet steel supports which are at least 24  gauge (0.024") in thickness.  Th

  e sheet steel sup-

ports shall be securely fastened to wall surfaces on all sides and  shall be sized to fi t and hold the chimney section.  Fasteners used to 
secure chimney sections shall not penetrate  chimney fl ue liner.  See Part C of Figure 8.
4.  Use an 8" inside diameter solid insulated listed factory-built chimney length which has 1" or more of solid insulation. Th

 e 

minimum length of this chimney section shall be 12" and will serve as a pass-through for the 6" diameter chimney connector.  Th

 ere 

must be at least a 12" air space between the outer wall of the chimney section and any  combustible materials.  Th

  e chimney section 

shall be concentric with and spaced 1" away from the chimney connector by means of sheet steel support plates on both ends of the 
chimney section.  Th

  e opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet 

steel supports which are at least 24  gauge (0.024") in thickness.  Th

  e sheet steel supports shall be securely fastened to wall surfaces 

on all sides and  shall be sized to fi t and hold the chimney section.  Fasteners used to secure chimney sections shall not penetrate  
chimney fl ue liner. See Part C of Figure 8.
5.  A listed factory-built wall pass-through system may be purchased and installed according to the instructions packaged with it 
to provide a safe method of passing the chimney connector through a combustible wall for connection to a masonry chimney.

Additional requirements pertaining to Figure 8 and the above wall pass-through systems:

1.  Insulation material used as part of wall pass-through system shall be of noncombustible material and shall have a  
thermal conductivity of 1.0 Btu • in./ft .² • °F (4.88 kg • cal/hr • m² • °C) or less
2.  All clearances and thicknesses are minimums:  larger clearances and thickness are acceptable.
3.  A chimney thimble, as shown for 3" and 4" above (Parts C and D respectively of Figure 8) shall be for types "3" and 4" connec-
tions to facilitate removal of the chimney connector for cleaning.  Th

  e chimney thimble shall be of  ASTM  C315  fi reclay with 5/8" 

minimum wall thickness , or material or equivalent durability.  Th

  e inside diameter of the  thimble shall be sized for the proper snug 

fi t of a 6" diameter chimney connector pipe.  Th

  e thimble shall be installed   without  damage to the chimney fl ue.  Th

  e thimble shall 

extend through the chimney wall to, but not beyond, the inner surface of the chim ney fl ue and shall be permanently cemented in 
place with high temperature cement.
4.  A chimney connector to a masonry chimney, except for 2" above (Part B of Figure 8), shall extend through the wall pass-through 
system to the inner face of the chimney fl ue, but not beyond.  It does not have to be fastened in place so long as it cannot accidently 
be pulled out of the chimney or shoved into the chimney fl ue.  If fasteners are used  to secure the chimney connector to a masonry 
chimney, the fasteners shall not penetrate the chimney fl ue liner.
5.  Any material used to close up any opening for the connector shall be noncombustible.

7

MINIMUM 12 IN.
TO COMBUSTIBLES

PART A, FIGURE 8
(FIGURE 8 CONTINUED ON NEXT PAGE)

CHIMNEY FLUE

MINIMUM CHIMNEY CLEARANCE TO
BRICK AND COMBUSTIBLES IS 2 IN.

MINIMUM CLEARANCES 12 IN.
OF BRICK ALL AROUND

CHIMNEY CONNECTOR
TO HEATER

FIRE CLAY LINER
(5/8" MIN. WALL THICKNESS)

MIN. 3-1/2" THICK BRICK
MASONRY WALL

MASONRY CHIMNEY
CONSTRUCTED TO
NFPA 211

Summary of Contents for Logwood 2421

Page 1: ...ME OR TRAILER SAVE THIS MANUAL FOR FUTURE REFERENCE THIS MANUAL WILL HELP YOU TO OBTAIN EFFICIENT DEPENDABLE SERVICE FROM THE HEATER AND ENABLE YOU TO ORDER REPAIR PARTS CORRECTLY KEEP IN A SAFE PLACE...

Page 2: ...Dia For Sheet Metal Screws Adjustable Wrench Screw Driver Blade Type Gloves Safety Glasses MATERIALS 6 Elbow Collar and Thimble As Required 24 gauge min 1 2 Sheet Metal Screws No 10A x 1 2 6 Diameter...

Page 3: ...this heater who is unfamiliar with the correct operation of the heater 9 For further information on using your heater safely obtain a copy of the National Fire Protection Association NFPA publication...

Page 4: ...secure with screw in slot 7 After consulting the installation instructions for minimumclearancestocombustibles locateyourfloor protector accordingly and carefully place the stove in your selected loc...

Page 5: ...ot pass through an attic roof space floor ceiling or similar concealed space Where pas sage through a wall or partition of combustible construction is desired the installation must conform with NFPA 2...

Page 6: ...connected to a masonry chimney by passing through a combustible wall NFPA Standard 211 allows the following wall pass through systems 6 MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 AIRTIGHT CLEANOUT DOOR...

Page 7: ...opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge 0 024 in thickness The sheet steel supports shall...

Page 8: ...INIMUM FACTORY BUILT CHIMNEY LENGTH MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN CHIMNEY LENGTH FLUSH WITH INSIDE OF FLUE NONSOLUBLE REFACTORY CEMENT MASONRY C...

Page 9: ...inlet air control and pour a large quantity of coarse salt baking soda or cool ashes on top of the fire in the firebox CAU TION A chimney fire may cause ignition of wall studs or rafters which you tho...

Page 10: ...RTH PLATE SLIDING DRAFT PLATE DOOR FRAME DOOR MAIN TOP LID LID SUPPORT LID LIFTER FLUE COLLAR SOLID FLUE DAMPER DOOR PINS DRAFT CONTROL KNOB HANDLE LATCH NUTS HANDLE EXTENSION HANDLE BRACKET OWNERS MA...

Page 11: ...given with a required thickness T in inches R 1 k x T c C factor is given R 1 C 2 Determine the R value of proposed alternate floor protector a Use formulas in step 1 above to calculate R value of pro...

Page 12: ...N WRITING ALWAYS GIVE THE FULL MODEL NUMBER WHICH IS ON THE NAME PLATE ATTACHED TO THE BACK OF THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 The P...

Reviews: