Part II - Adjustments

SPANNING THE MoDEL TX200™ TRANSMITTER  uSING THE  

SHuNT CAL FEATuRE 

A feature of the field adjustable transmitter (TX200A) is its span ratio of 5:1. The 
span can be field adjusted using the control buttons located on the transmit

-

ter (see diagram 2) and without removing it from service or the necessity of 
a precise pressure source.  using the following formula and procedure below, 
the transmitter is easily recalibrated to the desired pressure range.

Formula:  Ical = (Cal# x 16/Pcal) + 4 

Formula Key:   

Ical 

is the output current that the user will set, with the  

 

 

shunt cal on, in order to achieve the desired full scale  

 

 

pressure (Pcal).

 

 

Cal#

 is the amount of pressure simulated by turning

 

 

the shunt cal on.  The value is engraved on the TX200  

 

 

housing and written on the Certificate of Calibration.

 

 

Pcal

 is the desired (user defined) full-scale pressure  

 

 

recalibration point.

Procedure:

1) Determine transmitter pressure range for application and apply the above 
formula to get 

Ical

.

Example:

 End-user has a uE transmitter P/n TX200A10s1(0 to 2500 psig /0 

to 172,4 bar range).  For a particular application, a 0-1500 psig (0 to 103,4 
bar)  range  is  desired  using  this  transmitter  -  this  is  the 

Pcal.  

The 

Cal#

 

engraved on the transmitter housing is 424 psi (29,2 bar).  using the formula 
above, 

Ical

 = (424 x 16/1500) +4, the 

Ical

 calculated is 8.52.  When all 

steps below are completed, the transmitter in this example would be spanned 
so that the 4 mA output signal = 0 psig and the 20 mA output signal = 1500 
psig (103,4 bar).

2) Connect the transmitter to a 24 volt-nominal voltage source through a 100 
ohm load resistor (reference Diagram 1A).  Connect a digital voltmeter across 
the terminating resistor.  The output across the resistor will be 100 mVolts/mA.

3) Zero the transmitter (if necessary).

4) Turn the Cal switch to the on position.

5) Adjust the span and Fine span control buttons until the 

Ical

 value appears 

on the digital voltmeter.

6) Turn the Cal switch to the off position.

The transmitter should now be spanned to the desired pressure range.  To 
verify  the  new  pressure  range,  check  that  the  transmitter  output  is  4mA  at 
zero pressure.   next, apply full-scale pressure to the transmitter and check 
that the transmitter output is 20 mA at 

Pcal

.

Diagram 1C

Diagram 2

THE  WIRING  TO  THE  PRESSuRE  TRANSMITTER  MuST  ONLY  bE 

CONNECTED  IN  THE  SAFE  AREA  OR  bY  AN  APPROvED  TERMINAL 

BOX CErTIFIED TO En 60079-0 Or En 60079-1 FOr hAZArDOus 

LOCATIOns/FLAMEPrOOF ATMOsPhErEs. (ATEX rEquIrEMEnTs OnLY)

A 1/2” nPT (male) conduit connection is provided on top of the transmitter 

with 18 AWG, 72” leadwires. The leadwires are color coded as follows:

 

4-20 mA output

 

1-5 VDC output (option M204)

 

red: 

+VDC signal 

red:  +VDC signal

 

Black:   -VDC signal 

Black:  -VDC signal

 

Green:   Earth Ground 

Green:  Earth Ground

 

 

 

Blue:  1-5 V Output

The transmitter may be wired in either a sourcing (see diagram 1A) or sinking 

(see diagram 1B) circuit.  (Option M204 1-5 Volt output, see diagram 1C.)

LoAD IMPEDANCE 

4-20mA output 

1300 ohms max. at 36 VDC

 

700 ohms max at 24 VDC

1-5 V output 

2000 ohms min.

Summary of Contents for TX200

Page 1: ...ading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0 1224 725999 Email ab able co uk Internet www able co uk e procurement www 247able com Registered in England No 01851002 VAT No GB 417 2481 61 ...

Page 2: ...p testing The units may require re adjustment These products do not have any field replaceable parts Any substitution of components may impair suitability for Class I Division 1 TX200 Pressure Transmitter The epoxy resin shall not be subjected to a temperature greater than 125 C Part I Installation Tools Needed Adjustable Wrench Mounting Always locate units where shock vibration and ambient temper...

Page 3: ...would be spanned so that the 4 mA output signal 0 psig and the 20 mA output signal 1500 psig 103 4 bar 2 Connect the transmitter to a 24 volt nominal voltage source through a 100 ohm load resistor Reference Diagram 1A Connect a digital voltmeter across the terminating resistor The output across the resistor will be 100 mVolts mA 3 Zero the transmitter if necessary 4 Turn the Cal switch to the on p...

Page 4: ...6 0 54 13 7 B G 1 2 female 1 3 8 1 01 25 7 C 7 16 20 SAE male 15 16 0 77 19 6 D HM4 Autoclave male 15 16 1 10 27 9 E HM6 Autoclave male 15 16 1 29 32 8 F LM4 Autoclave male 15 16 1 18 30 0 G LM6 Autoclave male 15 16 1 32 33 5 H G 1 4 male 15 16 1 03 26 2 J G 1 2 male 1 3 8 1 78 45 2 Wire Color Coding Red VDC Black VDC Green Earth Ground Blue 1 5 VDC Output Option M204 only 03 0 to 15 psis 04 0 to ...

Page 5: ... on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and work manship and that any such product which is found to b...

Reviews: