background image

IMP120-17

www.ueonline.com

120 Series

Explosion-Proof Pressure and

Differential Pressure Switches 

 

Types

J120, J120K, H121, H121K, H122, H122K

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

IMP120-17

*Proof Pressure:  The maximum pressure to which a pressure sensor 

may be occasionally subjected, which causes no permanent damage 

(e.g., start-up testing).  The unit may require re-gapping. (See Part 

II- Adjustments)

**Over Range Pressure: The maximum pressure to which a pressure 

sensor may be continuously subjected without causing damage and 

maintaining set point repeatability.

***Working Pressure Range The pressure range within which two 

opposing sensors can be safely operated and still maintain set point 

repeatability.

THIS DEVICE DOES NOT HAVE  ANY FIELD  REPLACEABLE 

PARTS. ANY SUBSTITUTION  OF COMPONENTS MAY  IMPAIR 

SUITABILITY FOR CLASS I, DIVISION 1.

The 120 Series pressure and differential pressure switches are 

actuated when a bellows, diaphragm or piston sensor responds to 

a pressure change.  This response at a pre-determined set point(s) 

actuates a SPDT, DPDT or dual SPDT snap-acting microswitch(es), 

which convert the pressure signal into an electrical signal.  Control 

set point(s) may be varied by turning the internal adjustment hex 

(J120 & J120K models) or the external knob and pointer(s) (H121, 

H121K, H122, & H122K models, see picture above) according to the 

procedures outlined. (See Part II - Adjustments)

Please refer to product bulletin for product specifications.   Product 

bulletins may be found at www.ueonline.com.

UE declarations and third party issued certifications are available for 

download at www.ueonline.com/prod_approval.

Date code format on nameplate is “YYWW” for year and week.

Part I -Installation

Tools Needed

–Screwdriver/Adjustable Wrench to 1-1/2”

MOUNTING

TO PREVENT ELECTROSTATIC DISCHARGE, WIPE DOWN COVER 

AND ENCLOSURE OF ANY DUST BUILD UP BEFORE REMOVING 

COVER.
INSTALL DEVICE  WHERE  SHOCK, VIBRATION  AND 

TEMPERATURE FLUCTUATIONS ARE MINIMAL. DO NOT MOUNT 

DEVICE  IN  AMBIENT  TEMPERATURES  THAT EXCEED THE 

LIMITS ON THE NAMEPLATE FOR THE APPROPRIATE AREA

GENERAL

MISUSE  OF  THIS DEVICE MAY CAUSE EXPLOSION  AND 

PERSONAL  INJURY.  THESE  INSTRUCTIONS MUST BE 

THOROUGHLY READ AND UNDERSTOOD BEFORE DEVICE IS   

             INSTALLED.

THIS DEVICE  IS  SUITABLE FOR USE  IN  CLASS I, DIVISION 1, 

GROUPS B, C AND D; CLASS II, DIVISION 1, GROUPS E, F AND 

G; CLASS III; OR NON-HAZARDOUS LOCATIONS ONLY.  

  

            ENCLOSURE TYPE 4X, 7 & 9.

The device has been certified in accordance with the 

applicable requirements of the following standards:

• 

IEC 60079-0, 6

th

 Edition, Revision Date 2013/12

• 

IEC 60079-1, 7

th 

Edition, Revision Date 2014/06

• 

IEC 60079-1, 6

th 

Edition, Issue Date 2007/04

• 

IEC 60079-31, 2

nd 

Edition, Issue Date 2013/11

• 

EN 60079-0:2012+A11:2013

• 

EN 60079-1:2007

• 

EN 60079-31:2014

THIS DEVICE IS ATEX CERTIFIED FOR EQUIPMENT CATEGORY 

2.  SUITABLE FOR APPROPRIATE USE IN GAS ZONE 1 & DUST 

ZONE 21 APPLICATIONS.

 

DEMKO 09 ATEX 0815573X

 

 

0539 IECEx UL 03.0001X

 

II 2 G Ex db IIC T6 Gb

 

II 2 D Ex tb IIIC T85°C Db IP66

 

-40°C ≤ Tamb. ≤ + 75°C

BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED 

FOR COMPATIBILITY  TO  THE  PROCESS MEDIA  IN CONTACT 

WITH THE SENSOR AND WETTED PARTS.

TO  PREVENT  IGNITION  OF HAZARDOUS  ATMOSPHERES, 

DISCONNECT  SUPPLY CIRCUITS BEFORE  OPENING.  KEEP 

COVER TIGHT WHILE CIRCUITS ARE ENERGIZED.

PROOF PRESSURE*  LIMITS STATED IN THE  LITERATURE 

AND ON  NAMEPLATE  MUST NEVER BE EXCEEDED, EVEN BY 

SURGES IN THE SYSTEM.  OCCASIONAL OPERATION OF DEVICE 

UP TO MAXIMUM PRESSURE IS ACCEPTABLE (E.G., START-UP, TESTING).  

CONTINUOUS  OPERATION  SHOULD NOT EXCEED THE DESIGNATED 

OVER RANGE PRESSURE** OR WORKING PRESSURE RANGE***.

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

Summary of Contents for J120

Page 1: ... 1 1 2 MOUNTING TO PREVENT ELECTROSTATIC DISCHARGE WIPE DOWN COVER AND ENCLOSURE OF ANY DUST BUILD UP BEFORE REMOVING COVER INSTALL DEVICE WHERE SHOCK VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL DO NOT MOUNT DEVICE IN AMBIENT TEMPERATURES THAT EXCEED THE LIMITS ON THE NAMEPLATE FOR THE APPROPRIATE AREA GENERAL MISUSE OF THIS DEVICE MAY CAUSE EXPLOSION AND PERSONAL INJURY THESE INSTRUCTIONS ...

Page 2: ...ENT IGNITION OF HAZARDOUS ATMOSPHERES SEAL CONDUIT RUNS WITHIN 18 INCHES OF ENCLOSURE TYPE J120 IS PROVIDED WITH TWO 3 4 NPT ELECTRICAL CONDUIT OPENINGS EITHER OF WHICH OR BOTH CAN BE USED DURING INSTALLATION A 3 4 EXPLOSION PROOF PLUG IS PROVIDED FOR PROPERLY PLUGGING THE UNUSED CONDUIT OPENING THE EXPLOSION PROOF PLUG MUST BE PROPERLY INSTALLED Plug is approved explosion proof with the device as...

Page 3: ...39 15875 and types with option code 1519 incorporate a snap switch with integral adjustment wheel see figure 5 Turning this wheel increases or decreases the pressure rise setting The fall setting remains constant To use the adjustable deadband switch 1 Determine set point and deadband values For example a rising set point of 20 psi with a deadband value of 6 psi 2 Set the falling set point at desi...

Page 4: ...ger hex screw clockwise until microswitch deactuates 4 Continue per following instructions depending on model Models 171 174 521 525 531 535 and 540 548 Turn hex clockwise an additional 1 1 2 flats from this point This will provide a 5 9 mil gap Models 680 701 705 356 376 612 616 270 274 Turn hex clockwise 3 flats from this point approximately 1 2 turn This will provide a 14 16 mil gap Re Gapping ...

Page 5: ...1 2 530 535 8 84 224 5 1 2 550 552 8 81 223 8 1 4 551 553 555 8 34 211 8 1 4 565 567 7 53 191 3 1 1 2 Sanitary 612 616 7 88 200 2 1 4 680 8 13 206 5 1 4 701 705 15622 15834 15839 7 44 189 0 1 4 Differential Pressure 36 39 147 157 367 7 59 192 8 1 4 S147B S157B 7 59 192 8 1 2 455 457 559 8 44 214 4 1 4 540 543 9 34 237 2 1 8 544 548 9 41 239 0 1 8 Types H121 H122 H121K H122K Dimension A Models Inch...

Page 6: ...ld endanger property or personnel For all applications a factory set unit should be tested before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding publi...