Pipe Mounting
Mount the switch directly to the line via the NPT pressure connection.
Vertical Surface Mount
Two holes for #10 screws are provided in the bracket plate.
Conduit Connection
A 7/8” diameter hole has been provided in the bracket plate for mounting a
conduit fitting.
Skeleton Versions J54S, J54AS H54S
Pipe Mounting
Mount the switch directly to the line via the NPT pressure connection.
Vertical Surface Mount
Two openings for #6 screws are provided in the rear of the bracket plate.
(See Figure 1).
WIRING
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT.
WIRE UNITS ACCORDING TO NATIONAL AND LOCAL ELECTRICAL
CODES. MAXIMUM RECOMMENDED WIRE SIZE IS 14 AWG. THE
RECOMMENDED TIGHTENING TORQUE FOR FIELD WIRING TERMINALS IS 7 TO
17 IN-LBS.
ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAMEPLATES
MUST NEVER BE EXCEEDED - OVERLOAD ON A SWITCH CAN CAUSE
FAILURE ON THE FIRST CYCLE.
Bring wires up to the terminals from the rear, so that wires lay along insulator.
The three switch terminals are clearly labeled “common”, “normally open” and
“normally closed”. For optional switches supplied with leadwires, the following color
coding applies:
GENERAL
BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR
COMPATIBILITY BETWEEN THE PROCESS MEDIA AND THE SENSOR
AND WETTED PARTS.
54 Series pressure switches are activated when a bellows, diaphragm or
piston sensor responds to a pressure change. This response, at a pre-deter-
mined set point, actuates one or two snap-acting switch(es), converting the
pressure signal into an electrical signal. Control set point may be varied by
turning the adjustment hex on “J” types or a reference adjustment dial on
“H” types. (See Adjustment -PART II).
PROOF PRESSURE* LIMITS STATED IN THE LITERATURE AND ON
NAMEPLATES MUST NEVER BE EXCEEDED, EVEN BY SURGES IN
THE SYSTEM. OCCASIONAL OPERATION OF UNIT UP TO PROOF
PRESSURE IS ACCEPTABLE (E.G., START-UP, TESTING). CONTINUOUS
OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE.
*PROOF PRESSURE
THE MAXIMUM PRESSURE TO WHICH A PRESSURE SENSOR MAY BE OCCA-
SIONALLY SUBJECTED, WHICH CAUSES NO PERMANENT DAMAGE (E.G., START-
UP, TESTING). THE UNIT MAY REQUIRE RE-GAPPING.
THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS.
Please refer to product bulletin for product specifications. Product bulletins
may be found at www.ueonline.com
Part I - Installation
Tools Needed
Adjustable Wrench
Screwdriver
MouNTING
LOCATE SWITCH WHERE VIBRATION, SHOCK, AND AMBIENT
TEMPERATURE FLUCTUATIONS ARE MINIMAL. TO AVOID DAMAGE TO
SWITCH, ALWAYS HOLD THE WRENCH ON THE WRENCH FLATS OR HEX
PORTION OF THE PRESSURE CONNECTION WHEN TIGHTENING.
The switch can be mounted in any position
.
Enclosed Versions J54, J54A, and H54
Remove cover first by removing the one captive screw located on the front of
the cover.
Figure 1
54 Series
Pressure Switches
Types
Enclosed: J54, J54A, H54
Skeleton: J54S, J54AS, H54S
U N I T E D E L E C T R I C
C O N T R O L S
Installation and Maintenance
Instructions
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties.
IMP54-05
Manual Reset
(Option 1530)
SPDT
Common
Violet
Normally Open
Blue
Normally Closed
Black