Pipe Mounting

Mount the switch directly to the line via the NPT pressure connection.

Vertical Surface Mount

Two holes for #10 screws are provided in the bracket plate.

Conduit Connection

A 7/8” diameter hole has been provided in the bracket plate for mounting a 

conduit fitting.

Skeleton Versions J54S, J54AS H54S

Pipe Mounting

 

Mount the switch directly to the line via the NPT pressure connection.

Vertical Surface Mount 

Two openings for #6 screws are provided in the rear of the bracket plate. 

(See Figure 1).

WIRING

DISCONNECT  ALL  SUPPLY  CIRCUITS  BEFORE  WIRING  UNIT.  

WIRE  UNITS  ACCORDING  TO  NATIONAL  AND  LOCAL  ELECTRICAL 

CODES.    MAXIMUM  RECOMMENDED  WIRE  SIZE  IS  14  AWG.    THE 

RECOMMENDED TIGHTENING TORQUE FOR FIELD WIRING TERMINALS IS 7 TO 

17 IN-LBS.

ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAMEPLATES 

MUST NEVER BE EXCEEDED - OVERLOAD ON A SWITCH CAN CAUSE 

FAILURE ON THE FIRST CYCLE.

Bring wires up to the terminals from the rear, so that wires lay along insulator.

The three switch terminals are clearly labeled “common”, “normally open” and 

“normally closed”. For optional switches supplied with leadwires, the following color  

coding applies:

GENERAL

BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR 

COMPATIBILITY BETWEEN THE PROCESS MEDIA AND THE SENSOR 

AND WETTED PARTS.

54  Series  pressure  switches  are  activated  when  a  bellows,  diaphragm  or 

piston sensor responds to a pressure change. This response, at a pre-deter-

mined set point, actuates one or two snap-acting switch(es), converting the 

pressure signal into an electrical signal. Control set point may be varied by 

turning the adjustment hex on “J” types or a reference adjustment dial on 

“H” types. (See Adjustment -PART II).

PROOF PRESSURE* LIMITS  STATED IN THE LITERATURE  AND ON 

NAMEPLATES  MUST  NEVER  BE  EXCEEDED,  EVEN  BY  SURGES  IN 

THE  SYSTEM.    OCCASIONAL  OPERATION  OF  UNIT  UP  TO  PROOF 

PRESSURE IS ACCEPTABLE (E.G., START-UP, TESTING). CONTINUOUS 

OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE.
*PROOF PRESSURE

THE  MAXIMUM  PRESSURE  TO  WHICH  A  PRESSURE  SENSOR  MAY  BE  OCCA-

SIONALLY SUBJECTED, WHICH CAUSES NO PERMANENT DAMAGE (E.G., START-

UP, TESTING).  THE UNIT MAY REQUIRE RE-GAPPING.

THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS. 

Please refer to product bulletin for product specifications.  Product bulletins 

may be found at www.ueonline.com

Part I - Installation

 

Tools Needed

Adjustable Wrench

Screwdriver

MouNTING

LOCATE  SWITCH  WHERE  VIBRATION,  SHOCK,  AND  AMBIENT 

TEMPERATURE FLUCTUATIONS ARE MINIMAL. TO AVOID DAMAGE TO 

SWITCH, ALWAYS HOLD THE WRENCH ON THE WRENCH FLATS OR HEX 

PORTION OF THE PRESSURE CONNECTION WHEN TIGHTENING.

The switch can be mounted in any position

.

Enclosed Versions J54, J54A, and H54

Remove cover first by removing the one captive screw located on the front of 

the cover.

Figure 1

54 Series

Pressure Switches

Types 

Enclosed: J54, J54A, H54

Skeleton: J54S, J54AS, H54S

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

IMP54-05

 

 

 

Manual Reset

 (Option 1530)

 

 

 

SPDT

Common   

 

Violet 

Normally Open 

 

Blue

Normally Closed 

 

Black

Summary of Contents for 54 Series

Page 1: ...the pressure signal into an electrical signal Control set point may be varied by turning the adjustment hex on J types or a reference adjustment dial on H types See Adjustment PART II PROOF PRESSURE LIMITS STATED IN THE LITERATURE AND ON NAMEPLATES MUST never be exceeded even by surges in The system Occasional operation of unit up to proof pressure is acceptable e g start up testing continuous ope...

Page 2: ...n end wrench turn main adjustment screw counterclockwise right to lower set point or clockwise left to raise set point Turning the 1 4 hex screw clockwise until high set switch transfers at the target pressure point provides a pressure rise set point See Figure 4 Low Set of Range Usinga1 4 openendwrench turn lowset adjustmentscrewcounterclockwise right to lower set point or clockwise left to raise...

Page 3: ...J54S models 610 614 Type J54S models 22 28 Type H54 J54 J54A models 22 28 Type H54S models 22 28 Type J54 models 610 614 Dimensions Dimensional drawings for all models may be found at www ueonline com Type H54 J54 J54A models 126 164 ...

Page 4: ...for critical applications where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRAN...

Reviews: