background image

IM_1XTXSW-08

www.ueonline.com

26

U N I T E D   E L E C T R I C   
C O N T R O L S

180 Dexter Ave. P.O. Box 9143, Watertown, MA  02472-9143 USA
617 926-1000    Fax 617 926-2568

www.ueonline.com

RECOMMENDED PRACTICES AND WARNINGS 

United Electric Controls Company recommends careful consideration 
of the following factors when specifying and installing UE pressure and temperature 
units. Before installing a unit, the Installation and Maintenance instructions provided 
with unit must be read and understood. 

•  To avoid damaging unit, proof pressure and maximum temperature limits stated in 

literature and on nameplates must never be exceeded, even by surges in the system. 
Operation of the unit up to maximum pressure or temperature is acceptable on a lim-
ited basis (e.g., start-up, testing) but continuous operation must be restricted to the 
designated adjustable range. Excessive cycling at maximum pressure or temperature 
limits could reduce sensor life.

•  A back-up unit is necessary for applications where damage to a primary unit could 

endanger life, limb or property. A high or low limit switch is necessary for applica-
tions where a dangerous runaway condition could result.

•  The adjustable range must be selected so that incorrect, inadvertent or malicious 

setting at any range point cannot result in an unsafe system condition.  

•  Install unit where shock, vibration and ambient temperature fluctuations will not 

damage unit or affect operation. When applicable, orient unit so that moisture does 
not enter the enclosure via the electrical connection. When appropriate, this entry 
point should be sealed to prevent moisture entry.

•  Unit must not be altered or modified after shipment. Consult UE if modification is 

necessary.  

•  Monitor operation to observe warning signs of possible damage to unit, such as 

drift in set point or faulty display.  Check unit immediately.

•  Preventative maintenance and periodic testing is necessary for critical applications 

where damage could endanger property or personnel.

•  Electrical  ratings  stated  in  literature  and  on  nameplate  must  not  be  exceeded. 

Overload on a switch can cause damage, even on the first cycle.  Wire unit accord-
ing to local and national electrical codes, using wire size recommended in installa-
tion sheet.

•  Do not mount unit in ambient temp. exceeding published limits.

LIMITED WARRANTY

Seller warrants  that  the  product  hereby  purchased is,  upon  delivery,  free from  defects 
in  material  and  workmanship  and  that  any  such  product  which  is  found  to  be  defec-
tive in such workmanship or material will be repaired or replaced by Seller (Ex-works, 
Factory, Watertown, Massachusetts. INCOTERMS); provided, however, that this warranty 
applies only to equipment found to be so defective within a period of 24 months from 
the  date  of  manufacture  by  the  Seller  (36  months  for  the  Spectra  12  and  One  Series 
products;  18  months  for  Temperature  Sensors).  Seller  shall  not  be  obligated  under 
this  warranty  for  alleged  defects  which  examination  discloses  are  due  to  tampering, 
misuse,  neglect,  improper  storage,  and  in  any  case  where  products  are  disassembled 
by  anyone  other  than  authorized  Seller’s  representatives.  EXCEPT  FOR  THE  LIMITED 
WARRANTY  OF  REPAIR  AND  REPLACEMENT  STATED  ABOVE,  SELLER  DISCLAIMS 
ALL  WARRANTIES  WHATSOEVER  WITH  RESPECT  TO  THE  PRODUCT,  INCLUDING  ALL 
IMPLIED  WARRANTIES  OF  MERCHANTABILITY  OR  FITNESS  FOR  ANY  PARTICULAR 
PURPOSE. 

LIMITATION OF SELLER’S LIABILITY

Seller’s liability to Buyer for any loss or claim, including liability incurred in connection 
with (i) breach of any warranty whatsoever, expressed or implied, (ii) a breach of contract, 
(iii) a negligent act or acts (or negligent failure to act) committed by Seller, or (iv) an act 
for which strict liability will be inputted to seller, is limited to the “limited warranty” of 
repair and/or replacement as so stated in our warranty of product.  In no event shall the 
Seller be liable for any special, indirect, consequential or other damages of a like general 
nature, including, without limitation, loss of profits or production, or loss or expenses of 
any nature incurred by the buyer or any third party.
UE specifications subject to change without notice.

CP08113000

ECN #: 6476

Summary of Contents for 1XTX00

Page 1: ...International Flameproof Cert Number UL File E226592 DEMKO 09 ATEX 0813748X IECEx UL 08 0017X Applicable Standards UL 1203 UL 60079 0 UL 60079 1 UL 61010 1 UL 50 UL 50E CSA C22 2 No 25 CSA C22 2 No 60079 0 11 CSA C22 2 No 60079 1 11 CSA C22 2 No 61010 1 12 CSA C22 2 No 94 01 07 CSA C22 2 No 94 2 07 CSA C22 2 No 30 EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 31 2014 IEC 60079 0 Ed 6 2011 06 C...

Page 2: ...ED WITHIN THE LITERATURE AND ON DEVICE NAMEPLATE Over Range Pressure The maximum pressure to which a pressure sensor may be continuously subjected without cause damage and maintaining set point repeatability Max Working Pressure The maximum that can be applied to both process ports simultaneously without affecting sensor performance The One Series transmitter switch product line is based on an all...

Page 3: ...isplay mode after scrolling ALARM CONDITION When the process goes beyond the set point the display will begin to flash alternating between the process value and SW1 SW2 The display will continue to flash until the process has returned to a value beyond the deadband at which point the display will revert to normal operation and process value display If the unit was programmed to have a latching out...

Page 4: ... damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corrosion resistant material 5 threads engaged minimum with thread sealant is required to maintain enclosure type 4X IP66 For Remote Sensing Route the extension wire to avoid contact with live components or close proximity to electrical noise ...

Page 5: ...ovided inside the base enclosure Cleaning the display and keypad surface should be performed with a damp cloth only Do not attempt to wash down the One Series with the cover removed WIRING FOR FLAMEPROOF NON INCENDIVE INSTALLATIONS Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NO...

Page 6: ...polar ity must be observed Connections to the relays and the health status signal are optional not required NOTE As an alternative to loop power model 1XTXSW may be wired directly to a 24 VDC power supply and minus terminals see Figure 7 Page 7 In this wiring configuration power is provided for all switching and diagnostic func tions but the 4 20 mA analog output is not used The digital display wi...

Page 7: ...r Analog Inputs Ain1 24 VDC Loop Power RED TB1 Power Supply 24 VDC PowerOptions TB 2 TB3 TB 2 TB2 3 3 SW1 SW2 TB3 Logic Solver Discrete Inputs Din1 Din2 Din3 Din4 Din5 Din6 DC Common 24 VDC 0 3 A max TB3 This diagram provides an example wiring scheme for SW1 SW2 and IAW OUTPUT switches SW1 is connected to an external load providing a means to switch a local device e g lamp horn etc to provide a wa...

Page 8: ...nnect with no external load resistor NOTE Before attempting to change the polling address UE recommends installing the One Series device descriptions DDs on your handheld or software application Installation instructions for Device Descriptions DD as well as DD files may be found at www ueonline com products hazard ous location one series under HART Protocol Resources Once the DDs have been proper...

Page 9: ...3 8 863 6 36 571 4 909 1 37 619 0 945 5 38 666 7 1000 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperature sensor is subject to 103 25 to 110 of range or when the pressure sensor is subject to 103 25 to 150 of range Fault 0 FAULT CURRENT A diagnostic fa...

Page 10: ... The factory defualt password is 0000 The left 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR MAX MIN or MAN RSET if Latch is set will appear on the display This is the first command prompt in the Programming Mode NOTE The One Series will automatic...

Page 11: ...ecified by set point high and set point low Please use the Switch Decision Logic Figure 13 page 12 for help with setting the appropriate switch mode Press and release the left 2 button until the desired mode appears Press the right g button to select the mode and move on to the set point SP will appear NOTE ThesetpointistheprocessvalueatwhichtheOneSeriesopensorclosestheSW1andSW2switch TheSetPointi...

Page 12: ...SP DB SP DB Open Open Closed Closed Closed DBH DBL SPH SPL Open on Rise Open on Fall Window Open Open Open Open Closed Closed Close on Fall Close on Rise Switch Mode Open Closed Closed Open Open Open Window Close Window Figure 13 Resetting the Maximum Minimum Values The One Series continuously captures the readings from the sensor and stores one minimum and maximum value since the last time they w...

Page 13: ... factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to enter the new offset and return to the main menu Adjusting Span SPAN provides an adjustment to shift the slope of the sensor s response curve to accommodate an offset value other than zero To adjust SPAN calculate and enter a new SPAN va...

Page 14: ...s port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are configurable If the process variable does not change by the amount and selected time period the display will indicate PLUG and the IAW Output will open indicating a fault Refer to the Programming Flowchart on page 21 Enter the Programming Mode and press the left 2 button u...

Page 15: ...lable selections are as follows Pressure Models OFF Default Temperature Models 1 2 second 1 4 second 1 second 1 2 second 2 seconds 1 second 2 seconds Using the left 2 button select a time constant Press the right g button to enter the time constant and return to main menu NOTE The One Series typically responds to a process value change in less that 100 milliseconds when the Filter is set to off Us...

Page 16: ...eft 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digit This process value must be between 3 and 25 of the sensor s maximum range Press the right g button to enter the new scale and return to the main menu Setting the 20 mA portion of the scale see Figure...

Page 17: ...rrent Universal 6 Write Polling Address Universal 7 Read Loop Configuration Universal 8 Read Dynamic Variable Classifications Universal 9 Read Device Variables with Status Universal 11 Read Unique Identifier Associated with Tag Universal 12 Read Message Universal 13 Read Tag Descriptor Date Universal 14 Read Primary Variable Transducer Information Universal 15 Read Device Information Universal 16 ...

Page 18: ... Reads the value of the trip counters associated with switch 1 and switch 2 Trips 1 and 2 The number is an unsigned 16 bit integer between 0 9999 Device Specific 225 Manual Reset Resets one or more switches that are in the latched state Device Specific 226 Read Switch Latch Status Reads the latch status of one or more switches Device Specific 244 Write Switch Configuration Write Switch Number Mode...

Page 19: ...l sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagnostic Fault Relay Monitor The relay output fault monitor circuit has detected that the output state of the solid state relay is incorrect This feature must be enabled in the menu Check the wiring connections or d...

Page 20: ...al Model 1XTXSW Only LOST PASSWORDS Contact UE Inside Sales at 1 617 923 6977 or go online at www UEonline com UUC to obtain a unique unlock code The Kanban number from the product nameplate is required see Figure 16 Table 7 Table 8 THIS DOCUMENT IS PROPRIETARY PROPERTY OF UNITED ELECTRIC CONTROLS UNAUTHORIZED USE IS STRICTLY PROHIBITED TOLERANCES ON FRACTIONS 1 64 1 2 0 010 0 005 2 PLACE DEC 3 PL...

Page 21: ...nd Dead Band Low Details of entry are similar above OFST POS NEG Offset out of Range Flash Err 8888 Set Blinking Digit Increments of Blinking Digit Sets Digit and moves to the next SPAN POS NEG SPAN out of Range Flash Err 8888 Set Blinking Digit Increments of Blinking Digit Sets Digit and moves to the next LCH1 2 ON OFF PLUG PORT OFF 1MIN 1HR 24HR 8888 Set Blinking Digit Increments of Blinking Dig...

Page 22: ... PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 264 16 mm 203 2 mm 137 16 mm 129 54 mm 134 62 mm 137 16 mm 76 2 mm 92 20 mm 129 54 mm 134 62 mm 137 16 mm 107 95 mm 61 91 mm 158 75 mm 7 11 mm 107 95 mm 76 2 mm 6 35 mm 8 73 mm DIMENSIONAL DRAWINGS GAGE ...

Page 23: ...LATED CABLE Ø0 125 3 18 mm FOR DC UNITS Ø0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT PIPE NIPPLE 300 SERIES st st 0 50 12 7 mm Temperature Sensors Remote TR1 TRC TH1 THC TC1 TCC SENSOR OPTIONS Spring Loaded Local TTC Fixed Local TL1 TL3 Differential Pressure 1 4 18 NPT MALE BOTH EN...

Page 24: ...in may come in contact with the enclosure Installez les unités où le choc vibration et les fluctuations de température sont minimes Orienter l unité d une manière à empêcher l humidité de pénétrer dans l enceinte Utiliser des raccords d étanchéité bien notés pour l entrée de fil électrique Ne pas monter l unité à des températures ambiantes dépassant les limites publiées Cela est particulièrement i...

Page 25: ...losure cover Keep cover tight while in operation Do not disconnect equipment unless power has been switched off or the area is known to non hazardous Pour éviter l inflammation couper l alimentation avant de retirer le couvercle du boîtier Maintenir le couvercle fermé pendant le fonc coupée ou que la zone est connue pour être non explosives 5 Do not replace components unless power has been switche...

Page 26: ... personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national electrical codes using wire size recommended in installa tion sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon de...

Reviews: