United CoolAir VFD Installation, Operation And Maintenance Manual Download Page 4

Installation, Operation and Maintenance Manual

Field Installed Variable Frequency Drives (VFD’s

4

Subject to change without notice.

120.7-IM (1218)

General Information

Inspection of Equipment

Upon receiving of the variable frequency drive (VFD), 

carefully inspect for visible or concealed interior/exterior 

damage� If damage occurred during transit, contact the 

freight carrier immediately and file a damage claim report.
Inspect the unit data plate to verify the VFD is the appropriate 

one for the application� (Voltage, VFD and Evaporator Motor 

HP are compatible)
Some options/accessory items may have been shipped 

loose in one or more boxes� These may have been delivered 

to another location, or possibly within the unit� If shipped with 

the  unit  there  will  be  a  sticker  that  identifies  where  in  the 

unit the shipped loose items are located. Confirm that all of 

these options/accessory items are also available and that no 

damage has occurred�

Handling

Handle the VFD as prescribed by the VFD manufacturer�

Location

Before VFD can be installed, a thorough study should be 

made� Attention must be given to:

A. 

Wall, panel or structure load limitations are appropriate

B. 

Required service clearances are present

C. 

Location of wiring and safety devices is acceptable

D. 

Temperature and humidity levels will be within 

manufacturer tolerances

E. 

Mounting location is as recommended by the VFD 

manufacturer

F. 

Confirm that the mounting location will not subject the 

VFD to any moisture

G. 

Make sure that adequate ventilation is provided as 

recommended by the VFD manufacturer

H. 

Device will not be located near heat radiating elements

I. 

Make sure all power wiring and control wiring can be 

separated per industry accepted practices

Programming

Refer to the manual with the VFD for programming and 

troubleshooting instructions�

INFORMATION

Confirm  that  the  incoming  power  supply 

matches the unit and VFD data tags�

ELECTRICAL HAZARD

Only  a  qualified  licensed  electrician  or 

other individual that is properly trained in 

handling live electrical components should 

perform any installation, adjustment, 

repair or maintenance� Failure to follow all 

electrical safety precautions and industry 

accepted practices when exposed to 

live electrical components could result in 

death or serious injury�

INFORMATION

Use Copper Conductors Only� Failure 

to use copper conductors may result in 

equipment damage�

INFORMATION

All electrical wiring must be in accordance 

with NEC (National Electrical Code), NFPA 

(National Fire Protection Agency) most 

current versions as well as any applicable 

state or local codes�

INFORMATION

The correct phase sequence of the 

incoming power supply is a requirement� 

If the phase sequence is not correct it 

could cause damage or failure to electrical 

components� Reverse the incoming wiring 

to resolve the issue� Do not switch any 

internal unit wiring�

INFORMATION

Unit wiring and components have been 

designed  for  the  specific  unit  application 

and factory assigned controls� Do not use 

the unit transformers or alter the unit wiring 

to interface any field supplied accessories 

or controls�

Summary of Contents for VFD

Page 1: ...Variable Frequency Drive Field Installation Installation Operation and Maintenance Manual Effective December 2018 Interactive PDF DISCONTINUED For Reference Only ...

Page 2: ...ION 3 General Information 4 Inspection of Equipment 4 Handling 4 Location 4 Programming 4 Voltage Unbalance 5 Field Provided VFD Field Installed 6 Field Provided VFD Field Installed Continued 7 Static Pressure Transducer 7 Field or Factory Provided Field Installed 7 Field Provided VFD Field Installed Continued 8 Factory Provided VFD Field Installed 9 Field Provided VFD Field Installed Continued 10...

Page 3: ...which may result in minor or moderate injury if not avoided The information icon indicates a situation that may result in equipment or property damage The information provided alerts the reader to relevant facts and or conditions ELECTRICAL HAZARD WARNING CAUTION INFORMATION This publication includes warnings cautions and information icons that point out safety related issues or conditions as well...

Page 4: ...ect the VFD to any moisture G Make sure that adequate ventilation is provided as recommended by the VFD manufacturer H Device will not be located near heat radiating elements I Make sure all power wiring and control wiring can be separated per industry accepted practices Programming Refer to the manual with the VFD for programming and troubleshooting instructions INFORMATION Confirm that the incom...

Page 5: ...m desirable voltage unbalance is 2 0 When testing for voltage unbalance the phase to phase voltages should be measured rather than the phase to neutral voltages since 3 phase motors are connected across phases Use the following formula to determine the percent of voltage unbalance Percent Voltage Unbalance 100 x Maximum Voltage Deviation Average Voltage Example Phase Phase voltages A 8 479V 8 C 47...

Page 6: ...f the motor side power block to prevent wiring the VFD backwards Refer to Figure 1A or 1B WARNING Severe damage and personal injury may result if jumpers are not removed INFORMATION All field supplied wiring is to be sized per NEC or applicable local codes 6 Attach the appropriate size wire to the power block motor side and connect them to the terminals on the VFD marked for the Motor U V W Refer ...

Page 7: ...n making sure that the pneumatic tube connections are at the bottom This helps to prevent moisture from reaching the transducer 2 Attach field supplied pneumatic tubing to the HIGH connection of the transducer Refer to Figure 3 3 Route the pneumatic tubing to a point approximately 2 3rds of the distance down the straightest length of supply air ducting Make certain that there are no kinks in the t...

Page 8: ...nual Field Installed Variable Frequency Drives VFD s 8 Subject to change without notice 120 7 IM 1218 Field Provided VFD Field Installed Continued Figure 2A After VFD Installed Motor w Overload Figure 2B After VFD Installed Motor w o Overload ...

Page 9: ...motor side power block to prevent wiring the VFD backwards Refer to Figure 3 WARNING Severe damage and personal injury may result if jumpers are not removed 6 Attach the appropriate size wire to the power block motor side and connect them to the terminals on the VFD marked for the motor U V W Refer to Figure 4 INFORMATION Damage to VFD may occur if not correctly wired 7 Attach the appropriate size...

Page 10: ...nual Field Installed Variable Frequency Drives VFD s 10 Subject to change without notice 120 7 IM 1218 Field Provided VFD Field Installed Continued Figure 4A After VFD Installed Motor w Overload Figure 4B After VFD Installed Motor w o Overload ...

Page 11: ...Installation Operation and Maintenance Manual Field Installed Variable Frequency Drives VFD s 11 Subject to change without notice 120 7 IM 1218 NOTES ...

Page 12: ...or All Indoor HVAC Projects Authorized Distributor LIMITED WARRANTY United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor labor not included Maintenance items such as filters and belts are excluded under this limited warranty FACTORY TESTED All units are functionally run tested before shipment to ensure a trouble free start up and uni...

Reviews: