Installation, Operation and Maintenance Manual
Marvel Plus
20
Subject to change without notice.
120.5-IM (1018)
U01
Manual Analog-Out
VFD Input Auto
00.0vdc
Dig Cmpr1 Auto
0.0vdc
Dig Cmpr2 OFF
0.0vdc
DPC Valve OFF
00.0vdc
Air Econo OFF
00.0vdc
WSE Valve Auto
00.0vdc
Sensor Calibration
The sensor screens allow for calibration of temperature,
humidity, and pressure sensors� The sensor screens are
also used to adjust sensor ranges so that for instance if the
low end of a static pressure transducer is 0�0” w�c�, and it
starts at 4 mA, then the start point would be 4 mA is 0�0” w�c�
U01
Calibrate Sensor
Return Temperature
Calibration >
000.0°F
Actual >
000.5°F
U01
Calibrate Sensor
Return Humidity
Calibration >
000.0%
Actual >
050.1%
U01
Calibrate Sensor
Supply Temperature
Calibration >
000.0°F
Actual >
054.5°F
U01
Calibrate Sensor
Ambient Temperature
Calibration >
000.0°F
Actual >
041.2°F
U01
Calibrate Sensor
Ambient Humidity
Calibration >
000.0%
Actual >
051.9%
U01
Calibrate Sensor
Water Temperature
Calibration >
000.0°F
Actual >
043.6°F
U01
Sensor Setup
Duct Pressure
Calibration >
0.00iwc
Actual >
0.69iwc
4ma >
0.00iwc
20ma >
5.00iwc