5. Wiring Connection
1. Choose the appropriate conduit in accordance with all applicable, local, and electrical
safety codes and standards. The connection into the enclosure is 1.3 inches in diameter.
2. Using the appropriate tool, clamp the ring wire terminal to the copper wire. For non-
insulated terminals, use heat shrink tube to cover the non-insulated portion of the
terminal. Choose a terminal ring with the following characteristics:
»
Recommended Wire Strip length: 8mm (0.32in)
»
Width of the terminal block opening: 10.2mm (0.41in)
»
Mouth Size: 6.5mm (0.26in)
3. Remove the front cover by removing the 4 screws at each corner of the charging station.
4. Loosen the plastic cable gland beneath the charger.
5. Loosen strain relief clamp on inside of charger. Use a screwdriver or other tool to break
and remove metal clamp.
6. Use Philips screwdriver to release terminal screws of the NEMA 6-50 or NEMA 14-50 input
cable. Remove the input cable and cable gland.
7. Insert the wire end passing through the conduit and insert them into the input wiring
hole. (Use Red wire for L1, Black wire for L2, Green wire for G). Attach the terminal to the
corresponding terminal block. Use the following wire and torque force when connecting to
input terminal block:
5.1 Optional Hardwire Connection
Terminal
L1, L2, G
Conductor
6-8 AWG
(10AWG for ground)
Screw
M4
Rating
75°C
copper wire
Torque
max 1.8Nm | 16 LBF.IN